User Guide
Viewing Battery and Monitor Status
23-17
Select String Memos and Cell Memos to include string and cell memos.
Select Include Power to list power in reports, in addition to voltage and current.
Select Standard to create a standard report. Cells are listed by string, and strings are listed by
time in a Cell = Value format.
Select Tabular to create a tabular report, which is the same as a standard report, but in a
spreadsheet format, with Cells vs. Time.
Click Cell Graph to create a report that includes a cell graph.
Click Cell Detail to create a report that includes cell detail.
Click OV/I Graph to create a report that includes Overall Voltage and Load Current graphs.
MPM Current to Include in Report (MPM only) - Choose up to four current
channels Current 1 to Current 4 to view simultaneously if they are connected.
The Discharge Dates columns list the Start Date/Time, Duration, Lowest OV, OV@30 and
ACV@30 of all discharges. The Lowest OV column lists the lowest value reached during
discharge. OV@30 lists the overall voltage 30 seconds into discharge, and ACV@30 lists the
average cell voltage 30 seconds into discharge. Click the discharge for which the report will
be generated. Only one discharge date may be selected for a report.
Cell Detail area - To manually select cells to include in the report, click the cells in the list or
click All to select all items. If Auto Select is selected, cells that violate thresholds are already
selected. To clear all selected items, click None. If more than one subdirectory of cell data is
available, tabs for each subdirectory appear above the list of cell names.
After all options are selected, click the Preview button to create a report and display it on the
Preview screen. Refer to Using the Preview Screens.
Adjust the Replay Speed slider to have a replay run faster or slower. You may do this while
the replay is in process.
String View > Start resistance test or Stop resistance test or Get test results
If View|Load Test was selected, to start a load test and capture new readings, click Start.
After the Test in Progress message disappears, the Get button becomes active. Click Get to
retrieve the readings and transfer them to the computer. To stop the test before completion,
click Stop.
If View|Discharge was selected, to retrieve new discharge readings, click Get to display the
readings and transfer them to the computer. You cannot start a discharge test from this screen.
Options selected on the All Discharge screen are saved by the battery name.
After selecting a discharge from the list by clicking it, you can perform two types of analysis.
Click Discharge Replay to play back the discharge. Click Discharge Curve to display line
graphs of up to three specified parameters.