User Guide
Viewing Battery and Monitor Status
23-15
23.13. Alarm Acknowledge
String View > View alarm or View|Alarm then Acknowledge alarm
If the alarm acknowledge options are selected on Setup|System|Reporting and
Setup|Battery|General, the Acknowledge Alarm button appears on the Current Alarm screen,
and, to indicate an alarm event, the String Status screen displays Acknowledge in the
String Status column. You may acknowledge alarms three ways:
1. Press the alarm reset button on the MPM or BDS monitor, or
2. On the Current Alarm screen, click the Acknowledge Alarm button, or
3. On the String Status screen, right click the mouse and click Acknowledge Alarm on the
pop-up menu.
23.14. Discharge Data
String View > View load test or View|Load test
String View > View discharge
or View|Discharge
Click Load Test (MPM only) or Discharge to display the All Load Tests or All Discharges
screens, which list records of load tests or discharges for the connected string. View Load
Test lists discharges detected by user-programmed tests. View Discharge lists automatically
detected discharges. If String Status on the bottom left of the String View screen indicates
Discharging, Logging Discharge Data or R-test in Progress, View Discharge and View Load
Test cannot be selected.