User Guide

Viewing Battery and Monitor Status
23-7
23.7. Cell Voltage (String View Screen)
String View > Cell voltage (default)
The String View Cell Voltage screen bar graph shows the voltage of each cell or module
within the battery. A readings summary appears at the bottom. The cells with the maximum
and minimum values are indicated as Max(n) and Min(n). If current channel and temperature
transducers are installed, these readings also appear. If you click a bar on the graph, the cell
voltage value appears in the box near the top left.
Figure 98. String View - Cell Voltages (MPM shown)
Clicking certain text in the lower portion of the String View screen displays screens related to
the item clicked. For example, clicking Other Parameters - Overall Voltage displays the
Overall Voltage Trend screen.
If the Peukert number is enabled for the MPM under Battery|Setup|Discharge, the screen
displays the TTG (Time to Go) and Discharge Duration boxes. During discharge, TTG
gives an estimate of the discharge time remaining, based on user-entered data.
Discharge Duration indicates the time that has elapsed since the start of the discharge.
IMPORTANT NOTE: The TTG Time to Go is only an estimate.
When in discharge mode, if a cell goes negative, the respective bar on the bar graph is
displayed in black.