User Guide
Programming Battery Setup for the BDS
20-7
1x60x6V 1 30 5 6 6 1
2 30 5 6 6 6
1x62x6V 1 30 5 6 6 1
2 32 5 6 8 6
1x65x6V 1 32 4 8 8 1
2 33 4 8 9 5
1x78x6V 1 40 5 8 8 1
2 38 5 8 6 6
1x80x6V 1 40 5 8 8 1
2 40 5 8 8 6
1x81x6V 1 40 5 8 8 1
2 41 5 8 9 6
1x60x8V 1 30 5 6 6 1
2 30 5 6 6 6
1x61x8V 1 30 5 6 6 1
2 31 5 6 7 6
1x30x12V 1 30 10 3 3 1
1x31x12V 1 31 10 3 4 1
1x32x12V 1 32 8 4 4 1
1x33x12V 1 33 10 3 6 1
1x36x12V 1 36 9 4 4 1
1x40x12V 1 40 10 4 4 1
Figure 81. BDS Configuration Data for Setup Files (continued)
Parameter / Enabled - The OV, DC and FC parameters are assigned to DCM #1. Select
Enabled to view the parameter in String View and enable the hardware.
OV - Overall Volts. Not available for BDS-40.
DC - Discharge Current.
FC - Float Current.
Cell Voltage - From the drop-down list, select the nominal voltage of the cell or jar being
measured.
Intercell Enabled - Select this box if making separate measurements for intercells. Not
available for BDS-40.
Charger IT - Select the enabled check box if using the Charger IT option. This area allows
you to select and assign a cable to a DCM and intertier channel. The Cable+1 is the first
DCM and the Cable -1 is the last DCM.
Note: When intercells are enabled, they are defaulted to discrete. Each cable will have up to
four intertier channels, for example:
<DCM 1> <IT 1>
<DCM 1> <IT 2>
<DCM 1> <IT 3>
<DCM 1> <IT 4>
Note: On combined reading board, the intertier channel number will always start the first
available channel past the cells.
Intertier # / Cell # - For intertiers 1 to 15 in use, assign a cell number that relates to each
intertier.