User Guide

Viewing Battery and Monitor Status
21-7
21.7. Cell Voltage (String View Screen)
String View > Cell voltage (default)
The String View Cell Voltage screen bar graph shows the voltage of each cell or module within the
battery. A readings summary appears at the bottom. The cells with the maximum and minimum
values are indicated as Max(n) and Min(n). If current channel and temperature transducers are
installed, these readings also appear. If you click a bar on the graph, the cell voltage value appears in
the box near the top left.
Figure 80. String View - Cell Voltages (MPM shown)
Clicking certain text in the lower portion of the String View screen displays screens related to the
item clicked. For example, clicking Other Parameters - Overall Voltage displays the Overall Voltage
Trend screen.
If the Peukert number is enabled for the MPM under Battery|Setup|Discharge, the screen displays
the TTG (Time to Go) and Discharge Duration boxes. During discharge, TTG gives an estimate of
the discharge time remaining, based on user-entered data. Discharge Duration indicates the time that
has elapsed since the start of the discharge.
IMPORTANT NOTE: The TTG Time to Go is only an estimate.
When in discharge mode, if a cell goes negative, the respective bar on the bar graph is displayed in
black.