Installation, Operation and Maintenance Manual 8 Liebert SPDs SL-22085 Rev 5, 11/2009
Installation Instructions
1. Insure that all power is removed before beginning installation. A qualified licensed electrician shall install all electrical
connections.
2. The SPD is provided in the enclosure type listed below. NEMA 12 enclosures are suitable for use in indoor installations. NEMA
3R, NEMA 4 or NEMA 4X enclosures are suitable for use in indoor or outdoor installations.
4. The SPD has obtained the short circuit current rating shown below.
Circuit Ampacity Limitations. Representative samples of these products have been investigated by Underwriters Laboratories,
Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents of up to the rating
shown above, as described in the Standard for Safety, Surge Protective Devices (SPDs), Standard 1449, Third Edition, released (2009).
SPD Mounting Hardware SPD Mounting Hardware
Type SI/SH (Page 15) 3/8" Type LM (Page 19) 1/4"
Type H (Page 16) 3/8" Type ACV/AII (Page 16) #8
Type SS (Page 18) 1/4"
SPD Standard Enclosure Optional Enclosures SPD Standard Enclosure Optional Enclosures
Type SI/SH NEMA 4 NEMA 4X Type LM NEMA 12 NEMA 3R, 4, 4X
Type H NEMA 12 NEMA 3R, 4, 4X Type ACV/AII NEMA 4X N/A
Type SS NEMA 4X N/A
3. Determine where the SPD is to be mounted, allowing for minimum length of wire between itself and the input power terminals
of the service panel. Punch or cut the proper hole size in the side of the SPD closest to the knockout to be utilized in the service
panel. Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimensions shown in the
tables on the “Dimensional Information” pages in this manual. Mount surge suppressor using the hardware listed.
SPD Short Circuit Current Rating SPD Short Circuit Current Rating
Type SI/SH 200,000 Symmetrical Amperes Type LM 200,000 Symmetrical Amperes
Type H 200,000 Symmetrical Amperes Type ACV/AII 200,000 Symmetrical Amperes
Type SS 65,000 Symmetrical Amperes
Typical Parallel Installations
Surge Protective Devices (SPD)
Liebert SI Series
(Interceptor II)
Type SI/SH
Liebert HA Series
(Hybrid Advantage)
Type H
Liebert SS Series
(Type SS)
Liebert LM Series
(Type LM)
Liebert ACV Series
(AccuVar)
Liebert LM Series
(Type LM)
Service Panel for
Loads to be Protected
Phase L1/A
Phase L2/B
Phase L3/C
Disconnect/Main
Breaker for
Panel
Neutral Buss
Ground Buss
Dedicated
Disconnect
(Optional)
Recommended Wire
Entrance
E
F
(4X)
B
A
D
C
1.350
Max.
Liebert LM Series
Unit
Dimensions (Inches)
Weight
(lbs)
Suggested
Breaker Size
Suggested
Wire Size
(AWG)
Allowable
Breaker
Range
Allowable
Wire Range
A B C D E F
LM060
LM080
LM100
LM125
LM150
LM200
LM225
LM250
14
14
16
8
8
9
16.75
16.75
21.25
12
12
10
0.31
0.31
0.44
32
41
56
40 A
40 A
100 A
#8
#8
#2
15A –100A #14– #2
16
16
20
Liebert LM Series, with Rotary Disconnect
Unit
Dimensions (Inches)
Weight
(lbs)
Suggested
Breaker Size
Suggested
Wire Size
(AWG)
Allowable
Breaker
Range
Allowable
Wire Range
A B C D E F
LM060
LM080
LM100
LM125
LM150
LM200
LM225
LM250
14
14
16
8
8
9
16.75
16.75
21.25
12
12
10
0.31
0.31
0.44
32
41
56
40 A
40 A
100 A
#8
#8
#2
15A –150A #8 – #1/0
16
16
20
15A –175A
15A –175A
#8 – #1/0
#8 – #1/0
Summary Alarm Contacts (X2)
Pin 1 = Normally Open
Pin 2 = Common
Pin 3 = Normally Closed
TB1 TB2
1 2 3 1 2 3