Surge Protection For Business-Critical Continuity™ Liebert ACV, ACG, ATF, HA, SI, LM, LPGE and Type SS Products Installation, Operation and Maintenance Manual Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 800 877 9222 Phone (US & Canada Only) 614 888 0246 (Outside U.S.) 614 841 6022 FAX Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX Emerson Network Power Asia Pacific 7/F.
Surge Protective Devices Surge Protective Devices LIEBERT SURGE PROTECTIVE DEVICE INSTALLATION, OPERATION AND MAINTENANCE MANUAL Items Not Covered By Warranty: TABLE OF CONTENTS UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Surge Protective Devices Surge Protective Devices Limited Warranty INSTALLATION INSTRUCTIONS The installer should perform the following steps to assure a quality installation. The entire installation manual should be read before starting installation. These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the Liebert SPD system should only be performed by qualified personnel.
Surge Protective Devices Surge Protective Devices ELECTRICAL CONNECTIONS to the supply side of the service disconnect as permitted in 230.82(4) or All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes. (2) Type 1 SPDs shall be permitted to be connected in Type 2 locations as specified in 285.24. (B) At the service.
Surge Protective Devices N VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser’s business. General: Liebert Corporation products and systems are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship.
Surge Protective Devices Surge Protective Devices Typical Parallel Connections (without Internal Rotary Disconnect) Neutral Neutral Phases Phases Ground Ground To Protected ToLoads Protected Loads Neutral Neutral Phase(s) Protected Panel Protected Panel Wire should be less than 5 feet Wire should be and straight less than 5 feet as possible and straight as possible Phase(s) Transient Ground Transient Ground Safety Ground Safety Ground Liebert Surge Liebert Protective Surge Device Protective Device
Surge Protective Devices Example Installations Surge Protective Devices defeats the effectiveness of the SPD, is a potential safety hazard, may cause equipment damage, is an NEC violation (reference NEC 250-51 and 250-54), and is not recommended. System Grounding and Bonding The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment performance.
Surge Protective Devices Surge Protective Devices Troubleshooting / Servicing / Maintenance Troubleshooting If status failure indication occurs or Form C relay has changed states, a qualified electrician shall first determine if the systems voltage and proper phasing exists. Corrective Maintenance The Liebert SPD is designed for years of trouble-free operation. However, even the most reliable equipment may fail under abnormal conditions.
Surge Protective Devices Typical Parallel Installations Liebert LM Series (Type LM) Summary Alarm Contacts (X2) Surge Protective Devices (SPD) Liebert SI Series (Interceptor II) Type SI/SH Pin 1 = Normally Open Pin 2 = Common 2 3 1 2 Phase L1/A Phase L2/B Phase L3/C Service Panel for Loads to be Protected Pin 3 = Normally Closed 1 TB2 E F (4X) Dedicated Disconnect (Optional) C Liebert HA Series (Hybrid Advantage) Type H Liebert SS Series (Type SS) Liebert LM Series (Type LM) Disconnect/
Surge Protective Devices Surge Protective Devices Liebert SS Series (Type SS) 7. An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below (also indicated on the “Dimensional Information” pages in this manual). The SPD shall be connected in accordance with all national and local electrical codes.
Surge Protective Devices Surge Protective Devices Liebert ATF Series (Active Tracking Filter) - Type F F Liebert ATF Series (Active Tracking Filter) — Type F Small Bezel .50” Max. (No Options) A Surge Protective Device (SPD) A D Installation Instructions 1. Ampacity: The filter’s maximum continuous current (Ampere) rating must be greater than or equal to the protected load’s full load amps or overcurrent protection (Circuit Breaker) rating.
Surge Protective Devices Surge Protective Devices Liebert HA Series (Hybrid Advantage) — Type H Typical Series Connections for Wye (4 Wire + Ground) or Single Phase (3 Wire + Ground) System Service Panel for Loads to be Protected Liebert Active Tracking Filter System ’s Neutral (required) N Ground G INPUT OUTPUT Phase (s) Phase (s) Neutral Neutral Safety Ground Disconnect/Main Breaker for Panel Neutral Buss Dedicated Disconnect (Optional) } Transient Ground Phase L1/A Phase L2/B Phase L3/
Surge Protective Devices Surge Protective Devices Dimensional Information Liebert SI Series (Interceptor II) - Type SI/SH Summary Alarm Contacts (X2) Pin 1 = Normally Open Pin 3 = Normally Closed 1 2 3 1 2 Surge Protective Device (SPD) Phase L1/A Phase L2/B Phase L3/C Service Panel for Loads to be Protected Pin 2 = Common TB1 Liebert LPGE Series (PanelGuard Extension) - Type LPGE Disconnect/Main Breaker for Panel Neutral Buss 3 TB2 Dedicated Disconnect (Optional) E C F (4X) Ground Buss
Surge Protective Devices Surge Protective Devices Liebert ACG Series (AccuGuide) — Type ACG Connection The Liebert ACG Series (AccuGuide) assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an additional five feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of the pigtail is based on the SPD lug size. See chart below for units and acceptable wire ranges.
Surge Protective Devices Surge Protective Devices Liebert ACG Series (AccuGuide) — Type ACG Connection The Liebert ACG Series (AccuGuide) assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an additional five feet of #10, 8, 6, or 4 AWG pigtails for connection to the service and to the surge protective device (SPD). Gauge of the pigtail is based on the SPD lug size. See chart below for units and acceptable wire ranges.
Surge Protective Devices Surge Protective Devices Dimensional Information Liebert SI Series (Interceptor II) - Type SI/SH Summary Alarm Contacts (X2) Pin 1 = Normally Open Pin 3 = Normally Closed 1 2 3 1 2 Surge Protective Device (SPD) Phase L1/A Phase L2/B Phase L3/C Service Panel for Loads to be Protected Pin 2 = Common TB1 Liebert LPGE Series (PanelGuard Extension) - Type LPGE Disconnect/Main Breaker for Panel Neutral Buss 3 TB2 Dedicated Disconnect (Optional) E C F (4X) Ground Buss
Surge Protective Devices Surge Protective Devices Liebert HA Series (Hybrid Advantage) — Type H Typical Series Connections for Wye (4 Wire + Ground) or Single Phase (3 Wire + Ground) System Service Panel for Loads to be Protected Liebert Active Tracking Filter System ’s Neutral (required) N Ground G INPUT OUTPUT Phase (s) Phase (s) Neutral Neutral Safety Ground Disconnect/Main Breaker for Panel Neutral Buss Dedicated Disconnect (Optional) } Transient Ground Phase L1/A Phase L2/B Phase L3/
Surge Protective Devices Surge Protective Devices Liebert ATF Series (Active Tracking Filter) - Type F F Liebert ATF Series (Active Tracking Filter) — Type F Small Bezel .50” Max. (No Options) A Surge Protective Device (SPD) A D Installation Instructions 1. Ampacity: The filter’s maximum continuous current (Ampere) rating must be greater than or equal to the protected load’s full load amps or overcurrent protection (Circuit Breaker) rating.
Surge Protective Devices Surge Protective Devices Liebert SS Series (Type SS) 7. An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below (also indicated on the “Dimensional Information” pages in this manual). The SPD shall be connected in accordance with all national and local electrical codes.
Surge Protective Devices Typical Parallel Installations Liebert LM Series (Type LM) Summary Alarm Contacts (X2) Surge Protective Devices (SPD) Liebert SI Series (Interceptor II) Type SI/SH Pin 1 = Normally Open Pin 2 = Common 2 3 1 2 Phase L1/A Phase L2/B Phase L3/C Service Panel for Loads to be Protected Pin 3 = Normally Closed 1 TB2 E F (4X) Dedicated Disconnect (Optional) C Liebert HA Series (Hybrid Advantage) Type H Liebert SS Series (Type SS) Liebert LM Series (Type LM) Disconnect/
Surge Protective Devices Surge Protective Devices Troubleshooting / Servicing / Maintenance Troubleshooting If status failure indication occurs or Form C relay has changed states, a qualified electrician shall first determine if the systems voltage and proper phasing exists. Corrective Maintenance The Liebert SPD is designed for years of trouble-free operation. However, even the most reliable equipment may fail under abnormal conditions.
Surge Protective Devices Example Installations Surge Protective Devices defeats the effectiveness of the SPD, is a potential safety hazard, may cause equipment damage, is an NEC violation (reference NEC 250-51 and 250-54), and is not recommended. System Grounding and Bonding The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment performance.
Surge Protective Devices Surge Protective Devices Typical Parallel Connections (without Internal Rotary Disconnect) Neutral Neutral Phases Phases Ground Ground To Protected ToLoads Protected Loads Neutral Neutral Phase(s) Protected Panel Protected Panel Wire should be less than 5 feet Wire should be and straight less than 5 feet as possible and straight as possible Phase(s) Transient Ground Transient Ground Safety Ground Safety Ground Liebert Surge Liebert Protective Surge Device Protective Device
Surge Protective Devices N VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser’s business. General: Liebert Corporation products and systems are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances we offer with our products the following Ten Year Warranty Against Defects in Material and Workmanship.
Surge Protective Devices Surge Protective Devices ELECTRICAL CONNECTIONS The following is from the National Electric Code 2002 Edition. All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes. 285.21 Connection. Where a Surge Protective Device (SPD) is installed, it shall be connected as follows: (A) Location. (1) Service Supplied Building or Structure.
Surge Protective Devices Surge Protective Devices Limited Warranty INSTALLATION INSTRUCTIONS The installer should perform the following steps to assure a quality installation. The entire installation manual should be read before starting installation. These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the Liebert SPD system should only be performed by qualified personnel.
Surge Protective Devices Surge Protective Devices LIEBERT SURGE PROTECTIVE DEVICE INSTALLATION, OPERATION AND MAINTENANCE MANUAL Items Not Covered By Warranty: TABLE OF CONTENTS UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Surge Protection For Business-Critical Continuity™ Liebert ACV, ACG, ATF, HA, SI, LM, LPGE and Type SS Products Installation, Operation and Maintenance Manual Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 800 877 9222 Phone (US & Canada Only) 614 888 0246 (Outside U.S.) 614 841 6022 FAX Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy 39 049 9719 111 Phone 39 049 5841 257 FAX Emerson Network Power Asia Pacific 7/F.