Installation Instructions
D103768X012
ATEX 94/9/EC
Installation Sheet
May 2014
logo here
www.fisherregulators.com
ATEX 94/9/EC Operating and Safety Instructions
Introduction
This Installation Sheet is applicable for regulators
and accessories being used in a potentially explosive
atmosphere under ATEX 94/9/EC requirements.
Marking
Marking of regulator and accessories shall be strictly
in accordance with the requirements of ATEX 94/9/EC,
and includes:
• CE and EX Mark
• Equipment Group II
• Equipment Category 2, as label
• Type of explosive atmosphere, GD
• Equipment protected by constructional safety “c”
• Maximum temperature in service “TX”
Selection
1. Ensure that the equipment is marked with the correct
equipment group, category, type of atmosphere
and temperature class according to hazardous area
classicationoftheareaofinstallation.
2. Ensure that the maximum temperature indicated
on the product nameplate does not exceed the
maximum temperature foreseen by the hazardous
areaclassication.
Installation
1. Ensure that the safety instructions are followed for
each regulator.
2. Ensure that only non-sparkling tools are used, as
per EN 1127-1, Annex A.
3. Ensurethatnofreeamesarepresentnear
the regulator.
4. Be protected against other hazards using adequate
gloves and glasses.
5. Ensure that no metallic shocks/impacts are made
to the regulator or the adjacent pipelines system
during installation.
6. Strictly follow the operating and safety instructions
provided for the regulator.
7. Whentheregulatoristohandlehotuidsoruids
where exothermic reactions may take place,
ensure that all the necessary measures are taken
so that the hot surface of the regulator cannot
provide a source of ignition to the surrounding
gas, vapor, mist or dust atmosphere (including a
periodical removal of the dust deposits from the
hot surfaces of the regulator).
8. Before putting into use or during the operation with
dangerousuid,ensurethatnoreleaseoftheuid
to atmosphere can take place.
9. Make sure that the pressure regulator is
connected to the local earthing system for the
electric continuity.
10. Ensure a proper grounding of the regulator to
mitigate the effects of lightning strikes.