Reference Manual 00809-0200-4728, Rev RA April 2015 Rosemount 644 Temperature Transmitter with HART® Protocol
Title Page Reference Manual April 2015 00809-0200-4728, Rev RA Rosemount 644 Temperature Transmitter Rosemount 644 Hardware Revision Device Revision HART® Revision 30 7 5 1 8 5 1 9 7 Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure to thoroughly understand the contents before installing, using, or maintaining this product. The United States has two toll-free assistance numbers and one international number.
Title Page April 2015 iv Reference Manual 00809-0200-4728, Rev RA
Reference Manual Table of Contents 00809-0200-4728, Rev RA April 2015 Contents 1Section 1: Introduction 1.1 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1.1 Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.
Reference Manual Table of Contents 00809-0200-4728, Rev RA April 2015 2.6.2 Configuring the sensor(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 2.6.3 Setting output units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 2.7 Configure dual sensor options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 2.7.1 Differential temperature configuration . . . . . . . . . . . . . . . . .
Reference Manual Table of Contents 00809-0200-4728, Rev RA April 2015 3.4 Installation procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 3.4.1 Set the alarm switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 3.4.2 Mount the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 3.4.3 Install the device . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Table of Contents 00809-0200-4728, Rev RA April 2015 6Section 6: Troubleshooting 6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79 6.2 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79 6.3 Troubleshooting the 4-20 mA/HART® output . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 6.4 Diagnostic messages. . . . . . .
Reference Manual Table of Contents 00809-0200-4728, Rev RA April 2015 A.4.3 Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 A.5 Specifications and reference data for 644 HART Head Mount. . . . . . . . . . . . . . 121 A.5.1 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 A.5.2 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents April 2015 x Reference Manual 00809-0200-4728, Rev RA Table of Contents
Section 1: Introduction Reference Manual April 2015 00809-0200-4728, Rev RA Section 1 1.1 Introduction Safety messages Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol. 1.1.
Section 1: Introduction Reference Manual 00809-0200-4728, Rev RA April 2015 1.2 Overview 1.2.1 Manual This manual is designed to assist in the installation, operation, and maintenance of Rosemount 644 Head Mount, 644 Field Mount, and 644 Rail Mount transmitters with the HART protocol. Section 2: Configuration provides instruction the commissioning and operating the Rosemount 644 HART Transmitter.
Reference Manual Section 1: Introduction 00809-0200-4728, Rev RA 1.2.
Section 1: Introduction Reference Manual 00809-0200-4728, Rev RA April 2015 1.3 Considerations 1.3.1 General Electrical temperature sensors such as RTDs and thermocouples produce low-level signals proportional to their sensed temperature. The 644 converts the low-level sensor signal to a standard 4–20 mA DC or digital HART signal that is relatively insensitive to lead length and electrical noise. This signal is then transmitted to the control room via two wires. 1.3.
Reference Manual Section 1: Introduction 00809-0200-4728, Rev RA April 2015 Figure 1-1. 644 Head Mount Transmitter Connection Head Temperature Rise vs. Extension Length 50 (90) 40 (72) 30 (54) 0 54 81 5C (15 0 00 10 C( 22 0F ) F) Housing Temperature Rise Above Ambient C ( F) 60 (108) 20 (36) Ov en T em p Oven Temp era t 250 10 (18) C (4 82 eratu r e ure F) Oven Tempera ture 0 3 4 3.6 5 6 7 Extension Length (in.
Reference Manual Section 1: Introduction 00809-0200-4728, Rev RA April 2015 The center will provide: A Return Material Authorization (RMA) number Instructions and procedures that are necessary to return goods that were exposed to hazardous substances For other locations, contact an Emerson Process Management sales representative.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA Section 2 April 2015 Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System readiness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 2.2.1 Warnings Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions could result in death or serious injury. Do not remove the connection head cover in explosive atmospheres when the circuit is live.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA 2.3.2 April 2015 Surges/transients The transmitter will withstand electrical transients of the energy level encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, welding, heavy electrical equipment, or switching gears, can damage both the transmitter and the sensor.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Figure 2-1. Powering the Transmitter for Bench Configuration 644 Head Mount and Field Mount 644 Rail Mount 250 Ω ≤ RL ≤ 1100 Ω A B A. Power Supply B. Field Communicator Note 2.4.2 Signal loop may be grounded at any point or left ungrounded. A Field Communicator may be connected at any termination point in the signal loop. The signal loop must have between 250 and 1100 ohms load for communications.
Reference Manual 00809-0200-4728, Rev RA Section 2: Configuration April 2015 Figure 2-2.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Figure 2-3. LOI Configuration Buttons A A. Configuration Buttons Table 2-2. LOI Button Operation Button Left Right No Yes SCROLL ENTER LOI password An LOI password can be entered and enabled to prevent review and modification of device configuration via the LOI. This does not prevent configuration from HART or through the control system. The LOI password is a 4 digit code that is to be set by the user.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 output in failure mode depend on whether it is configured to standard, NAMUR-compliant, or custom operation. See “Hardware and software failure mode” on page 97 for standard and NAMUR-compliant operation parameters. 2.4.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Table 2-3.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Checking or setting process variables The “Process Variables” menu displays process variables, including sensor temperature, percent of range, analog output, and terminal temperature. These process variables are continuously updated. The default primary variable is Sensor 1. The secondary variable is the transmitter terminal temperature by default.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 2.6 Basic configuration of the transmitter The 644 must be configured for certain basic variables in order to be operational. In many cases, all of these variables are pre-configured at the factory. Configuration may be required if the transmitter is not configured or if the configuration variables need revision. 2.6.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA 2.6.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Contact an Emerson Process Management representative for information on the temperature sensors, thermowells, and accessory mounting hardware that is available through Emerson Process Management. 2-wire RTD offset The 2-wire offset feature allows the measured lead wire resistance to be input and corrected for, which results in the transmitter adjusting its temperature measurement for the error caused by this added resistance.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Each of the base parameters and calculated outputs from those values can have a Unit of measure associated with it. Set the transmitter output to one of the following engineering units: Degrees Celsius Degrees Fahrenheit Degrees Rankine Kelvin Ohms Millivolts Setting output units with a Field Communicator From the HOME screen, enter the Fast Key sequence.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 2.7 Configure dual sensor options Dual-sensor configuration deals with the functions that can be used with a transmitter ordered with Dual Sensor inputs. In the Rosemount 644 these functions include: Differential Temperature Average Temperature Hot Backup and Sensor Drift Alert Diagnostics (requires option code DC) – 2.7.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Figure 2-7. Configuring Differential Units with LOI VIEW CONFIG SENSOR CONFIG UNITS RERANGE LOOP TEST DISPLAY EXTENDED MENU EXIT MENU CHANGE ALL SENSOR 1 UNITS SENSOR 2 UNITS* DIFFRNTL UNITS* AVERAGE UNITS* 1ST GOOD UNITS** BACK TO MENU EXIT MENU DEG C UNITS DEG F UNITS DEG R UNITS KELVIN UNITS MV UNITS OHM UNITS BACK TO MENU EXIT MENU * Available only if option code (S) or (D) is ordered.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Average temperature configuration with LOI To configure average temperature on the LOI, the Units and Damping values must be set separately. Reference Figure 2-9 and Figure 2-10 below for where to find these in the menu. Figure 2-9.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA 2.7.3 April 2015 Hot Backup configuration The Hot Backup feature configures the transmitter to automatically use Sensor 2 as the primary sensor if Sensor 1 fails. With Hot Backup enabled, the primary variable (PV) must either be First Good or Average. See the “NOTE” directly above for details on using Hot Backup when the PV is set to Average.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Figure 2-11. Configuring Hot Backup with LOI VIEW CONFIG SENSOR CONFIG UNITS RERANGE LOOP TEST DISPLAY EXTENDED MENU EXIT MENU CALIBRAT DAMPING VARIABLE MAP TAG ALM SAT VALUES PASSWORD SIMULATE HART REV HOT BACK CONFIG** DRIFT ALERT** .... HOT BACK MODE HOT BACK PV HOT BACK RESET BACK TO MENU EXIT MENU * Available only if option code (S) or (D) is ordered.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Sensor drift alert configuration with AMS Device Manager 1. Right click on the device and select Configure. 2. On the Diagnostics Tab find the Sensor Drift Alert group box. 3. Select to Enable the Mode and fill in the Units, Threshold and Damping values from the drop downs provided or select the Configure Sensor Drift Alert button and walk through the guided steps. 4. Select Apply when complete.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 The range of expected readings is defined by the Lower Range Value (LRV) and Upper Range Value (URV). The transmitter range values can be reset as often as necessary to reflect changing process conditions. For a complete listing of Range & Sensor limits, refer to Table A-2 on page 98. Note The re-range functions should not be confused with the trim functions.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 The value chosen for damping affects the response time of the transmitter. When set to zero (disabled), the damping function is off and the transmitter output reacts to changes in input as quickly as the intermittent sensor algorithm allows. Increasing the damping value increases transmitter response time. With damping enabled, if the temperature change is within 0.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Damping can be applied to a number of parameters in the 644 transmitter. Variables that can be damped are: Primary Variable (PV) Sensor 1 Sensor 2 Differential Temperature Average Temperature 1st Good Temperature Note The instructions below only refer to the damping of the Primary Variable (PV). Damping the transmitter with a Field Communicator From the HOME screen, enter the Fast Key sequence.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA 2.8.3 April 2015 Configure alarm and saturation levels In normal operation, the transmitter will drive the output in response to measurements between the lower to upper saturation points. If the temperature goes outside the sensor limits, or if the output would be beyond the saturation points, the output will be limited to the associated saturation point.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Configuring alarm and saturation levels with a Field Communicator From the HOME screen, enter the Fast Key sequence. 2, 2, 5, 6 Device Dashboard Fast Keys Configuring alarm and saturation levels with AMS Device Manager 1. Right click on the device and select Configure. 2. In the left navigation pane select Manual Setup. 3. On the Analog Output Tab find the Alarm and Saturation Levels group box. 4.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA 2.8.4 April 2015 Configuring the LCD display The LCD display configuration command allows customization of the LCD display to suit application requirements. The LCD display will alternate between the selected items with each item displaying for a 3 second interval.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Configuring LCD display with AMS Device Manager 1. Right click on the device and select Configure. 2. In the left navigation pane select Manual Setup. 3. On the Display Tab there will be a group box with all available variables that can be displayed. 4. Check and un-check the desired display variables, with a checked box indicating that the variable will be displayed. 5. Select “Apply” when complete.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 extended to 32 characters long. Neither parameter has any impact on the primary variable readings of the transmitter, it is only for information. The Date is a user-defined variable that provides a place to save the date of the last revision of configuration information. It has no impact on the operation of the transmitter or the HART-based communicator.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 2.10 Configure measurement filtering 2.10.1 50/60 Hz filter The 50/60 Hz Filter (also known as Line Voltage Filter or AC Power Filter) function sets the transmitter electronic filter to reject the frequency of the AC power supply in the plant. The 60 Hz or 50 Hz mode can be chosen. The factory default for this setting is 50 Hz.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 feature can be switched ON or OFF and the threshold value can be changed to any value between 0 and 100% of the sensor limits with a Field Communicator. When the intermittent sensor detection feature is switched ON, the transmitter can eliminate the output pulse caused by intermittent open sensor conditions. Process temperature changes (T) within the threshold value will be tracked normally by the transmitter’s output.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 2.10.4 Open Sensor Hold Off The Open Sensor Hold Off option, at the normal setting, enables the 644 to be more robust under heavy EMI conditions. This is accomplished by the software having the transmitter perform additional verification of the open sensor status prior to activating the transmitter alarm. If the additional verification shows that the open sensor condition is not valid, the transmitter will not go into alarm.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Performing a loop test with AMS Device Manager 1. Right click on the device and select Service Tools. 2. In the left navigation pane select Simulate. 3. On the Simulate Tab find the Perform Loop Test button in the Analog Output Verification group box. 4. Follow the guided instructions and select Apply when complete.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Figure 2-20. Simulating the Digital Signal with LOI VIEW CONFIG SENSOR CONFIG UNITS RERANGE LOOP TEST DISPLAY EXTENDED MENU EXIT MENU CALIBRAT DAMPING VARIABLE MAP TAG ALM SAT VALUES PASSWORD SIMULATE HART REV .... SIMULATE SNSR 1 SIMULATE SNSR 2* END SIMUL BACK TO MENU EXIT MENU * Available only if option code (S) or (D) is ordered. 2.11.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Configure T/C Diagnostic with AMS Device Manager 1. Right click on the device and select Configure. 2. In the left navigation window select Manual Setup. 3. On the Diagnostics tab, there is a group box labeled Sensor and Process Diagnostics; select the button for Configure Thermocouple Diagnostic. 4. Follow the screen prompts to Enable and set the values for the diagnostic.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 1, Sensor 2, Differential, Average, First Good and Terminal temperatures. Min/Max Tracking only records temperature maxima and minima obtained since the last reset, and is not a logging function. To track maximum and minimum temperatures, Min/Max Tracking must be enabled using a Field Communicator, AMS Device Manager, Local Operator Interface, or other communicator.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Many Rosemount transmitters can be multi dropped. With the HART communications protocol, up to 15 transmitters can be connected on a single twisted pair of wires or over leased phone lines. A Field Communicator can test, configure, and format a multidropped 644 transmitter in the same way as in a standard point-to-point installation.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Changing transmitter address with a Field Communicator From the HOME screen, enter the Fast Key sequence. Device Dashboard Fast Keys 1, 2, 1 Changing transmitter address with AMS Device Manager 1. Right click on the device and select Configuration Properties from the menu. 2. In HART Revision 5 mode: a. 3. In HART Revision 7 mode: a. 2.13 In the HART tab, enter poll address into the Polling Address box, select Apply.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA 2.13.1 April 2015 Set the transmitter to burst mode To set the transmitter to burst mode, follow the steps below with the Fast Key sequence. Setting the burst mode with a Field Communicator From the HOME screen, enter the Fast Key sequence. Device Dashboard Fast Keys HART 5 HART 7 2, 2, 8, 4 2, 2, 8, 5 Setting the burst mode with AMS Device Manager 2.13.2 1. Right click on the device and select Configure. 2.
Reference Manual Section 2: Configuration 00809-0200-4728, Rev RA April 2015 Using the Tri-Loop to detect sensor drift alert The dual-sensor 644 transmitter sets a failure flag (through HART) whenever a sensor failure occurs. If an analog warning is required, the HART Tri-Loop can be configured to produce an analog signal that can be interpreted by the control system as a sensor failure. Use these steps to set up the HART Tri-Loop to transmit sensor failure alerts. 1.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA Section 3 April 2015 Hardware Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 3: Hardware installation 3.2.1 Reference Manual 00809-0200-4728, Rev RA April 2015 Warnings Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions could result in death or serious injury. Do not remove the connection head cover in explosive atmospheres when the circuit is live.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA 3.4 April 2015 Installation procedures Figure 3-1.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 3.4.1 Set the alarm switch Make certain that the alarm switch is set to the desired position before putting the device into operation to ensure correct function in the instance of a failure. Without an LCD display 1. Set the loop to manual (if applicable) and disconnect the power. 2. Remove the housing cover. 3. Set the physical hardware alarm switch to the desired position. H indicates High, L indicates Low.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA 3.4.2 April 2015 Mount the transmitter Mount the transmitter at a high point in the conduit run to prevent moisture from draining into the transmitter housing. The 644 head mount installs In a connection head or universal head mounted directly on a sensor assembly. Apart from a sensor assembly using a universal head. To a DIN rail using an optional mounting clip.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 3.4.3 Install the device Head mount transmitter with DIN plate style sensor installation 1. Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell before applying process pressure. 2. Verify the transmitter failure mode switch position. 3. Assemble the transmitter to the sensor(1). Push the transmitter mounting screws through the sensor mounting plate. 4.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 Head mount transmitter with threaded sensor installation 1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells before applying process pressure. 2. Attach necessary extension nipples and adapters to the thermowell. Seal the nipple and adapter threads with silicone tape. 3. Screw the sensor into the thermowell.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 Field mount transmitter with threaded sensor installation 1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells before applying process pressure. 2. Attach necessary extension nipples and adapters to the thermowell. 3. Seal the nipple and adapter threads with silicone tape. 4. Screw the sensor into the thermowell.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 Rail mount transmitter and sensor 1. Attach the transmitter to a suitable rail or panel. 2. Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell, according to plant standards, before applying pressure. 3. Attach the sensor to the connection head and mount the entire assembly to the thermowell. 4.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 Rail mount transmitter with threaded sensor 1. Attach the transmitter to a suitable rail or panel. 2. Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell before applying pressure. 3. Attach necessary extension nipples and adapters. Seal the nipple and adapter threads with thread sealant. 4. Screw the sensor into the thermowell.
Reference Manual Section 3: Hardware installation 00809-0200-4728, Rev RA April 2015 Figure 3-5. Multichannel Installations Backup Battery R Transmitter No. 1 R Transmitter No. 2 R Readout or Controller No. 1 dc Power Supply Readout or Controller No. 2 T o A d Between 250 Ω and 1100 Ω if no load resistor. 3.4.5 LCD display installation The LCD display provides local indication of the transmitter output and abbreviated diagnostic messages governing transmitter operation.
Section 3: Hardware installation Reference Manual 00809-0200-4728, Rev RA April 2015 Use the following procedure to install the meter. 1. If the transmitter is installed in a loop, secure the loop and disconnect the power. If the transmitter is installed in an enclosure, remove the cover from the enclosure. 2. Decide meter orientation (the meter can be rotated in 90° increments). To change meter orientation, remove the screws located above and below the display screen.
Section 4: Electrical Installation Reference Manual April 2015 00809-0200-4728, Rev RA Section 4 Electrical Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57 Wiring and powering the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 4: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 4.3 Wiring and powering the transmitter All power to the transmitter is supplied over the signal wiring. Use ordinary copper wire of sufficient size to ensure the voltage across the transmitter power terminals does not drop below 12.0 Vdc.
Reference Manual Section 4: Electrical Installation 00809-0200-4728, Rev RA 4.3.1 April 2015 Sensor connections The 644 is compatible with a number of RTD and thermocouple sensor types. Figure 4-2 shows the correct input connections to the sensor terminals on the transmitter. To ensure a proper sensor connection, anchor the sensor lead wires into the appropriate captive terminals and tighten the screws. Figure 4-2. Sensor Wiring Diagrams *Rosemount Inc.
Section 4: Operation and Maintenance Reference Manual 00809-0200-4728, Rev RA April 2015 Thermocouple or millivolt inputs The thermocouple can be connected directly to the transmitter. Use appropriate thermocouple extension wire if mounting the transmitter remotely from the sensor. Make millivolt inputs connections with copper wire. Use shielding for long runs of wire. RTD or Ohm inputs The transmitters will accept a variety of RTD configurations, including 2-wire, 3-wire or 4-wire.
Reference Manual Section 4: Electrical Installation 00809-0200-4728, Rev RA April 2015 Figure 4-3. Powering the Transmitter for Bench Configuration 644 Head Mount and Field Mount 644 Rail Mount 250 ≤ RL ≤ 1100 A B A. Power supply B. Field Communicator Note Signal loop may be grounded at any point or left ungrounded. A Field Communicator may be connected at any termination point in the signal loop. The signal loop must have between 250 and 1100 ohms load for communications.
Reference Manual Section 4: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 Shielding recommendations The following are recommended practices from API Standard 552 (Transmission Standard) section 20.7, and from field and laboratory testing. If more than one recommendation is given for a sensor type, start with the first technique shown or the technique that is recommended for the facility by its installation drawings.
Reference Manual Section 4: Electrical Installation 00809-0200-4728, Rev RA April 2015 Option 2 1. Connect signal wiring shield to the sensor wiring shield. 2. Ensure the two shields are tied together and electrically isolated from the transmitter housing. 3. Ground shield at the power supply end only. 4. Ensure the sensor shield is electrically isolated from the surrounding grounded fixtures. B A C A. Sensor wires B. Transmitter C. Shield ground point 5.
Reference Manual Section 4: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 4. Ground signal wiring shield at the power supply end. B A C A. Sensor wires B. Transmitter C. Shield ground point Grounded thermocouple inputs Option 1 1. Ground sensor wiring shield at the sensor. 2. Ensure the sensor wiring and signal wiring shields are electrically isolated from the transmitter housing. 3. Do not connect the signal wiring shield to the sensor wiring shield. 4.
Reference Manual Section 4: Electrical Installation 00809-0200-4728, Rev RA 4.3.4 April 2015 Wiring with a Rosemount 333 HART Tri-Loop™ (HART/4–20 mA only) Use the dual-sensor option 644 transmitter that is operating with two sensors in conjunction with a 333 HART Tri-Loop HART-to-Analog Signal Converter to acquire an independent 4–20 mA analog output signal for each sensor input.
Reference Manual Section 4: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 Figure 4-4. Load Limits Load (Ohms) Maximum Load = 40.8 X (Supply Voltage - 12.0) 4–20 mA dc 1240 1100 1000 750 500 Operating Region 250 0 10 12.0 20 30 40 42.
Section 5: Operation and Maintenance Reference Manual April 2015 00809-0200-4728, Rev RA Section 5 Operation and Maintenance Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibration overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 5.2.1 Warnings Failure to follow these installation guidelines could result in death or serious injury. Make sure only qualified personnel perform the installation. Explosions could resultin death or serious injury. Do not remove the connection head cover in explosive atmospheres when the circuit is live.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA 5.3.1 April 2015 Trimming The trim functions should not be confused with the rerange functions. Although the rerange command matches a sensor input to a 4–20 mA output—as in conventional calibration—it does not affect the transmitter’s interpretation of the input. One or more of the trim functions may be used when calibrating. The trim functions are as follows: 5.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 Use the following procedures to perform a sensor trim on the 644: Performing a sensor trim using a Field Communicator 1. Connect the calibration device or sensor to the transmitter. (If using an active calibrator, see “Active calibrator and EMF compensation” on page 71) 2. Connect the communicator to the transmitter loop. From the HOME screen, enter the Fast Key sequence.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA 5.4.1 April 2015 Recall factory trim—sensor trim The Recall Factory Trim—Sensor Trim feature allows the restoration of the as-shipped factory settings of the analog output trim. This command can be useful for recovering from an inadvertent trim, incorrect Plant Standard or faulty meter.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 EMF compensation allows the transmitter to provide sensor measurements that are unaffected by unwanted voltages, typically due to thermal EMFs in the equipment connected to the transmitter, or by some types of calibration equipment. If this equipment also requires steady sensor current, the transmitter must be set to “Active Calibrator Mode.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 From the HOME screen, enter the Fast Key sequence. Device Dashboard Fast Keys 3, 4, 5, 1 Performing an analog output trim using AMS Device Manager 1. Right click on the device and select Service Tools. 2. In the left navigation pane select Maintenance. 3. Find the Analog Calibration tab and click on the Analog Trim button. 4. Follow the screen prompts through the Analog Trimming process.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 Performing an analog output trim using AMS Device Manager 5.6 1. Right click on the device and select Service Tools. 2. In the left navigation pane select Maintenance. 3. Find the Analog Calibration tab and select the Scaled Trim button. 4. Follow the screen prompts through the Analog Trimming process.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 Table 5-2. Standard RTD vs. RTD with Matched CVD Constants with Enhanced Transmitter Accuracy Option P8 System Accuracy Comparison at 150 °C Using a PT 100 (α=0.00385) RTD with a Span of 0 to 200 °C Standard RTD 644 Standard RTD (1) Total System Matched RTD ±0.10 °C 644 ±1.05 °C Matched RTD ±1.05 °C ±0.10 °C Total System (1) ±0.18 °C ±0.
Reference Manual Section 5: Operation and Maintenance 00809-0200-4728, Rev RA April 2015 5.7 Switching HART Revision Some systems are not capable of communicating with HART Revision 7 devices. The following procedures list how to change HART revisions between HART Revision 7 and HART Revision 5. 5.7.1 Switching HART Revision using the generic menu If the HART configuration tool is not capable of communicating with a HART Revision 7 device, it should load a Generic Menu with limited capability.
Section 6: Troubleshooting Reference Manual April 2015 00809-0200-4728, Rev RA Section 6 Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting the 4-20 mA/HART output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 6: Troubleshooting 00809-0200-4728, Rev RA April 2015 6.3 Troubleshooting the 4-20 mA/HART output Table 6-1. Rosemount 644 Troubleshooting Table for 4-20 mA Output Symptom or issue Transmitter Does Not Communicate with Field Communicator Potential source Check the revision level of the transmitter device descriptors (DDs) stored in your communicator.
Reference Manual Section 6: Troubleshooting 00809-0200-4728, Rev RA April 2015 Table 6-1. Rosemount 644 Troubleshooting Table for 4-20 mA Output Symptom or issue Potential source Corrective action Connect a Field Communicator and enter the transmitter test mode to isolate a sensor failure. Check the process variable to see if it is out of range. Check for adequate voltage to the transmitter. It should be 12.0 to 42.4 Vdc (over entire 3.75 to 23 mA operating range).
Reference Manual Section 6: Troubleshooting 00809-0200-4728, Rev RA April 2015 6.4 Diagnostic messages Listed in the below sections are detailed tables of the possible messages that will appear on either the LCD/LOI Display, a Field Communicator, or an AMS® Device Manager system. Use the tables below to diagnose particular status messages. 6.4.1 Failed Maintenance Advisory Diagnostic messages: Failed Table 6-2.
Reference Manual Section 6: Troubleshooting 00809-0200-4728, Rev RA April 2015 Table 6-2. Status: Failed – Fix Now Alert name LCD screen LOI screen Invalid Configuration CONFG SNSR 1 CONFG SNSR 1 WARN ERROR WARN ERROR Problem Recommended action 1. Verify sensor type and number of wires matched the Sensor Configuration of the device. The Sensor Configuration (type and/or connection) does not match the sensor output and is invalid. 2. Reset the device. 3.
Reference Manual Section 6: Troubleshooting 00809-0200-4728, Rev RA April 2015 Alert name LCD screen LOI screen Calibration Error Sensor Out of Operating Limits(1) [none] [none] SAT SNSR 1 SAT SNSR 1 XX.XXX °C XX.XXX °C Problem The value entered for the user trim point was not acceptable. Sensor # readings are outside the sensor's specified range. Recommended action 1. Re-trim the device, make sure the user entered calibration points are close to the applied calibration temperature. 1.
Section 7: Safety Instrumented Systems (SIS) Certification Reference Manual April 2015 00809-0200-4728, Rev RA Section 7 Safety Instrumented Systems (SIS) Certification SIS certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 644 safety certified identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation in SIS application . . . . . . . . . . . . . . . . . . . .
Reference Manual Section 7: Safety Instrumented Systems (SIS) Certification 00809-0200-4728, Rev RA April 2015 Namur Software Revision Number SW(1) 1.1.x (1) Namur Software Revision: Located on the adhesive device tag. 4. You can also identify a certified 644 by its Device Revision which can be found using any HART compliant communicator. For the 644, certified device revisions are as follows: 7.3 – Device Revision 8.x (HART 5) – Device Revision 9.
Reference Manual Section 7: Safety Instrumented Systems (SIS) Certification 00809-0200-4728, Rev RA 7.5 April 2015 Configuration Use any HART capable configuration tool or the optional Local Operator Interface (LOI) to communicate with and verify the initial configuration or any configuration changes made to the 644 prior to operating in Safety Mode. All configuration methods outlined in Section 3 are the same for the safety certified 644 temperature transmitter with any differences noted.
Reference Manual Section 7: Safety Instrumented Systems (SIS) Certification 00809-0200-4728, Rev RA April 2015 Figure 7-1. Alarm Levels Rosemount alarm level Normal Operation 3.75 mA (1) 20 mA 4 mA 3.9 mA low saturation 20.8 mA high saturation 21.75(2) Namur alarm level Normal Operation 3.6 mA (1) 4 mA 3.8 mA low saturation 22.5(2) 20 mA 20.5 mA high saturation Custom alarm level(3)(4) Normal Operation 3.6 - 3.8 mA (1) 3.7 - 3.9 mA low saturation 4 mA 20 mA 20.1 - 22.
Reference Manual Section 7: Safety Instrumented Systems (SIS) Certification 00809-0200-4728, Rev RA 7.7.3 April 2015 4. Using Loop Test, enter the milliampere value representing a low alarm state. This tests for possible dormant current related failures. 5. Check the reference meter to verify the mA output corresponds to the entered value. 6. Use a Field Communicator to view detailed device status to ensure no alarms or warnings are present in the transmitter. 7.
Reference Manual Section 7: Safety Instrumented Systems (SIS) Certification 00809-0200-4728, Rev RA April 2015 1. Bypass the safety PLC or take other appropriate action to avoid a false trip. 2. Execute steps 2 through 6 of the Partial proof test (see 7.7.2). 3. Disconnect Sensor 1 and connect a calibrated sensor simulator in its place. 4. Using at least 2 simulated temperature points, verify the transmitter output remains within the required accuracy. 5.
Reference Manual Section 7: Safety Instrumented Systems (SIS) Certification 00809-0200-4728, Rev RA 7.8.2 April 2015 SIS safety transmitter failure values IEC 61508 Safety Certified SIL 2 Claim Limit Safety accuracy: Span > = 100 °C ± 2%(1) of process variable span Span < 100 °C ± 2 °C Safety response time: 5 seconds 7.8.3 Product life 50 years - based on worst case component wear-out mechanisms - not based on wear-out of process sensors.
Section 7: Safety Instrumented Systems (SIS) Certification April 2015 90 Reference Manual 00809-0200-4728, Rev RA Safety Instrumented Systems (SIS) Certification
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA Appendix A April 2015 Specifications and Reference Data Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–20 mA / HART specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Humidity limits 0–95% relative humidity Update time ≤ 0.5 seconds per sensor Accuracy (default configuration) PT 100 HART (0-100 °C): ±0.18 °C ±0.1 °C (when ordered with option P8) A.1.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Mounting The 644R attaches directly to a wall or a DIN rail. The 644H installs in a connection head or universal head mounted directly on a sensor assembly, apart from a sensor assembly using a universal head, or to a DIN rail using an optional mounting clip. Weight Code Options Weight 644H HART, Head Mount Transmitter 95 g (3.39 oz) ™ 644H FOUNDATION fieldbus, Head Mount Transmitter 92 g (3.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 A.1.3 Performance EMC (electromagnetic compatibility) NAMUR NE 21 Standard The Rosemount 644 meets the requirements for the NAMUR NE 21 rating. Susceptibility Parameter Influence HART ESD 6 kV contact discharge None Radiated 8 kV air discharge 80 MHz to 2.7 GHz at 10 V/m < 1.0% Burst 1 kV for I.O. None Surge 1 kV line–ground None Conducted 10 kHz to 80 MHz at 10 V < 1.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Sensor connections Figure A-1. 644 HART Head Mount – + + – Figure A-2.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Figure A-3. 644 Sensor Connection Diagram: 644 Fieldbus and PROFIBUS PA Head Mount and 644 Rail Mount 1234 2-wire RTD and 1234 4-wire RTD and 12 34 3-wire RTD and * 1234 T/C and mV * Rosemount Inc. provides 4-wire sensors for all single element RTDs. You can use these RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Power supply An external power supply is required for HART devices. The transmitter operates on 12.0 to 42.4 Vdc transmitter terminal voltage with load resistance between 250 and 660 ohms. A minimum of 17.75 Vdc power supply is required with a load of 250 ohms. Transmitter power terminals are rated to 42.4 Vdc. Maximum load = 40.8 x (supply voltage – 12.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Custom alarm and saturation level Custom factory configuration of alarm and saturation level is available with option code C1 for valid values. These values can also be configured in the field using a Field Communicator. Turn-on time Performance within specifications in less than 6.0 seconds after power is applied, when damping value is set to 0 seconds.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-2. Rosemount 644 Input Options and Accuracy Sensor options Sensor reference Cu 50 (α = 0.00428) GOST 6651-94 Cu 100 (α = 0.00426) GOST 6651-94 Cu 100 (α = 0.00428) GOST 6651-94 Type B(5) NIST Monograph 175, IEC 584 Type E Input ranges –185 to 200 Recommended (1) min. span Digital accuracy(2) D/A accuracy(3) –301 to 392 10 18 ±1.34 ± 2.41 ±0.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Accuracy example When using a Pt 100 (α = 0.00385) sensor input with a 0 to 100 °C span: Digital accuracy = ±0.15 °C D/A accuracy = ±0.03% of 100 °C or ±0.03 °C Total accuracy = ±0.18 °C Table A-3. Ambient Temperature Effect Sensor options Sensor reference Input range (°C) Temperature effects per 1.0 °C (1.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-3. Ambient Temperature Effect Sensor options GOST Type L Sensor reference GOST R 8.585-2001 Input range (°C) Temperature effects per 1.0 °C Range (1.8 °F) change in ambient temperature D/A effect (2) (1) 0.007 °C 0.007 °C – (0.003% of absolute value T) T ≥ 0 °C 0.001% of span -200 to 800 T < 0 °C 0.001% of span -10 to 100 mV 0 to 2000 Ω 0.0005 mV 0.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-4. Transmitter Accuracy when ordered with Option Code P8 Sensor options Sensor reference 2-, 3-, 4-wire RTDs Pt 100 (a = 0.00385) Pt 200 (a = 0.00385) Pt 500 (a = 0.00385) Pt 1000 (a = 0.00385) Pt 100 (a = 0.003916) Pt 200 (a = 0.003916) Ni 120 Cu 10 Pt 50 (a=0.00391) Pt 100 (a=0.00391) Cu 50 (a=0.00426) Cu 50 (a=0.00428) Cu 100 (a=0.00426) Cu 100 (a=0.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA A.3 April 2015 Dimensional drawings 644H (DIN A Head Mount) HART device shown with captivated screw terminals FOUNDATION fieldbus and PROFIBUS device shown with standard compression screw terminals 60 (2.4) C 60 (2.4) 33 (1.3) 33 (1.3) C D 59 (2.3) B 24 (.96) 24 (1.0) B A E D F E 31 (1.2) 33 (1.30) Dimensions are in millimeters (inches). A.Failure mode switch B. Display connection C.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 644 Field Mount Transmitter exploded view Display compartment Terminal compartment with optional transient protector F. Failure mode switch G. Display connection H. Sensor terminals I. Communication terminals J. Power terminals A. Nameplate B. Cover C. Housing with electronics module D. LCD display E. Display cover 644 Rail Mount A 82 (3.2) B 36 (1.4) 104 (4.1) A. Sensor terminals B.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Mounting Kits for 644 Head Mount 644H Rail Clips 644R Rail & Walls Clips G-Rail (asymmetric) Top Hat Rail (symmetric) A A B B C C B C A (part number 03044-4103-0001) A. Top hat rail grooves B. G-rail grooves C. Screw holes for mounting to a wall D. Mounting hardware E. Transmitter F. Rail clip Note Kit (part number 00644-5301-0010) includes mounting hardware and both types of rail kits.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Threaded-Sensor Universal Head (Option code J5, J6, J7 or J8) DIN Style Sensor Connection Head (Option code R1, R2, R3 or R4) 112 (4.41) A 96 (3.76) 104 (4.09) 95 (3.74) B D 78 (3.07) 128 (5.04) with LCD Display 75 103 (4.03) with LCD (2.93) Display C 100 (3.93) 316 SST “U” Bolt Mounting, 2-inch Pipe Note: A “U” Bolt is shipped with each universal head unless assembly option XA is ordered.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Stainless Steel Housing for Biotechnology, Pharmaceutical Industries, and Sanitary Applications Sanitary Housing (Option Code S1, S2, S3, S4) Standard cover A C B 76.2 (3.0) 33 (1.3) 79.8 (3.14) 27.9 (1.1) 25.4 (1.0) 44.5 (1.75) 24.4 (0.96) 70.0 (2.76) LCD display cover D C B 47 (1.85) 33 (1.3) 61 (2.4) 76.2 (3.0) 27.9 (1.1) 25.4 (1.0) 44.5 (1.75) 74.4 (2.93) 70.0 (2.76) A. Standard cover B.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 A.4 Ordering information The Rosemount 644 is a versatile temperature transmitter that delivers field reliability and advanced accuracy and stability to meet demanding process needs.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-5. Rosemount 644 Smart Temperature Transmitter Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-5. Rosemount 644 Smart Temperature Transmitter Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-5. Rosemount 644 Smart Temperature Transmitter Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-5. Rosemount 644 Smart Temperature Transmitter Ordering Information ★ The Standard offering represents the most common models and options. These options should be selected for best delivery. The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-6.
Appendix A: Specifications and Reference Data April 2015 Reference Manual 00809-0200-4728, Rev RA Table A-7.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-8.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Table A-9.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA A.4.1 April 2015 Configuration Transmitter configuration The transmitter is available with standard configuration settings for HART. The configuration settings may be changed in the field with DeltaV™, with AMS® Device Manager, or with any Field Communicator.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 External ground screw assembly The external ground screw assembly can be ordered by specifying code G1 when an enclosure is specified. However, some approvals include the ground screw assembly in the transmitter shipment, hence it is not necessary to order code G1. The table below identifies which approval options include the external ground screw assembly and which do not.
Reference Manual 00809-0200-4728, Rev RA A.5 Appendix A: Specifications and Reference Data April 2015 Specifications and reference data for 644 HART Head Mount (Device Revision 7 or previous) A.5.1 Functional specifications Inputs User-selectable; sensor terminals rated to 42.4 Vdc. See “Accuracy” on page 98 for sensor options. Output Single 2-wire device with either 4-20 mA/HART, linear with temperature or input. Device supports protocol revision HART 5.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 A.5.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Weight Code Options Weight 644H HART, Head Mount Transmitter 95 g (3.39 oz) 644H FOUNDATION fieldbus, Head Mount Transmitter 92 g (3.25 oz) 644H PROFIBUS PA, Head Mount Transmitter 92 g (3.25 oz) 644R HART, Rail Mount Transmitter 174 g (6.14 oz) M5 LCD Display 35 g (1.34 oz) J5, J6 Universal Head, Standard Cover 577 g (20.35 oz) J5, J6 Universal Head, Meter Cover 667 g (23.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 A.5.3 Performance specifications EMC (Electromagnetic Compatibility) NAMUR NE 21 Standard The 644H HART meets the requirements for NAMUR NE 21 Rating. Susceptibility Parameter Influence HART 6 kV contact discharge 8 kV air discharge Radiated 80 – 1000 MHz at 10 V/m AM < 1.0% Burst 1 kV for I.O. None Surge 0.5 kV line–line None 1 kV line–ground (I.O.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Sensor connections Rosemount 644 Sensor connections diagram 12 34 3-wire RTD and * 1234 2-wire RTD and 1234 4-wire RTD and 1234 T/C and mV * Rosemount Inc. provides 4-wire sensors for all single element RTDs. You can use these RTDs in 3-wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape.
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Temperature limits Operating limit Storage limit With LCD display(1) –40 to 185 °F –20 to 85 °C –50 to 185 °F –45 to 85 °C Without LCD display –40 to 185 °F –40 to 85 °C –60 to 248 °F –50 to 120 °C (1) LCD may not be readable and display updates will be slower at temperatures below -4 °F (-20 °C).
Reference Manual Appendix A: Specifications and Reference Data 00809-0200-4728, Rev RA April 2015 Configuration For standard configuration information, see “Configuration” on page 117. Table A-11.
Appendix A: Specifications and Reference Data April 2015 126 Reference Manual 00809-0200-4728, Rev RA Specifications and Reference Data
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA Appendix B Product Certifications European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 127 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 127 Hazardous Locations Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B: Product Certifications Reference Manual 00809-0200-4728, Rev RA April 2015 Certificate: 3044581 [Headmount HART] Standards: FM Class 3600: 2011, FM Class 3610: 2010, FM Class 3611: 2004, FM Class 3810: 2005, ANSI/NEMA - 250: 1991, ANSI/IEC 60529: 2004; ANSI/ISA 60079-0: 2009; ANSI/ISA 60079-11: 2009.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 I1 ATEX Intrinsic Safety Certificate: [Headmount HART]: Baseefa12ATEX0101X [Headmount Fieldbus/PROFIBUS]: Baseefa03ATEX0499X [Railmount HART]: BAS00ATEX1033X Standards: EN 60079-0: 2012, EN 60079-11: 2012 Markings: [HART]: II 1 G Ex ia IIC T6…T4 Ga; [Fieldbus/Profibus]: II 1 G Ex ia IIC T4 Ga; See Table B-2 for Entity Parameters and Temperature Classifications. Special Condition for Safe Use (X): 1.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 Special Conditions for Safe Use (X): 1. See certificate for ambient temperature range. 2. The non-metallic label may store an electrostatic charge and become a source of ignition in Group III environments. 3. Guard the LCD cover against impact energies greater than 4 joules. 4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA NG April 2015 IECEx Type n - no enclosure Certificate: [Headmount Fieldbus/Profibus, Railmount HART]: IECEx BAS 12.0053X [Headmount HART]: IECEx BAS 12.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 I2 INMETRO Intrinsic Safety Certificate: CEPEL 02.0096X Standards: ABNT NBR IEC 60079-0:2008, ABNT NBR IEC 60079-11:2009, ABNT NBR IEC 60079-26:2008, ABNT NBR IEC 60529:2009 Markings: Ex ia IIC T* Ga; IP66W See Table B-2 for Entity Parameters and Temperature Classifications Special Conditions for Safe Use (X): 1.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA 4. April 2015 During installation, use and maintain in explosive gas atmospheres, observe the warning “Do not open when energized”. During installation, use and maintain in explosive dust atmosphere, observe the warning “Do not open when an explosive dust atmosphere is present”. 5. During installation, there should be no mixture harmful to flameproof housing. 6.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 For Enhanced 644 HART 2. Maximum input power: (W) T code Ambient temperature 0.67 T6 -60 °C ≤ Ta ≤ +40 °C 0.67 T5 -60 °C ≤ Ta ≤ +50 °C 1.3 T4 -60 °C ≤ Ta ≤ +40 °C 5.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 3. This product complies to the requirements for FISCO field devices specified in IEC60079-27: 2008. For the connection of an intrinsically safe circuit in accordance FISCO model, FISCO parameters of this product are as above. 4. The product should be used with Ex-certified associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres.
Appendix B: Product Certifications Reference Manual 00809-0200-4728, Rev RA April 2015 4. Maintenance should be done in non-hazardous location. 5. End users are not permitted to change any components inside, but to settle the problem in conjunction with manufacturer to avoid damage to the product. 6. During installation, use and maintenance of this product, observe the following standards: GB3836.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 Additional Certifications SBS American Bureau of Shipping (ABS) Type Approval Certificate: 11-HS771994A-1-PDA ABS Rules: 2013 Steel Vessels Rules 1-1-4/7.7, 1-1-Appendix 3, 4-8-3/1.7, 4-8-3/13.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 Tables Table B-1.
Reference Manual 00809-0200-4728, Rev RA Appendix B: Product Certifications April 2015 Figure B-1. CSA Intrinsic Safety Installation Drawing 00644-2072.
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA 140 Product Certifications
Reference Manual 00809-0200-4728, Rev RA Product Certifications Appendix B: Product Certifications April 2015 141
Appendix B: Product Certifications April 2015 Reference Manual 00809-0200-4728, Rev RA Figure B-2. CSA Intrinsic Safety Installation Drawing 00644-1064, Rev.
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 Figure B-3. CSA Explosion-Proof Installation Drawing 00644-1059, Rev.
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA 144 Product Certifications
Reference Manual 00809-0200-4728, Rev RA Appendix B: Product Certifications April 2015 Figure B-4. FM Intrinsic Safety Installation Drawing 00644-2071.
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA 146 Product Certifications
Reference Manual Appendix B: Product Certifications 00809-0200-4728, Rev RA April 2015 Figure B-5. FM Intrinsic Safety Installation Drawing 00644-0009, Rev.
Appendix B: Product Certifications Reference Manual 00809-0200-4728, Rev RA April 2015 Sheet 2 of 2 148 Product Certifications
Reference Manual 00809-0200-4728, Rev RA Appendix B: Product Certifications April 2015 Figure B-6. FM Explosion-Proof Installation Drawing 00644-1049, Rev.
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA 150 Product Certifications
Reference Manual 00809-0200-4728, Rev RA Product Certifications Appendix B: Product Certifications April 2015 151
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA 152 Product Certifications
Reference Manual 00809-0200-4728, Rev RA Product Certifications Appendix B: Product Certifications April 2015 153
Appendix B: Product Certifications Reference Manual April 2015 00809-0200-4728, Rev RA 154 Product Certifications
Appendix C: Field Communicator Menu Trees and Fast Keys Reference Manual April 2015 00809-0200-4728, Rev RA Appendix C C.1 Field Communicator Menu Trees and Fast Keys Field Communicator menu trees Figure C-1.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA April 2015 Figure C-2.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA April 2015 Figure C-3.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA April 2015 Figure C-4.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA April 2015 Figure C-5.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA April 2015 Figure C-6.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA C.2 April 2015 Field Communicator Fast Keys Table C-1.
Reference Manual Appendix C: Field Communicator Menu Trees and Fast Keys 00809-0200-4728, Rev RA April 2015 Function HART 5 HART 7 Software Revision 1, 8, 2, 4 1, 8, 2, 4 Tag 2, 2, 7, 1, 1 2, 2, 7, 1, 1 Long Tag N/A 2, 2, 7, 1, 2 Terminal Temperature 2, 2, 7, 1 2, 2, 8, 1 URV (Upper Range Value) 2, 2, 5, 5, 2 2, 2, 5, 5, 2 USL (Upper Sensor Limit) 2, 2, 1, 7, 2 2, 2, 1, 8, 2 Variable Mapping 2, 2, 8, 5 2, 2, 8, 5 2-wire Offset Sensor 1 2, 2, 1, 9 2, 2, 1, 10 2-wire Offset Sens
Appendix D: Local Operator Interface (LOI) Reference Manual April 2015 00809-0200-4728, Rev RA Appendix D Local Operator Interface (LOI) Number entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Text entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual Appendix D: Local Operator Interface (LOI) 00809-0200-4728, Rev RA April 2015 Step Instruction Current position (indicated by underline) 12 Press the enter button to select the decimal, “.”, for the seventh digit. After pressing enter, all digits to the right of the decimal will now be zero. The eighth digit from the left will now be blinking. 000011.0 13 Press the scroll button to navigate through the numbers until the “2”, is on the screen. 000011.
Reference Manual Appendix D: Local Operator Interface (LOI) 00809-0200-4728, Rev RA April 2015 Figure D-1. Menu Scrolling/Text and Digit Scrolling Menu scrolling Text and digit scrolling VIEW CONFIG A L B SENSOR CONFIG L TAG L TAG L c UNITS TAG L z L BACK TO MENU Menu L BACK TO MENU L EXIT MENU EXIT MENU Scrolling backwards Moving backwards during digit or text entry was described above in Digit Entry “Usage Notes”.
Reference Manual Appendix D: Local Operator Interface (LOI) 00809-0200-4728, Rev RA April 2015 D.3 Timeout The LOI in standard operation will Time Out and return to the home screen after 15 minutes of inactivity. To re-enter into the LOI menu press either button. D.4 Saving and canceling The Save and Cancel functionality implemented at the end of a series of steps allows the user to save the change or exit the function without saving any of the changes.
Reference Manual Appendix D: Local Operator Interface (LOI) 00809-0200-4728, Rev RA D.
Reference Manual Appendix D: Local Operator Interface (LOI) 00809-0200-4728, Rev RA April 2015 D.
Reference Manual Index 00809-0200-4728, Rev RA April 2015 Index C Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index April 2015 Index-2 Reference Manual 00809-0200-4728, Rev RA Index
Reference Manual 00809-0200-4728, Rev RA April 2015 Rosemount World Headquarters Emerson Process Management 6021 Innovation Blvd Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com North America Regional Office Emerson Process Management 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@emerson.