Data Sheet

Bulletin 71.1:630
3
Figure 2. Type 630 Sectional Views
FULL SECTION
SPRING
CASE
DIAPHRAGM
DIAPHRAGM
CONNECTOR
DIAPHRAGM
ADAPTOR
VALVE DISK
AND HOLDER
ORIFICE
INLET ADAPTOR
W0428-3*
LEVER
BODY
W0429-3*
BODY ONLY
(ROTATED 90°)
REGISTRATION HOLE
[2-INCH / DN 50 SIZE ONLY]
PITOT TUBE
[1-INCH / DN 25 SIZE ONLY]
Figure 3. Type 630 Operational Schematic
A6673
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
Principle of Operations
Refer to Figure 2. In the regulator construction, outlet
pressure registers beneath the diaphragm. As long
as the outlet pressure is less than the set pressure,
spring force on the diaphragm causes the lever to hold
the valve open. When the outlet pressure exceeds the
set pressure, the diaphragm moves to compress the
spring and the lever closes the valve until the outlet
pressure returns to set pressure.
Capacity Data
Flow capacities are given in Tables 3 and 4 in standard
cubic feet per hour (SCFH) and normal cubic meters
per hour (Nm
3
/h)of0.6specicgravitynatural
gas.Todeterminetheequivalentowrateforother
gases, multiply the table value by the appropriate
factor: air—0.775; butane—0.547; nitrogen—0.789;
propane—0.627.