Installation Manual
Installation, Operation and Maintenance Manual IO-70103 Rev 2, 1/2015
(With AC Applied)
Pin 1 = Normally Open
Pin 2 = Common
Pin 3 = Normally Closed
1 2 3 1 2 3
Surge Rating
Per Mode
A B C D E F Weight
65kA-80kA
16” (406) 14” (356) 8” (203) 16.8” (426) 12” (305) 0.31” (8)
32 lb. (14.5 kg)
100kA-160kA 41 lb. (18.6 kg)
200kA-250kA 20” (508) 16” (406) 9” (229) 21.3” (540) 20” (508) 0.44” (11) 56 lb. (25.4 kg)
Units with Advanced Transient Detection System monitoring option. (NEMA 4/12 enclosure)
65kA-160kA 16” (406) 16” (406) 8” (203) 16.8” (426) 12” (305) 0.31” (8)
See weights
above
200kA-250kA 20” (508) 16” (406) 8” (203) 21.3” (540) 20” (508) 0.44” (11)
Surge Rating
Per Mode
Allowable
Range
Factory Suggested
Size
Circuit
Breaker
Size
Connection Wire
Size
Circuit
Breaker
Size
Connection Wire
Size
With
Disconnect
With Terminals
With
Disconnect
With Terminals
65kA-80kA
40A-150A
15A-100A #8-1/O #14-#2
40 Amp #8 AWG
100kA-160kA 40 Amp #8 AWG
200kA-250kA 100 Amp #2 AWG
NEMA 12 Metal (Modular) Enclosure Option
SUGGESTED CIRCUIT BREAKER AND WIRE SIZE
DIMENSIONAL INFORMATION
Located on PCB behind
monitoring panel
NEMA 4X Non-Metallic (Non-Modular) Enclosure Option
SUGGESTED CIRCUIT BREAKER AND WIRE SIZE
8
Summary Alarm Contacts
Connection shall be with #18 – 22
AWG. Form ‘C’ contacts are rated 5
amps at 250 VAC max.
7.38”
(187.4)
Overcurrent Protection (Circuit Breaker):
Allowable Range: 15A - 30A
Suggested Size: 30A
Connection Wire:
Allowable Range: #14 - #10
Suggested Size: #10
#10 supplied when built with “W=Wire Leads” option.
Weight:
6.5 lb. (3 kg)
Summary Alarm Contacts:
Connection shall be with #18 – 22 AWG.
Form ‘C’ contacts are rated 5 amps at 250
VAC max.
Shown with cover removed
N
C
COM
NO
(With AC Applied)
NO = Normally Open
COM = Common
NC = Normally Closed
A
C
B
E
D
F