Installation Manual

Installation, Operation and Maintenance Manual IO-70103 Rev 2, 1/2015
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or
signs of mishandling before unpacking the
unit.
2. Remove any securing bands and cardboard
packing and inspect the unit for any
obvious shipping damages.
3. If any damage as a result of shipping is
observed, immediately file a claim with the
shipping agency and forward a copy to your
local Emerson Network Power Surge
Protection Sales Representative.
Handling Considerations
Larger units are bolted to a shipping pallet to
facilitate handling by forklift or pallet jack.
Check the size and weight. Refer to the
cabinet data furnished with the unit.
Storage
The unit should be stored in a clean, dry
environment. Storage temperature range is -
55ºC (-67ºF) to +85ºC (+185ºF). Care should
be taken to avoid condensation. All packing
and shipping materials should be left intact
until the unit is ready for final installation. If
the unit has been stored for an extended
period of time, the unit should be cleaned
and carefully inspected before placing into
service.
LOCATION CONSIDERATIONS
For optimum transient surge protection,
coordinated surge suppression should be
applied at the service entrance and all other
electrical connections to the building
(telephone, CATV, etc.), at known surge
generating loads within the building (large
motors, arc welders, switched capacitors,
etc.), as well as at sensitive electronic loads
(such as computers, electronic appliances,
solid state motor drives, etc.). For
interconnected electronic loads (such as by
way of data cabling), transient surge
suppression should also be applied to the
interconnecting wiring (data cables).
Environment — Unit is designed for
operation indoors in ambient temperatures
of -40ºC (-40ºF) to +60ºC (+140ºF) with a
relative humidity of 0% to 95% (non-
condensing).
The unit is provided in an industrial use
enclosure, which is dust-tight and drip-tight
and should not be installed in areas with
excessive dust, corrosive vapors, flammable
materials or explosive atmospheres.
Audible Noise The audible noise of the
unit is less than 40 dB at 5 feet, which allows
its placement within almost any room if
desired.
Service Clearances Service clearance is
needed for units with hinged doors on the
front that are capable of being opened.
Thirty-six inches (36 in/914 mm) minimum is
recommended.
Mounting — Unit is intended to be wall
mounted. Refer to installation instructions for
mounting dimensions and weight.
Warnings Defined —
Danger: Indicate[s] a
hazardous situation which, if not avoided, will
result in death or serious injury. The signal
word "DANGER" is to be limited to the most
extreme situations. DANGER [signs] should
not be used for property damage hazards
unless personal injury risk appropriate to
these levels is also involved.
Danger:
Indique une situation dangereuse
qui, si elle n'est pas évitée, entraînera la mort
ou des blessures graves. Le mot comme
signal «DANGER» doit être limité aux
situations les plus extrêmes. Les signes
DANGER ne doivent pas être utilisés pour les
risques de dommages à la propriété, sauf si le
risque de blessures appropriées à ces niveaux
est également impliqué.
(continued)
2