Installation Manual

Installation, Operation and Maintenance Manual IO-70103 Rev 2, 1/2015
A B C D E F G
18”
(457)
12”
(305)
6”
(152)
11”
(279)
15”
(381)
20.25”
(514)
21.5”
(546)
NEMA 1 Panelboard Extension (Modular) Option
SUGGESTED CIRCUIT BREAKER AND WIRE SIZE
Overcurrent Protection (Circuit Breaker):
Allowable Range: 15A - 100A Suggested Size: 30A
Connection Wire:
Allowable Range: #14 - #2 Suggested Size: #10
Weight:
30 lb. (13.6 kg)
Summary Alarm Contacts:
Connection shall be with #18 – 22 AWG.
Form ‘C’ contacts are rated 5 amps at 250 VAC max.
Shown with module cover removed
DIMENSIONAL INFORMATION
9
A
C
B
E
D
F
(
SURFACE
)
G
(FLUSH)
(With AC Applied)
NO = Normally Open
COM = Common
NC = Normally Closed
Customer
Supplied
Panelboard
510 SPD
Panelboard
Extension