AC Power For Business-Critical Continuity™ Liebert® GXT3™ 230V, 5000-10,000VA User Manual
TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.5 Shut Down the Liebert GXT3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 8.6 Disconnecting Input Power from the Liebert GXT3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 8.7 Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 8.8 IT Power System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FIGURES Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Liebert GXT3 5000VA and 6000VA, front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Liebert GXT3, rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Internal battery pack with connector . . .
iv
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions. Read all safety and operating instructions before operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training. This product is designed for commercial/industrial use only.
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 complies with the limits of Category C2, pursuant to IEC/EN/AS 62040-2. Operation is subject to the following conditions: • The output cables shall be no longer than 10m (32ft). • This device may not cause harmful interference. • This device must accept any interference received, including interference that may cause undesired operation.
GLOSSARY OF SYMBOLS Risk of electrical shock ! Indicates caution followed by important instructions AC input AC output i - Requests the user to consult the manual + Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 R Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Manual Battery Test OFF/Bypass WEEE 3 Liebert® GXT3™
Introduction 1.0 INTRODUCTION Congratulations on your choice of the Liebert GXT3 uninterruptible power system (UPS). The Liebert GXT3 comes in nominal power ratings of 5000VA, 6000VA and 10,000VA. It is designed to provide conditioned power to microcomputers and other sensitive electronic equipment. When it is generated, alternating current is clean and stable.
System Description 2.0 SYSTEM DESCRIPTION Output Input Dynamic Bypass L1 N Rectifier /PFC DC-to-DC Converter TVSS & EMI/RFI Filters Inverter L1 N Battery Charger Battery G 2.1 G Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected. 2.
System Description 2.5 DC-to-DC Converter The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability. 2.6 Battery The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 15°C to 25°C (59°F to 77°F).
Major Components 3.0 MAJOR COMPONENTS The Liebert GXT3 is composed of three major assemblies to provide easier handling, installation and versatility. 3.1 Main Frame and Electronics The cabinet is shipped with internal batteries installed and a basic, hardwire distribution box attached and ready to install.
Major Components Figure 2 Liebert GXT3, rear view Liebert GXT3, 5,000 & 6000VA Terminal Block Communication REPO Liebert IntelliSlot® Port C19 Output Power Receptacles USB Port External Battery Connector Output Circuit Breakers IT Power System Access Cover Output Circuit Breakers C13 Output Receptacles Removable Power Distribution Box factory-attached in bottom-left corner Maintenance Bypass Breaker Output Circuit Breaker Knockouts for Hardwired Power Input Input Circuit Breaker Liebert GX
Major Components 3.2 Internal Battery Packs The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal battery pack is fitted with a connector to link to the UPS. Figure 3 Internal battery pack with connector Battery Handle GXT3 10,000 Battery Pack shown; 5000 and 6000VA battery packs have same features Battery Connector Front of Battery Pack 3.3 Removable Power Distribution Box The UPS arrives with a power distribution pack installed.
What’s Included 4.0 WHAT’S INCLUDED The Liebert GXT3 is shipped with the following items: • Terminal Block Communication terminals • Compact Disk with • Liebert MultiLinkt® • Configuration program • User manual (electronic version) • USB cable, one; 2m (6-1/2 ft.
Installation and Configuration 5.0 INSTALLATION AND CONFIGURATION Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 8.2 - Initial Startup and Electrical Checks. Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Emerson® representative. ! CAUTION The UPS is heavy (see 12.0 - Specifications). Take proper precautions when lifting or moving it.
Installation and Configuration b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into position, as shown in Figure 8. Figure 8 Rotate the operation and display panel Operation and Display Panel Rotated Clockwise 90 Degrees c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back into position. The rotated front plastic bezel cover is shown in Figure 8. d.
Installation and Configuration The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack. To install the rack mount brackets: 1. Unpack two (2) rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are interchangeable between left-hand or right-hand.
Installation and Configuration 6. If available, apply a bead of grease 25mm (1") long at four (4) places inside the bottom, curved tracks of the front members as shown below right. The grease will allow the equipment to slide into the bracket assemblies more easily. ! CAUTION Lifting equipment into the rack may be a two-person job, depending on the weight of the equipment. Emerson® recommends taking the internal batteries out of the UPS during rack installation.
Installation and Configuration Figure 9 External battery cabinets connected to 10,000VA Liebert GXT3 10,000VA Liebert GXT3 Cables connecting battery cabinets to 10,000VA Liebert GXT3 Battery Cabinets 1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Emerson® representative. 2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove.
Installation and Configuration 5.3 Connect Input/Output Power Figure 10 Power Distribution box removal—captive screws and maintenance bypass breaker Extract these captive screws Maintenance Bypass Breaker The UPS should arrive with the power distribution box attached. If the box needs to be removed for maintenance or replacement, follow these instructions to remove and install the power distribution pack. To remove: 1. Ensure maintenance bypass lamp is on.
Installation and Configuration 5.3.1 Distribution Box Electrical Connections Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS. • PD2-CE6HDWRMBS fits the 5000 and 6000VA models of the Liebert GXT3 • PD2-CE10HDWRMBS fits the 10,000VA model of the Liebert GXT3 The installer must provide an upstream branch circuit breaker.
Installation and Configuration Figure 12 Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS PD2-CE6HDWRMBS L N L OUTPUT INPUT PD2-CE10HDWRMBS N L N INPUT L N OUTPUT NOTE The installer must provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.
Configuration Program 6.0 CONFIGURATION PROGRAM The final step of installation may require custom configuration of your UPS using the enclosed configuration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full-time service powering the critical load. For most users operating with 230VAC and with no external batteries, the factory default settings will be adequate. 6.
Controls and Indicators 7.0 CONTROLS AND INDICATORS Battery Level Indicators Load Level Indicators Fault Indicator Bypass Indicator AC Input Indicator Inverter Indicator Liebert ® GXT3 AC Power System 10000VA On/Alarm Silence/Manual Battery Test Button Standby/Manual Bypass Button 7.
Controls and Indicators off power to the output sockets and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice. 7.3 Load Level Indicators (4 Green, 1 Amber) The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in Figure 13.
Controls and Indicators Figure 14 Battery level indicators. Charging Discharging 0 - 20% Flash OFF OFF OFF OFF ON OFF OFF OFF OFF OFF OFF OFF ON ON OFF OFF OFF Flash OFF OFF ON ON ON OFF OFF 21 - 40% ON Flash ON ON 41 - 60% 61 - 80% ON ON ON Flash OFF ON ON ON ON OFF 81 - 100% ON ON ON ON Flash ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON Fully Charged 7.
Operation 8.0 OPERATION This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the UPS. NOTE The Liebert GXT3’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping. To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before putting the UPS into service. 8.
Operation 8.3 Manual Battery Test To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from mains power with no alarm conditions present. • If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours. • Retest the batteries after 24 hours of charging.
Operation 8.8 IT Power System Configuration 1. Remove screws on the IT Power System Access Cover as shown in Figure 15. 2. Disconnect the connectors as shown in figure. 3. Install IT Power System Access Cover and screws.
Communication 9.0 COMMUNICATION 9.1 Communication Interface Port The Liebert GXT3 UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows. 9.2 Terminal Block Communication The terminal block includes eight pins, as shown in Figure 16. Figure 16 Terminal block communication terminals 9.2.
Communication 9.2.2 Battery Mode Shutdown Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active. Battery Mode Shutdown can be performed locally or remotely: • Local Battery Mode shutdown can be performed by shorting the pins in Set 4.
Communication 9.3.1 Liebert MultiLink® Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the event of an extended power failure. Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot® SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to coordinate shutdown across the network with other computers running Liebert MultiLink when you purchase a Liebert MultiLink License Kit.
Maintenance 10.0 MAINTENANCE This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s status and checking UPS functions. 10.1 Replacing the Internal Battery Pack The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Read the safety cautions before proceeding. Contact your local dealer or Emerson® representative to obtain the part number and pricing of the appropriate replacement battery pack. 10.1.
Maintenance Figure 19 Pulling out the battery packs 10,000VA model 5000 & 6000 VA models Internal Battery Pack Internal Battery Pack Battery Handle Battery Handle Pull Out with Battery Handle Each model has two battery packs Pull Out with Battery Handle 6. Unpack a new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery packs to make sure they are the same type and model.
Maintenance 10.4 Checking UPS Status Emerson® recommends checking the UPS operation status every six months. • Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm? • Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support. • Check whether the battery is discharging.
Troubleshooting 11.0 TROUBLESHOOTING This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation. 11.1 UPS Symptoms The following symptoms indicate the Liebert GXT3 is malfunctioning: • The relative indicators illuminate, indicating the UPS has detected a problem.
Troubleshooting 11.1.2 Audible Alarm An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in Table 5.
Troubleshooting Table 6 Troubleshooting table (continued) Problem Cause Solution Fault and Bypass indicators and diagnostic C indicator are illuminated UPS DC/DC fault UPS requires service. Contact your local dealer, Emerson® representative or Emerson Channel Support. Fault indicator and diagnostic D indicator are illuminated UPS PFC (Power Factor Correction Circuit) fault UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.
Specifications 12.0 SPECIFICATIONS Table 7 UPS specifications Model # Rating GXT3-5000RT230 GXT3-6000RT230 GXT3-10000RT230 5000VA/4000W 6000VA/4800W 10000VA/9000W Dimensions, mm (in) Unit, W x D x H 430 x 574 x 217 (16.9 x 22.4 x 8.5) 430 x 581 x 261 (16.9 x 22.9 x 10.3) Shipping, W x D x H 516 x 745 x 530 (20.3 x 29.3 x 20.9) 530 x 745 x 563 (20.9 x 29.3 x 22.2) Weight, kg (lb) Unit 60 (132.2) 70 (154.3) Shipping 71 (156.5) 92 (202.
Specifications Table 7 UPS specifications (continued) Model # GXT3-5000RT230 GXT3-6000RT230 Relative Humidity GXT3-10000RT230 0-95% non-condensing Operating Elevation Up to 1000m (3281 ft) at 25°C (77°F) without derating Audible Noise <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides Agency Safety IEC62040-1:2008 version, GS mark EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6) ESD IEC/EN EN61000-4-2, Level 4, Criteria A Radiated Susceptibility IEC
Specifications Table 10 External battery cabinet specifications GXT3-240VBATTCE GXT3-240RTVBATT GXT3-5000RT230 GXT3-6000RT230 GXT3-10000RT230 Unit (with bezel) 430 x 574 x 130 (16.9 x 22.6 x 5.8) 430 x 581 x 173 (16.9 x 22.9 x 6.8) Shipping 530 x 745 x 407 (20.9 x 20.3 x 16.0) 530 x 745 x 475 (20.9 x 29.3 x 18.7) Unit 43 (94.8) 65 (143.3) Shipping 54 (119) 76 (167.6) Model Number Used with UPS Model Dimensions, W x D x H, mm (in.
Specifications Table 11 Battery run time, minutes, all models Number of Batteries/Cabinets Internal Battery Internal Battery + 1 External Battery Cabinet Internal Battery + 2 External Battery Cabinets Internal Battery + 3 External Battery Cabinets Liebert® GXT3™ 230VAC RT Models Load Percent of Capacity 5kVA 6kVA 10kVA 10% 105 97 81 20% 52 47 39 30% 40 33 22 40% 27 22 15 50% 21 17 11 60% 17 14 9 70% 14 11 7 80% 12 9 5 90% 10 8 4 100% 9 6 3 10% 187 158
Specifications Table 11 Battery run time, minutes, all models Number of Batteries/Cabinets Internal Battery + 4 External Battery Cabinets 230VAC RT Models Load Percent of Capacity 5kVA 6kVA 10kVA 10% 460 360 316 20% 205 191 163 30% 159 138 137 40% 124 108 107 50% 106 97 82 60% 98 81 69 70% 83 71 52 80% 75 61 48 90% 66 51 44 100% 53 48 40 Using the configuration program, the user may specify the number of GXT3-240VBATT external battery cabinets attached to th
Specifications Liebert® GXT3™ 40
Ensuring The High Availability Of Mission-Critical Data And Applications. Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™ from grid to chip for telecommunication networks, data centers, health care and industrial facilities.