ACTURA Flex 48330 Power System User Manual Version: Revision date: BOM: V1.0 May 20, 2005 31011084 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2005 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd.
Safety Precautions To avoid accident, read the safety precautions very carefully before operation. The "Caution, Notice, Warning, Danger" in this manual do not represent all the safety points to be observed. Therefore, the installation and operation personnel must be strictly trained and master the correct operations and all the safety points before actual operation.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well-earthed in time to avoid damage by lightning strikes. 4. ESD The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive elements. The other end of the ESD wrist strap must be well earthed.
Special Safe Requirements of This Equipment The equipment has multi power inputs; The equipment shall be installed on cement ground. Others 1 Safety requirement Please use the same model fuse to replace the fuse in the DC Power System. 2. Sharp object When moving equipment by hand, wear protective gloves to avoid injury by sharp object. 3. Cable connection Please verify the compliance of the cable and cable label with the actual installation prior to cable connection. 4.
Contents Chapter 1 System Description................................................................................................1 1.1 Abbreviation ..............................................................................................................1 1.2 Introduction ...............................................................................................................1 1.3 Features..........................................................................................................
Chapter 4 Testing................................................................................................................. 32 4.1 Testing MFU ...........................................................................................................32 4.2 Testing Rectifier ......................................................................................................32 4.3 Testing SCU............................................................................................................
6.5.2 6.5.3 Daily Inspection.............................................................................................73 Replacement.................................................................................................74 Chapter 7 Troubleshooting...................................................................................................75 7.1 Troubleshooting Rectifier ........................................................................................75 7.2 Mains Failure .........
Table List Table 1-1 Configurations of Actura Flex 48330 Power System ..............................................3 Table 1-2 Dimensions of rectifier shelf ...................................................................................5 Table 1-3 Function of indicators .............................................................................................7 Table 1-4 Authority and default password..............................................................................
Figure List Figure 1-1 Outline ..................................................................................................................2 Figure 1-2 Rectifier shelf outline.............................................................................................4 Figure 1-3 Rectifier shelf with rectifiers and CU .....................................................................4 Figure 1-4 Dimensions ......................................................................................
Chapter 1 System Description Chapter 1 1 System Description 1.1 Abbreviation 1.2 AC Alternate Current DC Direct Current SCU Standard Controller Unit BCU Battery Connection Unit CSU Central Supervision Unit HVSD High Voltage Shutdown MCB Miniature Circuit Breaker APFC Active Power Factor Correction MFU Multi-Function Unit Introduction The ACTURA Flex 48330 Power system consists of 50A rectifiers, Control Unit, Multi-Function Unit (MFU), rectifier shelf and BCU (optional).
2 Chapter 1 System Description High power density of rectifier; Rectifier has damage-free hot plugging/unplugging function, the replacement time is less than 1min; Rectifier has two kinds of over-voltage protection methods; Perfect battery management with BLVD function; Up to 200 PCS of historical alarms can be stored in SCU; Provide RS232, Modem and dry contacts communication interfaces; 1.
Chapter 1 System Description Table 1-1 Configuration Configurations of Actura Flex 48330 Power System Cabinet dimension 2.0 % 0.6 % 0.6 m 3 2.0 % 0.6 % 0.4 m3 0.7 % 0.6 % 0.
4 Chapter 1 System Description 1.5 Components 1.5.1 Rectifier Shelf Outline The outline of the Rectifier Shelf is illustrated in Figure 1-2: Terminal connecting 50A Rectifier Chassis Connector Board Ear Bracket (a) Actual appearance (front view) Bus Bar Back Board (b) Actual appearance (rear view) Figure 1-2 Rectifier shelf outline The shelf can accommodate 5 rectifiers and a control unit as shown in Figure 1-3.
Chapter 1 System Description The Dimension of Rectifier Shelf are given in Table 1-2 Table 1-2 Dimensions of rectifier shelf Manufacture type W(mm) ×D(mm) ×H(mm) Note PSS485023/C 584.2×327×132.5 23’’ with controller Backboard The backboard has the functions below: DC power source feed for controller and the connector board. DC input filter and input fuse.
6 Chapter 1 System Description One Ethernet output One RS485 output One console output for ECU debug The connector board can be hot plug and has enough space for accommodating all the interface cables. The connector board should space the hollow to the SCU convection for air flowing The connector board is mounted in the room 1U×2U at the top of the SCU. The shelf has a 1U×2U panel for the connector board. One RS232 and Ethernet ports are located at the front of the connector board.
Chapter 1 System Description Table 1-3 LED Power indicator (green) Protection indicator (yellow) Alarm indicator (red) 1.5.
8 Chapter 1 System Description When SCU communicates with MC through MODEM or ES-MOD, it uses PSTN to realize long-distance monitoring. Power supply cables and communication cables shall be prepared for the communication through MODEM. 3. Dry Contacts Output SCU has 8 dry-contact outputs. Every dry-contact output has NC (normally closed) and NO (normally-open) contacts. Every dry-contact output shall be configured before the alarm event occurs. Different dry-contact output can trigger different alarms.
Chapter 1 System Description 9 Password protection for important operations The users must input the correct password before they conduct “Maintenance” and “Settings” operations. The password has 3 levels: user, operator or administrator. The authorities of the 3 levels are the same while conducting “Maintenance”, but different in conducting “Settings”. The operator can see 3 more pages than the user, which are “resetting system”, “resetting password” and “modifying system type”.
10 Chapter 1 System Description Table 1-5 No.
Chapter 1 System Description 11 alarm generated from battery circuit breakers that are switched off in the BCU (for example when using a BCU in an extension battery cabinet and battery circuit breakers in the BCU in a main cabinet). BCU configuration The BCU configuration is as shown in Table 1-6: Table 1-6 Item Battery connection unit 1.5.6 BCU configuration Function unit Amount 100A CB for battery input 2/3/4/5 200A CB for battery input 2/3/4/5 System Cabinet There are three kinds of cabinets.
12 Chapter 2 Installation Chapter 2 2.1 Installation Preparation 2.1.1 Environmental Conditions Installation Make sure the following environmental conditions are satisfied when selecting the installation site: Table 2-1 Environmental conditions in power room Environmental conditions Recommended range Ambient temperature -5~50°C (If ambient temperature > 45°C, for the cabinet with 400mm depth, it should demount the front door of cabinet to ensure the normal operation of the system.
Chapter 2 Installation 13 voltage AC power supply system should adopt three-phase five-line or single-phase three-line modes. The AC power cable should adopt copper core cable, and the cable section should suit the load. It is recommended that the power cable outside the power room be buried directly under the ground or by means of cable pipe. Power cable should be wired separately from signal line. The AC mains voltage shall be within the range of the voltage input range of rectifiers.
14 Chapter 2 Installation In this formula: A is the sectional area of the lead (mm2), ΣI is the total current (A) flowing through the lead, L is the length (m) of the lead loop, △U is the permitted voltage drop on the lead, while K is the conductivity. Kcopper=57. For safety, the voltage drop on the cables connecting battery and load cannot exceed 3.2V.
Chapter 2 Installation 2.2 Installation Procedures 2.2.1 Cabinet Installation 15 Installation on the floor Step 1: mark the position where the power system is to be installed. Determine the installation position of the power supply cabinet in the power room according to the installation chart. Based on the mechanical specifications (see Fig.
16 Chapter 2 Installation not to shake the drill, and try to keep as vertical as possible to the ground, as shown in Figure 2-2. Step 3: install expansive pipes. Clean the dust, and insert the expansive pipe into the reserve hole, knock it down gently using a hammer until the top of the expansive pipe is level with the ground, as shown in Figure 2-2.
Chapter 2 Installation 17 2.3 External Electrical Connection Interface 2.3.1 Connection Of Input Cables The AC input terminals, SPD, rectifier AC input switch, PE bus and PE terminals are illustrated in Figure 1-6. SPD is just adjacent to the AC input terminals and has been connected in before delivery. PE bus is at the top of the MFU and is connected to the DC Power Cabinet through screws. PE bus is connected PE terminal through a cable.
18 Chapter 2 Installation AC input terminals Figure 2-5 Connection of input terminals The AC input cable is fed to the system through the top cover of the cabinet, as shown in Figure 2-6: AC input cable Cable bracket Figure 2-6 Top cover Top cover There is a cable bracket on the top cover. The input cables are bound to the cable bracket with a cable tie. Different cable connection modes There are 4 AC input terminals.
Chapter 2 Installation 19 For single-phase AC power input, connect the AC input cables as in Figure 2-8: L N AC Input Terminals Figure 2-8 Connection of single-phase AC power input If the AC input is single phase, the second and fourth terminals are not connected. For dual-phase AC power input, connect the AC input cables as in Figure 2-9: L1 L2 AC Input Terminals Figure 2-9 Connection of dual-phase AC power input If the AC input is dual-phase, the second and fourth terminals are not connected.
20 Chapter 2 Installation 2.3.2 Connection Of Load Cables Loads are connected to the MCB with suitable capacity to avoid their failure to function in the case of overload. The capacity of the MCBs is recommended to be about 1.5 times of the peak value of the load capacity. The load circuit breakers are shown in Figure 1-7. The circuit breakers can be ABB or CBI circuit breakers. We take the CBI circuit breakers of 13mm for example to illustrate the load cable connection, as shown in the Figure 2-10.
Chapter 2 Installation 21 Note 1. The cable should not be spliced. The load cable, signal cable and AC cables should be wired separately as possible to avoid them affecting each other. 2. If the power supply system is in operation, switch off the DC output MCB before connecting the cables. 3. The rated current of the output cable should be bigger than that of the corresponding MCB connected with it. DC output branch should match the load capacity.
22 Chapter 2 Installation 2.3.
Chapter 2 Installation 2.3.
24 Chapter 2 Installation Connector J14 J19 2.3.6 Pin 1 2 3 1 2 Signal name RS485 communication+ RS485 communicationProtection ground 48V+ 48V- Mark number Logic relation E485+ E485PGNG POWER+ POWER- Connection Of Temperature Sensor Cables There are two 3-pin terminals on the connector board in rectifier shelf. These two terminals are J11 and J10 respectively. They are used to connect the temperature sensors. The locations of J11 and J10 are as shown in Figure 2-12.
Chapter 2 Installation 2.3.8 25 Connection With Dry Contacts The M500D monitoring module provides 8 sets of alarm dry contacts through the J3-J6 sockets on the connector board S6415X2. Each set has a normally open contact and a normally closed contact. Once the corresponding alarm event occurs, the dry contact will act to report alarms under the control of M500D monitoring module. Through the dry contact networking, the system can realize the level isolation transmission of fault signals.
26 Chapter 2 Installation Battery Connection Unit(BCU) Battery(4 in a string) Battery Shelf Figure 2-15 Cabinet with four battery strings installed Note To satisfy the safety requirement of the whole equipment, the fire-retardant class of the battery materials should not be lower than V-2. Insure that the charge/discharge current of single battery group is not bigger than 100A, and the total charge/discharge current of the all battery groups are not bigger than 200A. 2.4.
Chapter 2 Installation battery cable is connected to the negative terminals of the battery string in each level as shown in Figure 2-16: Negative Battery Cables 4 Battery Circuit Breakers Figure 2-16 Connection of battery cables.
28 Chapter 2 Installation Note The actual number of battery circuit breakers in MFU may be 0~5 according to the user’s need. Non-standard configuration The DC power system with non-standard configuration has a BCU. The connection of positive cables is the same with that of the system with standard configuration. The only difference is that there are five positive battery cables because the system has five battery strings.
Chapter 2 Installation 29 2.5 Parallel Connection Of Cabinets In order to prolong the backup time of battery, the battery capacity should be increased. Another cabinet can be connected in parallel with the DC power system cabinet. The expanded cabinet has no rectifier shelf and Multi-Function Unit. It is only installed with battery strings and a BCU. So, it is actually the battery cabinet. BCU in Extension Unit connects to Main Unit through cables.
30 Chapter 3 Startup Chapter 3 Startup 3.1 Checking Before Startup Check the DC Power System according to Table 3-1 before startup. Table 3-1 Item 1 2 3 4 5 Action System checklist before startup Result Check all the circuit breakers of the shelf and BCU Check the mains supply fuses/circuit breakers. Check with an ohmmeter between the positive and negative terminals of battery. Check with an ohmmeter between the battery terminals and shelf chassis.
Chapter 3 Startup 31 3.2 Startup Process Item 1 2 3 4 5 6 Action Result Comments (Fill in “OK” or not) The LEDs on the rectifiers and the controller will emit light. The rectifier fans will start. Connect/switch on the mains supply The LVD contactors will operate. fuses/circuit breakers of the DC shelf. The green LEDs of the rectifiers and the controller will flash for about 10 s. and then emit steady light. The voltage should be close to what has been set in the controller.
32 Chapter 4 Testing Chapter 4 Testing 4.1 Testing MFU Measure the L-N voltage at the input terminals with a multi-meter to check if it is normal. 4.2 Testing Rectifier 1. Turn on one rectifier input MCB in the MFU to feed AC supply to the corresponding rectifier, the rectifier should operate normally; 2. Turn off this MCB, and turn on the other rectifier input MCBs one by one to check if all the other rectifiers operate normally. If all of the rectifiers can operate normally, switch them on.
Chapter 4 Testing 33 4.4 Battery Breaker Test 1. Before turning on the battery circuit breaker, confirm with a multi-meter that the battery is not reverse-connected. 2. When connecting the battery, be careful not to short the two battery terminals. 3. When connecting two batteries, be careful to avoid battery mutual charging due to unequal terminal voltages of the two batteries. 4.5 BCU Test The BCU can connect to a single battery via suitably sized cables from the Distribution Unit.
34 Chapter 5 Operating SCU Chapter 5 5.
Chapter 5 Operating SCU 5.2 35 Operation Procedures After the system is powered on for the first time, you should set the system type according to the actual configuration. The monitoring module will restart after the system type is changed. In that case, you should re-configure those parameters whose default values are inconsistent with the actual situation. Only after that can the monitoring module operate normally.
36 Chapter 5 Operating SCU 4. At any system information page, press “ENT” to enter the “MAIN MENU” page, which contains 3 sub-menus: “Status”, “Maintenance” and “Settings”. Main Menu Status Maintenance Settings You can press “ ” or “ ” repeatedly to select a sub-menu, and press “ENT” to enter the sub-menu. Press “ESC” to return to the menu of higher level. 1) Status Including rectifier information, active alarm information and alarm history information.
Chapter 5 Operating SCU 37 other shows hour, minute and second. The year is displayed with 4 digits; other time units are in 2 digits. 10:09:16 53.5V 125 A System: No alarm Auto /BC 2004-09-16 53.5V 125 A System: No alarm Auto /BC Note 1. At this page, you may use “ ” and “ " to adjust the LCD contrast (7-level). 2. If there has been no keypad operation for 8 minutes, the monitoring module will return to the first system information page.
38 Chapter 5 Operating SCU 2. Actual battery capacity The monitoring module can approximately calculate the remaining battery capacity in real time. Through configuration at the host, the remaining battery capacity can be displayed in the mode of percentage, remaining Ah or remaining time, etc. The default is the percentage. During the normal BC/FC management, the monitoring module regards the rated capacity as the capacity that each battery group can reach.
Chapter 5 Operating SCU 39 The 2nd and 3rd rows of the page are the temperature information detected by the temperature sensor. The display will vary with different parameter settings (see 4.7 for parameter setting). If the temperature sensor is not connected or is faulty, system will prompt invalid. Meanwhile, the 4th row will display “Check Temp Sensor”. 5.4 Querying Rectifier Status The rectifier information includes the rectifier serial No.
40 Chapter 5 Operating SCU 5. At any rectifier information page, press “ESC” repeatedly and you can return to the higher-level menus. 5.5 Querying Alarms And Setting Alarm Plans The monitoring module can locate and record the system fault according to the collected data, as well as raise audible/visual alarms and output through dry contact according to the preset alarm level. Meanwhile, it reports the alarms to the host.
Chapter 5 Operating SCU 41 2) If there is any alarm, the display will be like the following: Active Alarm! 3 1 Major Alarm AC! Ph-A Failure 040412 12:30:23 The information in the active alarm information pages includes: alarm serial No., alarm level, alarm name and time (year, month, day, hour, minute and second). The alarm raising time determines the sequence it is displayed, with the latest alarm displayed first. Use “ ” or “ ” to view all active alarms.
42 Chapter 5 Operating SCU Status Rectifiers Active Alarm Alarm History 3. Use “ ” or “ ” to select the “Alarm History”, as shown in the above figure and press “ENT” to confirm. If there is no historical alarm, the prompt will be “Alarm History: None”. ALARM HISTORY None The historical alarms of the monitoring module are stored in cyclic order. Up to 200 alarms will be recorded. Above that, the earliest alarm will be cleared automatically.
Chapter 5 Operating SCU 43 5.5.3 Alarm Type Table Table 5-3 Serial No. 1 2 Alarm Alarm type table Description Default alarm level Input MCB Trip SPD Fault The system AC input MCB tripped The SPD circuit is faulty 3 Digit Input Fault The alarm name is user defined, not longer than 10 characters. The No alarm high/low level alarm can be set in the alarm mode.
44 Chapter 5 Operating SCU Serial No.
Chapter 5 Operating SCU Serial No.
46 Chapter 5 Operating SCU Note When the DC load 9 and its above (load 10, load 11 …) have circuit fault alarm, the monitoring module all display “Load 9 Failure” or “Aux Load Fails”. 5.5.4 Changing Audible/Visual Alarm And Alarm Call Back Plan There are different audible/visual alarms and call back modes for alarms of different levels. For the products in China market, the alarming mode for major alarms and critical alarms are the same.
Chapter 5 Operating SCU *: The logic relationship between the two alarms. Options: “And”/”Or”.
48 Chapter 5 Operating SCU Alarm type Remark BLVD Output voltage abnormal AC power off Multiple rectifiers alarm Time for system maintenance (replace the fan) Any rectifier comm interrupted Any rectifier AC power off Any rectifier over-temperature Any rctifier faulty Any rectifier in protection Any rectifier fan faulty Any AC derated rectifier Any temperature derated rectifier For example: To make dry contact No.
Chapter 5 Operating SCU Table 5-6 Logic matrix used for configuring 8 dry contacts Setting 0,1 Alarm SN Logic Alarm SN Column(B) 0 Row(A) Dry Contact 0 0 Dry Contact 1 1 Dry Contact 2 2 Dry Contact 3 3 Dry Contact 4 4 Dry Contact 5 5 Dry Contact 6 6 Dry Contact 7 7 49 1 2 Logic Alarm SN 4 5 3 The format of PLC setting is AlarmPLC[A][B]=C. Where, “A” is the row No., and “B” is the column No., and “C” is the value of the matrix element.
50 Chapter 5 Operating SCU PLC SN Alarm description Remark 6 Load 6 Failure 7 Load 7 Failure 8 Load 8 Failure 9 Load 9 Failure 10 Aux Load Fails Load 10 is Auxiliary Load for China Market 11 SPD Fault Enabled when an AC Signal Acquisition Board is installed. 12 Input MCB Trip Enabled when an AC Signal Acquisition Board is installed.
Chapter 5 Operating SCU PLC SN 5.6 Alarm description 41 Short Test Error 42 BattTest Error 43 LLVD 44 BLVD 45 Outvolt Error 46 Power Failure 47 Multi-Rect Fails 48 Rect Fan Fails 49 Rect Com Failure 50 Rect Vac Err 51 Rect Over Temp 52 Rect Failure 53 Rect Protect 54 Rect Fan Fails 55 Rect PowerLimit 56 Derateby Temp 51 Remark Disabled for China Market, Enabled for rest of world Maintenance Note 1.
52 Chapter 5 Operating SCU To input the password, use “ ” or “ ” to modify numbers, and use “ move the cursor. After the input, press “ENT” to confirm. ” or “ ” to If the password is incorrect, system will prompt “password incorrect”. If the password is less than 6 digits, end it with a “#”. Note You can choose to enter the “Maintenance” menu by using either the user, operator or administrator password, for in this menu, all users have the same authority. 4.
Chapter 5 Operating SCU 53 The maintenance operations over a single rectifier include: “DC ON/OFF”, “AC ON/OFF” and “Reset”. The operation method is: ① Use “ ” or ” ” to select the rectifier parameter, and “ ” or “ ” to change the rectifier serial No. Then press “ENT” to confirm. The bottom line of the page displays the rectifier ID. ② Use “ “ ” or “ ” or “ ” to move the cursor to the maintenance operation area, and ” to select the value.
54 Chapter 5 Operating SCU 2. Use “ ” or “ ” to select the submenu “Settings” and press “ENT” to confirm. System will then prompt you to input the password. Enter Password: 123456 3. Press " " or " " to select the number of password digits. Enter the password digit by digit using “ ” or “ ”. Press “ENT” to confirm and enter the parameter setting submenu.
Chapter 5 Operating SCU 55 Battery Setting Batt. Selection LVD Setting Charge Battery Setting Batt. Test Temp Comp What follows is the description of the parameter functions and values by dividing them into 5 small categories and 5 big categories. 5.7.2 Batt. Selection 1. The first page of the Batt. Selection is shown below: Mode: Manual Batt String: 1 Capacity: 300Ah Batt Name: 1# Use “ ” or “ ” to select the page and the parameter to be set, and “ select the proper value for the parameter.
56 Chapter 5 Operating SCU 3. If setting parameter “System Type” requires setting the battery shunt coefficient, the second page of the basic battery settings is as follows: Batt Shunt1: Yes Batt Shunt2: No Shunt Coeff: 300A / 75mV 4. The value description of the basic battery parameters is listed below: Table 5-10 Parameter Mgmt Mode (Management mode) Batt String (number of battery strings) Rated AH (rated capacity) BTT Name Battery Name Batt Shunt1 Batt Shunt2 Shunt Coeff (shunt coefficient) 5.7.
Chapter 5 Operating SCU 57 LLVD Enable: Y BLVD Enable: Y LVD Mode: Voltage LVD Vlotage LLVD: 44.0 BLVD: 43.2 LVD Time LLVD: 300min BLVD: 600min Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save. ” or “ ” to Note Generally you do not need to set the LVD parameters’ value. The defaults will do. 3. The value description of the LVD parameters is listed below.
58 Chapter 5 Operating SCU Automatic Boost Y Cyclic Boost: Y To Boost Current: 80% Capacity: 0.06C10 Constant Boost Current: 0.01C10 Duration: 180min Cyclic Boost Interval: 400h Duration: 300min Boost Limit Time: 300min Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save. ” or “ Note Generally you do not need to set the management value. The defaults will do. 2.
Chapter 5 Operating SCU Table 5-12 Parameter Range Float Charging management parameter value description Default 53.5V 42V ~ 58V Boost Limit (current limit) 56.4V 0.1 ~ 0.25C10 0.1C10 Over (over current 0.3C10 ~ 1.0C10 0.300C10 point) Automatic Boost Yes, No To Boost Capacity 0.1 ~ 0.95 Select “Y”, and the monitoring module will control the system to enter the Cyclic Boost when the FC time reaches the “Cyclic Boost Interval”.
60 Chapter 5 Operating SCU 5.7.5 Battery Test Parameters 1. There are 7 related pages, as shown below: Battery Test Voltage: 45.2 Time: 300min Test End Cap: 0.700C10 Planned Test: N Planned Test1: 01.02 12Hr Planned Test2: 04.02 12Hr Planned Test3: 07.02 12Hr Planned Test4: 07.02 12Hr Short Test: Enable: Y Alarm Current 10A Short Test: Cyclye: 300h Duration: 5min Stable Test Enable: Y Current: 9999A Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value.
Chapter 5 Operating SCU 61 2. The value description of the parameters is listed below: Table 5-13 Parameter Range Default Battery test 43.1V ~ 45.2V voltage 57.9V Battery test time 5 ~ 1440min 300min Test End Cap (capacity) 0.01C10 ~ Scheduled Test Planned Test 1 Planned Test 2 Planned Test 3 Planned Test 4 Alarm Current ShortTest Cycle Y, N Y 00:00, Jan. 1st Month,day, 00:00, April 1st hour 00:00, July 1st 00:00, Oct.
62 Chapter 5 Operating SCU 5.7.6 Temperature Compensation Coefficient Parameters 1. The first page of the setting interface is shown below: Temp 1: Ambient Temp 2: Battery 2. If the “Temperature1” or “Temperature2” is set to “Battery Temp”, you need to set the following parameters: Center Temp: 25°C Temp. Comp: 70mV / °C /Str Batt Temp Alarm Over: 70°C High: 50°C Low: 0°C Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save.
Chapter 5 Operating SCU Parameter Range When Temp 1 or Temp 2 is Over set to “Battery Temp” High Low 5.7.
64 Chapter 5 Operating SCU 5.7.8 DC Setting 1. There are three related pages, as shown below: DC Volt Alarm Over: 58.5V Low: 45.0V Under: 45.0V Amb. Temp Alarm High: 25°C Low: 0°C Load Shunt None Shunt Coeff: None Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save. ” or “ ” to 2. The value description of the parameters is listed below: Table 5-16 Parameter Range Default Over (over-voltage) 58.
Chapter 5 Operating SCU 5.7.9 65 Rect Settings 1. There are three related pages, as shown below: Rect Over Volt: 59.0V Default Volt: 42.0V Walk-in Enabled N Walk-in Time: 8s Fan Speed Full Speed HVSD Time: 300s Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save. ” or “ ” to 2.
66 5.7.10 Chapter 5 Operating SCU System Settings Users of different password levels have different authorities. 1. For the user level password (123456), there are 2 related pages, as shown below: Adress: 1 Text: Chinese CommMode:Modem Baud: 9600 Set Date: 2004-05-01 Set Time: 17:30:30 Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save.
Chapter 5 Operating SCU 67 System Type: 48V/50A/300/NONE Serial No: 2004051025252 There will be a prompt when resetting the system: Notice: All Param Lost! ENT Continue ESC Quit 3. For administrator level password (by default: 640275), you can see the following pages, besides all those above, as shown below: Change Password: Code Con Alarm Voice: 1 Hour Serial: 12345689101112 SW Ver: 1.00 Set Enable: Y You can change the value of “Change Password” and press “ENT” to confirm.
68 Chapter 5 Operating SCU Table 5-18 Parameter Range Value description of system settings Default Value description Text Chinese, English and Spanish Address 1 ~ 254 The addresses of power systems that are at the same monitored office should be different CommMode modem, EEM-M, RS-232 “MODEM”: Through modem and based on the Telecom protocol. “EEM-M”: Through modem and based on the EES protocol.
Chapter 5 Operating SCU Parameter Operator level or above System Type Administrator Range Default 24V/75A/500/NONE 24V/75A/500/MAN 24V/75A/500/AUTO 24V/50A/500/NONE 24V/50A/500/MAN 24V/50A/500/AUTO 48V/50A/500/NONE 48V/50A/500/MAN 48V/50A/500/AUTO 48V/50A/300/NONE 48V/50A/300/MAN 48V/50A/300/AUTO 48V/30A/300/NONE 48V/30A/300/MAN 48V/30A/300/AUTO 48V/30A/100/NONE 48V/30A/100/MAN 48V/30A/100/AUTO 48V/15A/100/NONE 48V/15A/100/MAN 48V/15A/100/AUTO 48V/100A/SET/NON 48V/100A/SET/MAN 48V/100A/SET/AUT 48V/50A
70 Chapter 5 Operating SCU The relationship between the system model and system type is listed in the following table: Table 5-19 Relationship between system model and system type Power system model System type PS48400-3/2900, Single AC Input PS48400-3/2900, Double AC Inputs, Manual Switchover PS48400-3/2900, Double AC Inputs, Auto Switchover PS48600-3/2900, Single AC Input PS48600-3/2900, Double AC Inputs, Manual Switchover PS48600-3/2900, Double AC inputs, Auto Switchover 48V/50A/300/NONE 48V/50A/3
Chapter 5 Operating SCU Use “ ” or “ ” to select one page or one of the parameters, and “ select the parameter value. Press “ENT” to confirm and save. ” or “ 71 ” to 3. After setting the “Set DI Name” and confirming it, the system will prompt you to name the DI: DI Name Digital 1 Use “ ” or “ ” to change the number, and “ right. Press “ENT” to confirm. ” or “ ” to move the cursor left or 4.
72 Chapter 6 Routine Maintenance Chapter 6 6.1 Routine Maintenance Maintenance Of Rectifier The fan of rectifier shall be maintained periodically. The fan shall be replaced if it does not work due to faults. Follow the procedures below to replace the fan: 1. Loosen the 3 screws on the baffle and remove the baffle. 2. Unplug the power cable of the fan and remove the fan. 3. Replace the fan. 4. Plug the fan power cable back into the corresponding socket. 5.
Chapter 6 Routine Maintenance 73 6.4 Cover Plates The Multi-Function Unit has a cover plate to protect the load and battery circuit breakers and to create a neat finish. This cover plate is easy to open/remove in order to switch on or off a circuit breaker, or to connect additional loads. The cover plate can be opened or removed without the need of using special tools. The DC section of the Distribution Unit is made safe for a “User” to access, which follows the “Look and Feel” guidelines. 6.
74 Chapter 6 Routine Maintenance After one year of operation, all the units should be within the range of 13.50±0.48V. 6.5.3 Replacement 1) Replacing Criterion Replace the battery if its capacity measured during the battery test is less than 80% of the battery rated capacity. The capacity measured during the battery test shall be evaluated at a discharge rate close to its actual use. 2) Replacement Interval The battery is expendable, and has a certain life cycle.
Chapter 7 Troubleshooting Chapter 7 75 Troubleshooting 7.1 Troubleshooting Rectifier 1. Troubleshoot Rectifier according to LED Indication The usual fault symptoms of the rectifier include: power indicator (green) off, protection indicator (yellow) on, protection indicator (yellow) blinking, alarm indicator (red) on, and alarm indicator (red) blinking.
76 Chapter 7 Troubleshooting If the current sharing is still unsuccessful after the correction, replace the rectifier of which the current sharing function is disabled. 7.2 Mains Failure Mains failure often occurs in power system operation. Batteries will provide backup DC power in case of short-period of mains failure. If the cause of mains failure remains unknown or the failure lasts too long, the generator should be started to provide mains supply to the system.
Appendix 1 Appendix 1 Parameter AC input alarm and protection DC output alarm and protection 77 System Technical Parameters category Note AC input over-voltage alarm point Default: 280 ! 5Vac, cofigurable through monitoring module AC input over-voltage recovery point Default: 270 ! 5Vac, 10Vac lower than the AC input over-voltage alarm point AC input under-voltage alarm point Default: 180 ! 5Vac, configurable through monitoring module AC input under-voltage recovery point Default: 190 ! 5Vac,
78 Appendix 1 System Technical Parameters Parameter category Others Dielectric strength MTBF Size (mm) Mechanica Weight Note (Remove the SPD, monitoring module and rectifiers from the system before the test.) AC to DC circuits, AC circuit to earth: 50Hz, 3,000Vac (RMS). DC circuit to earth: 50Hz, 1,000Vac (RMS). Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac (RMS).
Appendix 2 Appendix 2 Engineering Design Diagram Engineering Design Diagram Appendix 2.
80 Appendix 2 Engineering Design Diagram Appendix 2.
Appendix 2 Engineering Design Diagram Appendix 2.3 Engineering Design Diagram For 700mm%600mm%400mm Cabinet Appendix 2.
Appendix 3 Appendix 3 System Circuit Diagram Appendix 3.
Appendix 3 Appendix 3.
Appendix 3 Appendix 3.
Appendix 3 Appendix 3.
86 Appendix 4 Glossary Appendix 4 Glossary Abbreviation Amb.