User’s Manual Rev J May 2014 475 Field Communicator User’s Manual
475 FIELD COMMUNICATOR 475 Field Communicator NOTICE Read this User’s Manual before working with the 475 Field Communicator. For personal and system safety, and for optimum product performance, thoroughly understand the contents before using or servicing this product. For equipment service needs, contact the nearest product representative. ©Emerson Process Management. 2014. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co.
475 FIELD COMMUNICATOR TABLE OF CONTENTS SECTION 1 Introduction Using this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 SECTION 2 Learning the basics Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 475 Field Communicator overview . . . . . . . . . . . . . . . . . 10 Device interoperability. . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Adding functionality by enabling licenses . . . . . . . . . . . . ScratchPad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Creating a new document . . . . . . . . . . . . . . . . . . . . . . . . Opening an existing document . . . . . . . . . . . . . . . . . . . . ValveLink Mobile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Running a self test . . . . . . . . . .
Table of Contents 5 Starting the Fieldbus Application . . . . . . . . . . . . . . . . . . Working online with fieldbus devices . . . . . . . . . . . . . . Connecting to a fieldbus device . . . . . . . . . . . . . . . . . . . Displaying the connected fieldbus devices . . . . . . . . . . . Displaying the online device . . . . . . . . . . . . . . . . . . . . . . Block modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Device blocks . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power supply/charger specifications . . . . . . . . . . . . . . . Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage .
475 FIELD COMMUNICATOR SECTION 1 USING THIS MANUAL www.fieldcommunicator.com INTRODUCTION The sections in this manual provide the following information on the 475 Field Communicator. Section 2: Learning the basics contains information on assembly, components, starting, entering standby, shutting down, settings, supported PC applications, and maintaining the 475 Field Communicator.
Introduction
475 FIELD COMMUNICATOR SECTION 2 LEARNING THE BASICS OVERVIEW This section provides instructions on basic features and functions of the 475 Field Communicator. It also provides information on assembly, components, starting, entering standby, shutting down, settings, applications, and maintaining the 475 Field Communicator. The functionality described in this section is based on system software version 3.8.
Learning the basics WARNING You can install or remove the Lithium Ion (Li-Ion) battery (Power Module) in a hazardous area environment.You cannot charge the battery in this environment because the power supply/charger (00375-0003-0005) is not IS-approved. 475 FIELD COMMUNICATOR OVERVIEW The 475 Field Communicator supports HART and FOUNDATION fieldbus devices, letting you configure, maintain, or troubleshoot devices.
Learning the basics Working in a hazardous area 11 A 475 Field Communicator that meets the Intrinsic Safety requirements (I/S-approved) can be used in Zone 0 (FM and CSA only), Zone 1, or Zone 2, for Group IIC, and Class I, Division 1 and Division 2, Groups A, B, C, and D locations.
Learning the basics Checking the remaining charge To view the remaining charge, press the Charge Indicator button on the lower left side of the battery. See Figure 2-1 for the location of this button. When you press and release the button, the lights above the button slowly illuminate to display the charge remaining. Each light represents 20 percent of the charge. The battery is fully charged when all of the lights are illuminated.
Learning the basics 13 To charge the battery: 1.Plug the power supply/charger into a power outlet. 2.Plug the green power supply/charger connector into the green connector on the battery. The flat side of the power supply/charger connector should face the front of the 475 or the inside of the battery, if the battery is not attached to the 475. The battery is fully charged when the light on the power supply/charger is green. Figure 2-2.
Learning the basics Power supply/charger lights Three lights are on the power supply/charger to indicate the conditions below. Each light displays a different color. Table 2-1. Power supply/charger lights Color Condition Green The battery is fully charged. Flashing green The battery is nearly fully charged. Yellow The battery is charging. Flashing yellow The power supply/charger is not connected to the 475 Field Communicator.
Learning the basics 15 Figure 2-3.
Using the touch screen Learning the basics The touch screen and keypad let you select menu items and enter text. Use the provided stylus or the up and down arrow keys on the keypad to select a menu item. On the Settings and Field Communicator Main Menu, tap an icon or press Enter to open the selected icon. On other menus, double-tap the selected item on the screen or press the right arrow key on the keypad to open a menu item.
Learning the basics 17 If the Power key is pressed when there is unsent data or a device method is running, a warning message appears. Tap OK to have the 475 Field Communicator enter standby or shut down, or tap Cancel to return to the previous window. The Power key is disabled when the 475 Field Communicator is in Listen for PC mode or when the ScratchPad application is open. Arrow navigation keys Four arrow navigation keys let you move through the menus and icons in the applications.
Learning the basics Backlight key The Backlight key lets you adjust the intensity of the touch screen display. There are four different settings. The intensity impacts the charge in the battery. Expect a shorter charge life for higher intensities. See “Backlight” on page 24 for information on timers that can turn off the backlight after specified periods of inactivity. These timers can help conserve the battery power.
Learning the basics 19 If the selected device descriptions are already on your 475, they are removed the next time you connect the 475 Field Communicator to the Easy Upgrade Utility. You are prompted before the files are removed. See the Easy Upgrade Utility Help for more information. Accessories Rubber boot A rubber boot can be purchased to further protect your 475 Field Communicator. The boot has an additional stand on the back, cut outs for the straps, and holders for the stylus.
Learning the basics Straps Two straps are available with the 475 Field Communicator. The magnetic strap attaches to the top of the 475 Field Communicator and lets you hang it from a metal pipe. The strap attachment is located near the HART and fieldbus terminals on the top of the 475 Field Communicator. The side strap lets you attach a strap to the sides or back of the 475 Field Communicator, making it easy to carry. See Figure 2-5. The side strap also holds the stylus used with the touch screen.
Learning the basics 21 ASSEMBLY Installing the System Card and the battery If you received a 475 Field Communicator with the System Card already installed, proceed to the " Starting up" section. 1.Place the 475 Field Communicator face down on a level, secure surface. 2.Remove the protective rubber boot, if attached. 3.With the battery removed, slide the System Card (labeled System Card), with the metal card contacts facing up, into the System Card socket until it clicks.
Learning the basics Removing the battery and the System Card To remove the battery and System Card: 1.Remove the rubber boot, if attached. 2.Place the 475 Field Communicator face down on a level, secure surface. 3.Loosen the battery retaining screws until the top of each screw is slightly above the top of the 475 Field Communicator. 4.Slide the battery off the 475 Field Communicator. Do not pull up the battery because this could damage the connector pins. 5.
Learning the basics 23 Figure 2-7. Field Communicator Main Menu Entering standby You can put the 475 Field Communicator into standby to save power or to reduce the boot-up time if you are using the 475 Field Communicator intermittently. Standby turns off the touch screen and areas within the 475 Field Communicator. You can put the 475 Field Communicator in standby when the HART Application or the Fieldbus Application is running.
SETTINGS About Backlight Clock Learning the basics You can view and modify the options below for the 475 Field Communicator from the Settings option on the Field Communicator Main Menu. To return to the Field Communicator Main Menu, tap the Back button on the screen. Tap the MORE button to view additional items on the Settings menu. The About setting lets you view the software revisions in your 475 Field Communicator.
Learning the basics 25 The Contrast setting lets you adjust the lightest and darkest areas on the window. This option applies to only the 375 Field Communicator. Contrast NOTE Temperature can affect contrast. Licenses Power The Licenses setting lets you view the enabled and available licenses for the 475 Field Communicator. A checkmark indicates the license is enabled. Unlicensed features cannot be accessed.
Learning the basics After you select the appropriate power management settings, tap OK to apply the settings for this session only, SET DEFAULT to retain the settings upon startup, or CANCEL to exit without changes. Power Button Retrain Battery The Power Button setting lets you set the default option for the Power Switch dialog. The Power Switch dialog appears when you press the Power key.
Learning the basics Event Capture 27 The Event Capture setting lets you create an Event Capture file (.rec), which is a log of communication, input, and output that occurs between the 475 Field Communicator and a device (HART only). When working with Technical Support personnel, you may be asked to create an Event Capture file to help troubleshoot issues that cannot be easily isolated or resolved.
Learning the basics CONNECTING TO A DEVICE Use the provided lead set and the HART or Fieldbus (if licensed) Applications to connect and communicate with a device. The appropriate device description is also required. If the 475 Field Communicator does not have the HART device description, the device can be displayed in forward compatibility mode. This mode uses a generic device description and does not display all device functionality.
Learning the basics 29 The Easy Upgrade Utility lets you do the following: • Download new system software and device descriptions to upgrade your 475 Field Communicator at your site. • Enable new functionality and applications by purchasing and downloading new application licenses using the Online Licensing feature. • Upload Event Capture and ScratchPad files to your PC. • Upload, download, and print HART device or user configurations (.hcf files).
Learning the basics Table 2-2. Required connection types to transfer files using the Easy Upgrade Utility File to Transfer Required Connection Type Device Descriptions* IrDA, Bluetooth, or a Card Reader Event Capture Files IrDA or Bluetooth HART Device or User Configuration Files IrDA, Bluetooth, or a Card Reader Licenses IrDA or Bluetooth ScratchPad (.
Learning the basics 31 NOTE The 475 Field Communicator does not communicate with HART or fieldbus devices using Bluetooth. To use Bluetooth, you need the following: • 475 Field Communicator with a Bluetooth license. To see if your 475 is licensed for Bluetooth, tap the Settings icon from the Field Communicator Main Menu. Then tap Licenses. A checkmark next to Bluetooth indicates it is licensed. • An approved Bluetooth adapter attached to your PC that uses the Windows Bluetooth software and drivers.
Learning the basics To enable IrDA communication: 1.Tap Listen for PC from the Field Communicator Main Menu. 2.Tap Change Connection Type. 3.Tap IrDA and then tap OK.You can tap Save as Default to always use IrDA as the connection type. A “Waiting for connection” message appears when IrDA is enabled. See AMS Device Manager Books Online or the Easy Upgrade Utility Help for instructions to connect to those applications using IrDA.
Learning the basics Upgrading the 475 Field Communicator 33 The Field Communicator Easy Upgrade Utility on the Resource CD or DVD lets you download new system software and device descriptions to upgrade your 475 Field Communicator at your site. To download new system software and device descriptions, your 475 Field Communicator must be licensed for Easy Upgrade. You can also send your Field Communicator to a Service Center to be upgraded. For more information, contact your sales representative.
Learning the basics Viewing current licenses To view the current licenses and the Easy Upgrade expiration date in your 475 Field Communicator, tap the Settings icon from the Field Communicator Main Menu. Then tap the Licenses icon. The Easy Upgrade Utility can also display all licensing information from the Licensing & Registration window or Upgrade window. A 475 Field Communicator must be connected to view licensing information from the Upgrade window.
Learning the basics Creating a new document 35 From the Main Page in ScratchPad, tap NEW. An empty text window and SIP keyboard appears. See Figure 2-8. You are now ready to enter text into your new document. A new document can also be created within ScratchPad by tapping the New ( ) icon in the toolbar or by selecting File | New from the menu. Figure 2-8. ScratchPad displaying the SIP keyboard Opening an existing document 1.
Learning the basics Pasting text 1.Copy the text to be pasted. 2.Tap a location on the screen. This is where the text will be pasted. 3.Tap Edit | Paste. You can also paste text by copying the text and tapping the Paste ( ) icon in the toolbar. Saving a document 1.In your document, tap File | Save. 2.Type the file name in the dialog box if your document is new. 3.Tap OK. You can also save a document by tapping the Save ( ) icon in the toolbar.
Learning the basics VALVELINK MOBILE 37 ValveLink Mobile lets you configure, calibrate, and troubleshoot Fisher digital valve controllers (DVC) through an easy-to-use, graphical interface.To open ValveLink Mobile, tap the ValveLink Mobile icon from the Field Communicator Main Menu. The Field Communicator must have a 1 GB or larger System Card and a valid Easy Upgrade license to open ValveLink Mobile. Use the leadset to connect to the DVC and run the desired diagnostics or operations.
Learning the basics
475 FIELD COMMUNICATOR SECTION 3 HART FUNCTIONALITY OVERVIEW This section provides instruction on basic HART functionality in the 475 Field Communicator. It is based on the operation of the HART Application version 6.1. SAFETY MESSAGES Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operation. Information that raises potential safety issues is indicated by a warning symbol ( ).
HART functionality BASIC FEATURES AND FUNCTIONS HART Application functionality The HART Application lets you communicate with and configure HART devices that are connected to the 475 Field Communicator. You can also create and edit configurations and run diagnostics. Using a fast key sequence A fast key sequence is a sequence of numerical button presses, corresponding to the menu options that lead you to a given task. See your device documentation for fast key sequence options.
HART functionality 41 WORKING WITH OFFLINE CONFIGURATIONS The Offline menu lets you create offline configurations and view and change configurations stored in the 475 Field Communicator. There are two types of HART configurations: device configurations and user configurations. A device configuration is created from a connected, online HART device. A user configuration is created offline or transferred to a 475 Field Communicator from another program.
HART functionality a.To change the location where the configuration is saved, double-tap Location, select an option, and tap ENTER. b.To specify a name for the configuration, double-tap Name, enter the name, and tap ENTER. c.Tap SAVE. Opening a saved configuration A saved configuration lets you edit, copy, send, delete, or rename it. You can also compare it to other saved configurations. To open a saved configuration: 1.From the HART Application main menu, double-tap Offline. 2.
HART functionality 43 variables marked. Double-tap Unmark all | OK to clear the marks from all variables. To mark and edit variables individually: a.Double-tap Edit individually. b.Scroll through the list of variables and select the variable you want to mark or edit. To change the value for the selected variable, tap EDIT, change the value, and tap ENTER. A “*” symbol appears next to the variable name and the value is highlighted yellow to indicate the change has not been saved.
HART functionality Renaming a saved configuration The Rename option lets you change the name of a saved configuration. To rename a saved configuration: 1.Open a saved configuration. See “Opening a saved configuration” on page 42. 2.Double-tap Rename from the Saved Configuration menu. 3.Double-tap the file you want to rename. 4.Enter the new file name and tap ENTER. 5.Tap SAVE. Comparing two saved configurations Any two configurations can be compared.
HART functionality 45 Field Communicator Easy Upgrade Utility Use the Easy Upgrade Utility to back up, transfer, and print the configurations saved in your 475 Field Communicator. See the Easy Upgrade Utility Help for more information about connecting and transferring configurations. WORKING ONLINE WITH HART DEVICES Connecting to a HART device The 475 Field Communicator can communicate with a device from the control room, on the bench, or any wiring termination point in the loop.
HART functionality Wiring diagrams Figure 3-3 shows how to connect the 475 Field Communicator to a HART loop. Figure 3-3. Connecting to a HART loop HART device RL≥250Ω + - - + + + mA + - + Power supply - - Current meter Figure 3-4 shows how to connect the 475 Field Communicator directly to the terminals of a HART device. Figure 3-4.
HART functionality 47 Figure 3-5. Connecting with a 250 Ohm resistor HART device + Power supply – + – Optional 250-Ohm load resistor To temporarily install the optional 250 ohm load resistor: 1.Insert the load resistor into the lead set jacks. 2.Open the loop to allow connection of the resistor in series in the loop. 3.Close the loop using the lead set connectors. Figure 3-6 shows how to connect the 475 Field Communicator directly to the communication terminals on a wireless device. Figure 3-6.
Displaying the connected HART devices HART functionality After the device is connected, tap from the Field Communicator Main Menu. The HART Application automatically polls for connected devices using the selected polling options. See “Changing the HART polling options” on page 53 for information on modifying these options.
HART functionality The HART icon 49 A beating HART icon appears at the top of the window when the 475 Field Communicator is communicating with a device. See the table below for the icons and their meanings. Table 3-1. HART icons Icon Meaning The 475 Field Communicator is communicating with a live, online HART device. The 475 Field Communicator is communicating with a HART loop with a device in burst mode.
Displaying Device Setup options HART functionality The Device Setup on the HART Online menu accesses every configurable parameter for the connected device. Some devices may not display a Device Setup menu. Check your device documentation for more information. Double-tap Device setup to view the process variables, diagnostics and service, basic setup, detailed setup, and review menus. Process Variables The Process Variables menu lists all process variables and their values.
HART functionality 51 Figure 3-8. Modified parameter example Detailed setup The Detailed setup menu provides access to every editable device parameter and all device functions. The Detailed setup menu varies widely from one HART device to another. Functions in this menu can include tasks such as characterization, configuration, and sensor and output trims.
HART functionality CONFIGURING THE HART APPLICATION Using hot keys Setting up hot key options The Hot key menu is a user-definable menu that can store shortcuts for up to 20 of your most frequently performed tasks. For example, if you change device tags and damping often, you can add options for these functions to the Hot key menu for quick access. The Hot key automatically appears in the toolbar when you are working online. Hot keys created from generic DDs are not saved.
HART functionality 53 Removing a hot key option To remove individual Hot key options: 1.Tap and hold the Hot key ( ). The Hotkey Configuration window appears. 2.Tap the menu option you want to remove. NOTE Some options are predefined and cannot be removed from the Hot key menu. These options vary depending on the device type. 3.Tap DEL. 4.When you are done, tap EXIT to close the Hotkey Configuration window. Removing all hot key options To remove all Hot key options currently defined: 1.
HART functionality To change the polling option: 1.From the HART Application main menu, double-tap Utility. 2.Double-tap Configure HART Application. 3.Double-tap Polling Options. Select one of the following polling options: • Poll By Address - Lets you poll for devices at the specified addresses. Tap Enter and then double-tap Polling Addresses from the Configure HART Application window to select addresses to poll. (This option appears only when Poll By Address is selected.
HART functionality Ignoring status messages 55 The 475 Field Communicator displays status messages from the connected HART device. The Ignore Status option lets you specify the number of device status messages that are not displayed, extending the time between displayed messages. The default is 50 messages and it is reset to this value after you close the HART Application.
Viewing available device descriptions HART functionality The Available Device Descriptions menu lets you view all the device descriptions in the 475 Field Communicator. HART device descriptions enable the 475 Field Communicator to recognize and configure specific HART devices. Use the Field Communicator Easy Upgrade Utility to download or import new device descriptions and then transfer them to your 475 Field Communicator. See the Easy Upgrade Utility Help more information.
HART functionality 57 4.Double-tap the desired model to expand the list. The device revisions available for the selected model are listed. 5.Double-tap the desired device revision. Refer to the device manual to determine the device revision. 6.If a warning appears, thoroughly read the warning, tap CONT to accept the warning and proceed, or tap EXIT to return to the Utility menu. (This warning does not appear if your device is tested.) The Online menu for the simulated device appears.
HART functionality
475 FIELD COMMUNICATOR SECTION 4 FIELDBUS FUNCTIONALITY OVERVIEW This section provides instruction on basic fieldbus functionality in the 475 Field Communicator. It is based on the operation of the Fieldbus Application version 6.1. SAFETY MESSAGES Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operation. Information that raises potential safety issues is indicated by a warning symbol ( ).
Fieldbus functionality BASIC FEATURES AND FUNCTIONS Fieldbus Application functionality The Fieldbus Application lets you communicate with connected fieldbus devices, modify settings for the application, and run diagnostics. Your 475 Field Communicator must be licensed for FOUNDATION Fieldbus to run this application. See your sales representative or the Online Licensing feature in the Field Communicator Easy Upgrade Utility to purchase this license.
Fieldbus functionality STARTING THE FIELDBUS APPLICATION 61 A general warning message may appear upon starting the Fieldbus Application when a LAS is detected on the segment. Tap YES to go to the Live Device List, NO to return to the Field Communicator Main Menu, or HELP to get more information on the warning. To start the Fieldbus Application: 1.Press and hold the Power Key until the green light on that key blinks to turn on the 475 Field Communicator. 2.Tap from the Field Communicator Main Menu.
Connecting to a fieldbus device Fieldbus functionality Connect the 475 Field Communicator by using the lead set with the appropriate connectors in parallel with the device. Due to measurement circuitry, the 475 Field Communicator fieldbus connectors on the communication terminals are polarity sensitive. An error message appears if the lead set is connected incorrectly. For information about Intrinsically Safe connections, see Appendix B.
Fieldbus functionality 63 Bench hook-up Figure 4-3 illustrates one method of connecting the 475 Field Communicator on a bench. For segments that are limited in size, the power conditioner and terminators can be contained in a single wiring block. Figure 4-3.
Fieldbus functionality Field hook-up Figure 4-4 illustrates one method of connecting the 475 Field Communicator to a fieldbus segment. The 475 Field Communicator can be connected at any convenient place along the bus (segment). In the field, this is typically done at the device or at the fieldbus junction box. Figure 4-4.
Fieldbus functionality Displaying the connected fieldbus devices 65 To display the connected devices on a fieldbus segment (Live Device List): 1.Connect the 475 Field Communicator to a fieldbus segment. 2.Turn on the 475 Field Communicator. . 3.On the Field Communicator Main Menu, tap 4.On the Fieldbus Application main menu, double-tap Online. The Fieldbus Live Device List appears and indicates which device or host is acting as the LAS.
Displaying the online device Fieldbus functionality Depending on the device description, the first screen displayed may be the Block List or a Device Dashboard menu. The Block List displays the block tag, block type, and actual mode of the device blocks in the connected device. It also lists an Advanced menu with additional menu options. Consult your device manual or the Fieldbus Foundation for more information on blocks and their functionality. FOUNDATION fieldbus menu trees are on www.
Fieldbus functionality 67 Types of modes For the procedures described in this manual, it is helpful to understand the following modes: AUTO The functions performed by the block will execute. If the block has any outputs, these will continue to update. This is typically the normal operating mode. MAN In this mode, the output of the block can be manually overwritten for testing purposes. Out of Service (OOS) The functions performed by the block will not execute.
Fieldbus functionality Change modes Whenever you need to change the parameters or properties of a block, you need to change the mode. A warning message may appear if the mode of any block is included in a list of parameter changes to be sent to a device. To change the block mode: 1.Tap the MODE button in the Block Menu or at the bottom of a screen. See Figure 4-7. 2.If prompted, select a block from the list and tap OK. 3.Remove the checkmark next to the current mode by tapping the checkbox next to it.
Fieldbus functionality Device blocks 69 The Block Menu is a submenu of the Block List and it displays block information for the fieldbus device to which you are connected. The Block Menu is also available from the Advanced option in a Device Dashboard menu. Devices that do not support transducer block menus within the device description have the following selections: All, Process, Status, Other.
Fieldbus functionality CAUTION Changing device parameters could adversely affect the control of your process. Put the control loop in Manual/Out of Service before applying changes. Verify the output before returning the control loop to Auto. Failure to do so could result in property damage, serious injury, or death. Ensure all safety precautions and work procedures have been followed. To change the values for parameters: 1.Display the parameters for the device. 2.Double-tap the desired parameter. 3.
Fieldbus functionality 71 Displaying device information NOTE The physical device tag and address of a device are read-only when the device is commissioned or, at a minimum, any of the following hosts/linking devices are detected on the segment: Rosemount 3420, DeltaV, Ovation, Allen-Bradley FFLD and FFLDC, Honeywell Experion PKS, Yokogawa Stardom or CENTUM, Softing FG-100/HSE, or SMAR DF62.
Fieldbus functionality 6.Select Yes or No when you are asked if the device is commissioned. You cannot change the physical device tag or address if the device is commissioned. 7.Using the SIP keyboard, enter the new information. When you modify a parameter value, an asterisk (*) appears and the value is highlighted yellow to indicate the change has not been sent to the device. 8.Tap OK. 9.Tap SEND to send the changes to the device. A window appears until the changes are made. 10.Tap YES, if prompted.
Fieldbus functionality 73 7.Tap the appropriate checkboxes next to the I/O blocks. 8.Tap OK. This schedules the blocks and sets the block mode to Auto. 9.After reading the note, tap OK to acknowledge that the I/O blocks were successfully scheduled. Instantiating blocks The Instantiate Block menu lets you add function and transducer blocks to a connected device. This menu item appears only if the fieldbus device contains instantiable block types.
Fieldbus functionality 4.Double-tap Delete Block. 5.Select Yes or No when you are asked if the device is commissioned. You cannot delete blocks if the device is commissioned. 6.Tap the block that you want to delete from the device. 7.Tap OK. 8.When the warning message appears, tap YES to delete the block, or NO to cancel the operation. NOTE Some devices restart after a block is instantiated or deleted, causing a loss in communication between the 475 Field Communicator and the device.
Fieldbus functionality 75 To set a device to be a link master or basic device: 1.Display the Live Device List; see page 65. 2.Double-tap a device. 3.Double-tap Advanced. 4.Double-tap Link Master Configuration. 5.Select Yes or No when you are asked if the device is commissioned. You cannot change the operating class if the device is commissioned. 6.Select the Basic or Link Master option from the drop down box. 7.Tap OK. 8.Tap OK when prompted that the device will restart. The Live Device List appears. 9.
Fieldbus functionality Changing the Slot Time Select the default Slot Time of 8 to allow the devices to be seen on the 475 Field Communicator Live Device List. From the Fieldbus Application Utility main menu, double-tap Utility and then double-tap Link Settings to access the Slot Time menu. It may be necessary to change the Slot Time to 16 to view older devices on the 475 Field Communicator Live Device List.
Fieldbus functionality 77 RUNNING FIELDBUS DIAGNOSTICS The Fieldbus Diagnostics menu lets you run diagnostics to troubleshoot fieldbus networks and devices. You can check the DC voltage, the noise level at low frequencies, and the signal level and communication status. The selected tests are automatically repeated and the test results are updated in the Diagnostics Results window.
Fieldbus functionality This test displays the node address, measurement value, measurement unit, and one of the status indicators listed below. - All signal responses from the device were received by the 475 Field Communicator. ! - One or more signal responses from the device was not received by the 475 Field Communicator. This may be caused by noise on the segment. X - No signal responses from the device were received by the 475 Field Communicator. This may be caused by noise on the segment.
475 FIELD COMMUNICATOR SECTION 5 TROUBLESHOOTING OVERVIEW This section provides basic troubleshooting techniques for the 475 Field Communicator. Below are methods for troubleshooting networks that are experiencing problems communicating between a device and the 475 Field Communicator. Troubleshooting suggestions Answer the questions below and use the tables in this section before calling Technical Support personnel.
Troubleshooting HART loops Verify the HART loop current and voltage on the device. Almost all devices need at least 4 mA and 12V DC to operate properly. If there are multiple devices on a multidrop loop, set the 475 Field Communicator to Poll by Address. See “Changing the HART polling options” on page 53 for more information on polling options. Inspection of the loop wiring can often reveal problems. The shield is normally grounded at one end only, which is usually the control system.
Troubleshooting Table 5-1. Troubleshooting table for the HART protocol Symptom Intermittent communication Possible causes Solution Insufficient loop current Verify there is at least 4 and voltage at the mA and 12V DC at the device terminals. device terminals; see “DC voltage measurement (HART terminals)” on page 57. Noise on the field loop. Noise or signal distortion from the control system, i.e.
Troubleshooting 82 More than one Field Communicator or other Secondary Master may be attached to the control loop. Ensure there is only one Primary Master and one Secondary Master on the control loop. The incorrect polling Change the addresses A HART device appears at the addresses may be used. being polled. See multiple addresses. “Changing the HART polling options” on page 53.
Troubleshooting Table 5-2. Troubleshooting table for the fieldbus protocol Symptom No communication with device. Possible causes Solution The Field Communicator is connected to a segment with DeltaV and the device on the same segment is being commissioned using DeltaV. The Field Communicator is unable to communicate with this device until you go offline and then back online.
Troubleshooting 84 ERROR AND STATUS MESSAGES Table 5-3. Field Communicator error messages General error messages License file check failed - error code x. Please contact service center to resolve this problem. Press OK to turn off. (Where x indicates the test that failed.) Warning: System incompatibility detected - error code x. Start Listen For PC and use the Easy Upgrade Utility to resolve this, turn off your Field Communicator and contact service center to resolve this.
Troubleshooting Table 5-4. HART Application error messages HART error messages Hart Application Error... “registry failure”...Reinstall System Files...See User's Manual for details. Description A registry setting in the 475 is corrupted. From the Field Communicator Main Menu, do the following: 1. Tap Settings. 2. Tap About. 3. Double-tap RE-FLASH. 4. Tap Yes to proceed. Voltage detected on FF connectors. Insert the lead set connectors into Check your connectors and press the HART communication OK.
Troubleshooting 86 Warning: this DD is untested with the current Hart App ver …you may experience unexpected or inappropriate results…See Programming Interface for details on DD updates…Do you want to accept these risks and proceed? DD Error…"tested-to sequence mismatch"…DD version ; HART application ; HART app version x.y…See Programming Utility for solution.
Troubleshooting Forward Compatibility Blocked…The Device Description for x Device Rev x dd Rev x cannot be used in forward compatibility mode…x… Press OK to load the Generic Device Description.
Troubleshooting 88 Table 5-5. Fieldbus Application error messages Fieldbus error messages Connection Error - Voltage Detected on HART connectors. Please check your connectors. Press OK to retry connecting to the segment. Press CANCEL to end the Fieldbus Application. Connection error - Polarity reversed on the fieldbus segment connection. Please reverse connectors. Press OK to recheck polarity. DDP Error 1: Unable to load DD. Press OK to return to Block List.
Troubleshooting Function Block Service Error: Parameter Check The parameter value being entered is invalid for this device. Check with the device supplier. Make sure the value entered is valid for that specific device parameter. Function Block Service Error: The parameter value being Exceeds Parameter Limits entered is outside the range of valid values for the device parameter. Check with the device supplier. Make sure the value entered is in the correct range for that device parameter.
INFORMATION FOR TECHNICAL SUPPORT Troubleshooting Before you call Technical Support personnel, have a detailed description of the issue, including the information below (if applicable). Have the User’s Manual for the device available. • 475 Field Communicator system software revision. • What is the serial number of the 475 Field Communicator having the communication issue? This is located on the label on back of the Field Communicator.
475 FIELD COMMUNICATOR APPENDIX A REFERENCE DATA PROCESSOR AND MEMORY SPECIFICATIONS Microprocessor 80 MHz, max 133 MHz Hitachi® SH3 Memory Internal Flash 32 MB System Card 1 GB Secure Digital card or higher RAM 32 MB PHYSICAL SPECIFICATIONS Weight Approximately 1.65 lb (750 grams) includes battery Display 3.5” diagonal, 1/4 VGA (240 by 320 pixels) color touch screen Hard-coated surface Dimensions approximately 2.81” x 2.11” (71.5 mm x 53.
USAGE SPECIFICATIONS Temperature limits +14°F to +122°F (-10°C to +50°C) 0% to 95%RH (non-condensing) for +32°F to +122°F (0°C to +50°C) Storage with batteries -4°F to 131°F (-20°C to +55°C) for less than 1 month Storage without batteries -4°F to +140°F (-20°C to +60°C) Enclosure rating IP51 (front) Shock Passes the 1-meter drop test onto concrete General guidelines • • • • Only use new, original parts. Do not recharge the battery in hazardous areas.
Card reader Only supported card readers can be used with the System Card. Unsupported card readers may corrupt files. See the readme file on your Resource CD or DVD or www.fieldcommunicator.com for the list of supported card readers. The card reader can be used only with the Field Communicator Easy Upgrade Utility.
POWER SUPPLY/CHARGER SPECIFICATIONS Connection Green six-pin mini din (male) plug Lights The power supply/charger has three colored lights that indicate the conditions below. Each light displays a different color. Voltage Color Condition Green The battery is fully charged. Flashing green The battery is nearly fully charged. Yellow The battery is charging. Flashing yellow The power supply/charger is not connected to the 475 Field Communicator.
ORDER INFORMATION Product Description Field Communicator (Note 1) Communication Protocol Code H HART F HART and FOUNDATION fieldbus (Note 2) Battery Type Code P Rechargeable Li-ion Power Module Power Supply/Charger Code 1 Power Supply/Charger Li-ion/NiMH US/UK/EU connection types included (Note 3) 9 Not Included (Note 4) Language Code E English D German J Japanese R Russian C Chinese F French P Portuguese Product Certifications Code KL ATEX, FM, CSA and IECEx Intrinsically Safe (includes FISCO as applic
(5) The Easy Upgrade feature allows the user to add new System Application software and device descriptions (DDs) to the 475 for a period of 3 years. To upgrade without this feature, the System Card would have to be sent to a Service Center. (6) The Graphics Option enables a user to access enhanced graphical features when using the HART or FOUNDATION fieldbus application.
SPARE PARTS LIST Description Ruggedized 250 Ohm Load Resistor Rechargeable Li-Ion Power Module Power Supply/Charger (Li-Ion/NiMH) US/UK/EU connection types included Power Supply/Charger Standard cord set (US/UK/EU cords) Australian (AU cord) for Power Supply/Charger Lead Set with connectors Hand Strap (pack of 2) Carrying Case (with spare Hand Strap and Stylus) Magnetic Hanger Protective Rubber Boot with stand (Boot available to ship Dec.
(4) These parts support license upgrades of System Cards in the field through the use of the Field Communicator Online Licensing system. The capability is available to end users and may also be performed by an agent on the user’s behalf. It is at the agent’s discretion if an additional fee should apply. Any order must be accompanied by the System Card S/N. Instant notification of when the licenses are available for download are sent to emails provided at time of order.
475 FIELD COMMUNICATOR APPENDIX B PRODUCT CERTIFICATIONS OVERVIEW All 475 Field Communicators come with the main unit label (see Figure B-1). Intrinsically Safe (KL option) 475 Field Communicators also have an additional label opposite the main unit label on the back of the Field Communicator. If the 475 Field Communicator does not contain this label (NA option), then it is considered non-IS approved. The Declaration of Conformity and other approval information are available on www.fieldcommunicator.
TELECOMMUNICATIONS REGULATORY AUTHORITY OMAN - TRA TRA/TA-R/0089/11 D080273 EUROPEAN DIRECTIVE INFORMATION - CE COMPLIANCE R&TTE (1999/5/EC) This equipment is in conformity with the Radio and Telecommunications Terminal Equipment (R&TTE) Directive 1999/5/EC, ETSI EN 300328:2006-10, and IEC 2209-2:2007 standards. Electro Magnetic Compatibility (2004/108/EC) Tested to the EN 61326-1:2006 and ETSI EN 301489-17:2002-08 specification.
Output Parameters U0 I0 = 1.9 Volt DC = 32 μA FOUNDATION fieldbus The FISCO standard applies to the FM, CSA, IECEx, and ATEX certifications. Intrinsically Safe FISCO UiIIC UiIIB U0 = 17.5 Volt DC = 17.5 Volt DC = 1.9 Volt DC IiIIC IiIIB I0 = 215 mA = 380 mA = 32 µA PiIIC PiIIB = 1.9 Watt = 5.3 Watt = 380 mA = 32 µA =0 Pi = 1.3 Watt Intrinsically Safe Non-FISCO Ui U0 Li International Certification = 30 Volt DC = 1.9 Volt DC =0 Ii I0 Ci IECEx Certification No.: IECEx BVS 10.
hazardous locations when connected as indicated in the control drawing 00475-1130. See the control drawing for input and output parameters. Please note the parameters in the control drawing are the same as the FM parameters. POWER SUPPLY/CHARGER CERTIFICATION Declaration of Conformity/Approvals The 475 Field Communicator power supply/charger complies to the requirements of the relevant EU directives. The conformity assessment process has been successfully completed as per the directives listed below.
Figure B-2. Approval Ex Label Example (Only on 475 Field Communicators with the KL option) Label 1-2 ZN:2009 08 51 3 44.0mm -10 C £ Ta £ 50 C Barcode SN 33.0 mm O 2009 08 51 3 O Model 475...KL BVS 09 ATEX E 022 IECEx BVS 10.0094 II 2G (1GD) Ex ia [ia Ga] [ia Da IIIC] IIC T4 Gb CL I, ZONE 0, AEx ia IIC T4 CL I, DIV 1, GP A, B, C, D APPROVED T4 max amb 50°C CSA 213004 Exia Ex ia [ia Ga] [ia Da IIIC] IIC T4 Gb FISCO Field Device / Hand Held Terminal IS when installed per dwg 00475-1130 R = 1.
Figure B-5. Battery Label Examples Label 4-1 ZN:2009 08 54 3 49.0mm 89.0 mm Manufactured Exclusively for Fisher-Rosemount Systems, Inc. (an Emerson Process Management company) By R.
Figure B-6. Waste Electrical and Electronic Equipment (WEEE) label Products with the following label comply with the Waste Electrical and Electronic Equipment (WEEE) directive, 2002/96/EC, which applies to European Union (EU) member states only. The label indicates this product should be recycled and not treated as household waste. Customers in EU member states should contact their local Emerson sales representative for information on discarding any part of the 475 Field Communicator.
This approval drawing can also be found on the www.fieldcommunicator.com website. APPROVAL DRAWINGS THIS DRAWING IS PROPERTY OF AND PROPRIETARY TO EMERSON PROCESS MANAGEMENT. THIS DRAWING AND THE INFORMATION CONTAINED HEREIN SHALL NOT BE REPRODUCED NOR DISCLOSED TO ANYONE EXCEPT THOSE REQUIRING ITS USE FOR CSI AUTHORIZED PURPOSES. THIS DOCUMENT SHALL BE DESTROYED OR RETURNED TO EMERSON WHEN NO LONGER REQUIRED FOR THOSE PURPOSES.
FF Connection Terminals C: \ Docum ent s and S et t i ngs\ bdpard\ Deskt op\ 475\ 475_ControlDrawing-090219_b_ACD_3.jpg 475_ControlDrawing-090219_b_ACD_2.jpg Ci = 0 mH = 0 uF Po = 100 uF = 61 uW = 5600 mH Max. Ambient temp: -10°C less than or equal to Ta less than or equal to +50°C Classification: T4 Leakage current: less than or equal to 50 uA La Ca Io (Isc) = 32 uA Uo (Voc) = 1.9 Vdc Li Pi (Pmax) = 1.
FF Connection Terminals MULTIPLE FF DEVICES ( Number is limited by the requirement to meet all other IS and FISCO requirement for the network. ) C :\Do cu me nts an d Se ttin gs \b dp ard\De sk to p\47 5\47 5_ Co ntro lD ra wi ng -0 90219_b_ACD_3.jpg 90219_b_ACD_2.
FISCO CONCEPT THE FISCO CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS NOT SPECIALLY EXAMINED IN SUCH COMBINATION.
475 FIELD COMMUNICATOR APPENDIX C GRAPHICS INFORMATION OVERVIEW The Graphics functionality enables new, graphical screens by using enhanced Electronic Device Description Language (EDDL) capabilities. You can now view HART or fieldbus device information as images, charts, and graphs. To view the graphical representations, you need a device using an enhanced EDDL device description and a 475 Field Communicator.
BUTTONS Use the following buttons to modify the appearance of the graphs and charts on your window: Pan - Tap this button, select a point in the chart or graph, and drag to move it back and forth in the window. Area zoom - Tap this button, then tap and drag a point in the chart to create an enlarged box. After you release your stylus from the window, the chart enlarges to fit the area. This control is available on strip charts and graphs only.
Charts Charts display a graphic view of variables as they occur over time. There are four major types of charts: • Strip/sweep/scope - Displays variable data with an x-axis of time. A strip chart continually updates the chart, scrolling from right to left. A sweep chart paints the window from left to right, and then paints the window from left to right again, overwriting the oldest data. A vertical line is used to separate the old and new data.
Figure C-3. Strip/sweep/scope chart example Horizontal bar charts A horizontal bar chart formats device data into bars from left to right and varies with time. Use the drop-down list to select the variable you want to highlight. Additional horizontal bars may be present if more than one variable is defined for the option you selected in the drop-down list. The selected variable from the drop-down list appears in color and has a black dot at the end of it.
Vertical bar charts A vertical bar chart formats device data into bars from bottom to top and varies with time. Use the drop-down list to select the variable you want to highlight. Additional vertical bars may be present if more than one variable is defined for the option you selected in the drop-down menu. The selected variable from the drop-down list appears in color and has a black dot above it. The colors displayed are determined by the device description and may vary between devices.
Figure C-6. Gauge chart example Graphs A graph is a snapshot line drawing of device information. Use the drop-down list to select the variable you want to highlight. Additional variables may be present if more than one is defined for the option selected in the drop-down list. The selected variable from the drop-down list appears as a bold, solid colored line while the other variables with the same Y-axis appear as thin colored lines.
475 FIELD COMMUNICATOR GLOSSARY Alphanumeric A character set that contains both letters and digits and, usually, other characters, such as punctuation marks. AMS Suite: Intelligent Device Manager Software for remotely managing Smart devices (offline or online) over existing HART, FOUNDATION fieldbus, or PROFIBUS DP networks. You can use AMS Device Manager to monitor and configure devices, maintain calibration results, run diagnostic routines, and maintain historical data.
Data Link Time Data Link Time is a network-wide time periodically distributed by the LAS to synchronize all device clocks on the bus. Device See HART device or fieldbus device. Device configuration Parameters that define the physical attributes and operating characteristics of a device. It does not include dynamic data. Device configuration management A licensed feature that lets you save up to 1000 HART device or user configurations, depending on file size, to a System Card.
Fieldbus device A device that communicates information using the fieldbus protocol on a digital, serial, multidrop data bus. Fieldbus Foundation The organization that develops and supports FOUNDATION fieldbus, an international, interoperable standard for communication of process automation and control information. Members include suppliers and end users of process control and manufacturing automation products.
Instantiation Some FOUNDATION fieldbus devices support instantiation of function or transducer blocks in the device. This means the device allows a command to be sent to it that will create (instantiate) additional function or transducer blocks in the device. After instantiation, these blocks operate like any other block in the device. The 475 Field Communicator supports the commands to instantiate and to delete function and transducer blocks in a fieldbus device.
Link Master A Link Master device controls when devices access the fieldbus and executes the link schedule, which synchronizes communications with function block execution on the fieldbus. The H1 card or any device that supports Link Master functionality can function as a Link Master device. Only one Link Master device can be active at a time on the fieldbus segment. This device is called the LAS. Link Master Configuration An option to set a device as a basic or link master device.
Resource CD or DVD A CD or DVD included with the purchase of a 475 Field Communicator. It contains electronic copies of product documentation, the install file for the Easy Upgrade Utility, and the latest system software and device descriptions at the time the CD or DVD was created. The Resource CD contains English versions of the documentation, system software, and Easy Upgrade Utility. The Resource DVD contains the documentation and software in English and additional languages.
User data file A text (.TXT) file created by a user either on a PC or with the ScratchPad application on the 475 Field Communicator. User data files can be transferred between the Field Communicator Easy Upgrade Utility and a 475. WirelessHART adapter A HART device that meets the WirelessHART standard and enables a wired HART device to join a Wireless network and communicate with the gateway.
475 FIELD COMMUNICATOR Index Symbols .hcf files 29, 44 .rec files 27, 118 .
user 41, 122 configure Fieldbus Application 75 HART Application 52 connecting 250-ohm resistor 47 fieldbus device 63 fieldbus segment 64 HART device 46 HART loop 45 load resistor 46 D D/A trim 50 damping 50, 52 data link time 118 date/time 24 DDL 118 DeltaV System Polling checkbox 75 detail 71 detailed setup 51 device address 71 blocks 69 configuration 118 ID 71 revision 71 setup 50 status 70 tag 50, 71 test 50 Device Configuration Management 118 Device Dashboard 48, 66 device description add new 33 de
G gauge chart 116 graphics 119 buttons 112 controls 112 enhanced DDs 51, 75 fieldbus devices 75 HART devices 51 license 51 options 112 overview 111 graphs 116 H HART 23 device 119 diagnostics 57 functionality 39 icon 49 long tag 55 loop 45, 46, 80, 119 main menu 40 Offline menu 41 polling options 53 protocol 119 short tag 55 simulation 56 starting application 40 tag 119 terminals 45 Utility menu 52 wiring 46 hazardous locations certifications ATEX 100 CSA 101 FM 101 IECEx 101 HOME 48 horizontal bar cha
menu Block 69 Fieldbus Diagnostics 77 Fieldbus Main 61, 75, 76 Fieldbus Online 61, 75 Fieldbus Utility 61, 75, 76 HART diagnostics 57 HART Offline 41, 42 HART Online 48, 51 HART Utility 53, 54, 55, 56 Hot Key 52 title 55 messages error 84 ignored status 55 safety 9, 39, 59 status 84 methods 70 microprocessor 91 modes 66 actual 68 block 69 burst 49, 117 change 68 MAN 69 out of service 69 parameters 67 shout/deaf 49, 122 target 68 types 67 N navigation keys 17 O Online Fieldbus menu 61, 65 HART menu 48 L
new 35 opening 35 saving text 36 screen. See touch screen 26 segment 122 sensor setup 51 sensor trim 50, 51 Settings About 24 Backlight 24 Clock 24 Contrast 25 Event Capture 27 Licenses 25 Memory 27 Power 25 Power Button 26 Retrain Battery 26 Touch Screen 26 short tag 55 shout/deaf mode 49, 122 shut-down timer.
V V(FUN) 75 V(NUN) 75 ValveLink Mobile 37 vertical bar chart 115 voltage 57, 61 troubleshooting 80 W WEEE 105 weight 91 WirelessHART adapter 54, 123 WirelessHART device 123 wiring fieldbus 63, 64 HART 46 troubleshooting 81 X XPAND button 42
Emerson Process Management Asset Optimization 12001 Technology Drive Eden Prairie, MN 55344 USA T 1(952) 828-3633 F 1(952) 828-3006 www.fieldcommunicator.com ©2014, Emerson Process Management. The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.