Installation Manual
Installation, Operation and Maintenance Manual IO-70104 Rev 2, 6/2014
SPD WIRING & MOUNTING
CIRCUIT BREAKER & WIRE SIZE
Overcurrent Protection: ............... 20A Recommended
Connection Wire
: ........................ Phase/Neutral/Ground;
(24’’ of #12 AWG Included)
Summary Alarm Contacts
............ 250VAC, 5A Max; (
24’’ of #18 AWG Included
)
Designations are with AC Applied
Normally Open ............ (NO) = Yellow
Normally Closed .......... (NC) = Blue
Common .................... (COM) = Orange
DIN RAIL MOUNTING KIT
The optional DIN Rail mounting kit allows the 420 & 425 SPDs to be installed on standard
35mm industrial Din Rail. Individual clips mount to the bottom of the enclosure using 6-32
hardware included.
Part Number: 420-DIN (Sold separately)
Remove cover, and use #6 x 3/4”
self-threading screws (provided)
for mounting,
Replace cover, torque screws to
10 in/lbs.
PARALLEL WIRING DIAGRAM
SCREW MOUNTING
5