Technical Specifications
8/2012-Rev A (LCV)
ENGINEERING SPECIFICATION
FOR MEDIUM VOLTAGE VERTICAL AIRFLOW
OUTDOOR RESISTIVE LOAD BANK
MODEL LCV-10000
PART 1.0 GENERAL
1.1 SCOPE
A. This specification contains the minimum requirements for the design, manufacture and testing of
a direct connect, medium voltage, air-cooled, outdoor resistive load bank.
B. The load bank is required for periodic exercising and testing of the (standby) emergency power
source. The load bank shall be permanently mounted outdoors in a weather resistant 40' ISO
style container. Unit shall be forced air cooled. The control panel will be remotely mounted.
C. This specification shall apply if the load bank is supplied to the purchaser, or as a part of other
equipment.
D. Should the vendor take exception to any part of this specification, it shall be stated in the bid, and
referenced to the specification line number.
1.2 SUBMITTALS
A. The manufacturer shall submit for review technical data including features, performance,
electrical characteristics, physical characteristics, ratings, accessories, and finishes.
B. Shop drawings shall include dimensional plans, front and side elevations and mounting details
sufficient to properly install the load bank. Load bus configuration and load connections
termination area shall be clearly identified.
C. Electrical schematic drawings shall be provided to detail the operation of the load bank and the
provided safety circuits. Over-current protection and control devices shall be identified and their
ratings marked. A system interconnection drawing shall be included for control wiring related to
the load bank.
1.3 STANDARDS
A. The equipment covered by this specification shall be GOST-R standard certified.
B. The load bank shall be manufactured using UL Listed components as available.
PART 2.0 PRODUCTS
2.1 RATINGS
A. The total capacity of the load bank shall be rated 10MW at 6.3 KV, 3-Phase, 3-Wire, 50 Hertz,
916 Amps per Phase at unity 1.0 Power Factor and 500 KW minimum load step resolution.
B. The load bank shall be designed for continuous duty cycle operation with no limitations. The load
bank shall operate in an ambient temperature of -40°C to 49°C (-40°F to 120°F).
C. To avoid any transformation of voltage, load bank shall be designed as a true medium voltage
direct connect unit. The use of a medium voltage step down power transformer and low voltage
load bank shall not be permitted.