Installation Guide

D102684XUS2
Installation Guide
English – September 2012
299H Series
www.sherregulators.com
Introduction
This Installation Guide provides instructions for
installation, startup, and adjustment of 299H Series
regulators. To receive a copy of the Instruction
Manual, contact your local Sales Ofce or view
a copy at www.sherregulators.com. For further
information refer to: 299H Series Instruction
Manual, form 5497, D102684X012.
P.E.D. Categories
This product may be used as a safety accessory
with pressure equipment in the following Pressure
Equipment Directive 97/23/EC categories. It may
also be used outside of the Pressure Equipment
Directive using sound engineering practice (SEP)
per table below.
product size category fluid type
DN 40, 50 / NPS 1-1/2, 2 I 1
Specications
Available Congurations
Type 299H: Pilot-operated pressure reducing
regulator with a pilot integrally mounted to the
actuator casing
Type 299HR: A Type 299H with a token internal
relief valve to relieve minor overpressure caused
by thermal expansion
Type 299HS: Same as the Type 299H
with a Type VSX-2 slam-shut valve which
provides overpressure or overpressure and
underpressure protection
Type 299HSR: Same as the Type 299HS with
an internal token relief valve
Body Size and End Connection Styles
See Table 1
Maximum Operating Inlet Pressure
(1)
by Orice Size
6.4 x 9.5 mm / 1/4 x 3/8 inch – 12.1 bar / 175 psig
9.5 mm / 3/8 inch – 12.1 bar / 175 psig
13 mm / 1/2 inch – 12.1 bar / 175 psig
19 mm / 3/4 inch – 10.3 bar / 150 psig
22 mm / 7/8 inch
(3)
– 8.6 bar / 125 psig
25 mm / 1 inch
(3)
– 6.9 bar / 100 psig
30 mm / 1-3/16 inch
(3)
– 5.5 bar / 80 psig
Maximum Casing and Emergency
Outlet Pressure
(1)
4.5 bar / 66 psig
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4
Outlet (Control) Pressure Ranges
(1)(2)
See Table 2
Minimum Differential Pressure For Full Stroke
0.10 bar / 1.5 psi
Maximum Set Pressure for Type 299HS
(1)
1.1 bar / 16 psig
Maximum Set Pressure for Type VSX-2
Slam-Shut Device
(1)
1.6 bar / 23 psig
Minimum and Maximum Trip Pressure Ranges
(1)
See Table 3
Temperature Capabilities
(1)
-29 to 66°C / -20 to 150°F
Installation
Warning
!
Only qualied personnel should
install or service a regulator.
Regulators should be installed,
operated, and maintained in
accordance with international and
applicable codes and regulations,
and Emerson Process Management
Regulator Technologies Inc. (Regulator
Technologies) instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately
may create a hazardous condition.
Personal injury, equipment damage,
or leakage due to escaping uid
or bursting of pressure-containing
parts may result if this regulator is
overpressured or is installed where
service conditions could exceed the
limits given in the Specications
section, or where conditions exceed
any ratings of the adjacent piping or
piping connections.
1. The pressure/temperature limits in this Installation Guide and any applicable
standard or code limitation should not be exceeded.
2. For optimum performance, a pilot supply regulator may be installed in the pilot
supply tubing between the main valve and pilot.
3. This orice size is not available for Types 299HS and 299HSR.