Data Sheet
Bulletin 71.2:299H
7
Table 2. Outlet Pressure Ranges
Table 1. Body Sizes and End Connection Styles
BODY SIZE,
NPS / DN
BODY MATERIAL AND END CONNECTION STYLES
Cast Iron
(For Types 299H and 299HR only)
Ductile Iron
Steel
(For Types 299H and 299HR only)
1-1/4
1-1/2
NPT
NPT
- - - -
NPT
- - - -
NPT
2 / 50 NPT, CL125 FF Flanged
(1)
NPT, CL125 FF and CL250 RF Flanged,
PN 10/16 Flanged
NPT, CL150 RF Flanged
1. This ange is available with a face-to-face dimension of 7.5 or 10 inches / 191 or 254 mm.
Type 299HS
Refer to Figure 5. The Type VSX-2 slam-shut device
on the Type 299HS regulator is a fast acting slam-shut
valve which provides overpressure or overpressure
and underpressure protection by completely shutting
off the ow of gas to the downstream system. The
slam-shut module’s actions are independent of the
Type 299HS main regulator and of variations to
the inlet pressure. The Type VSX-2 has internal or
external registration. External registration requires a
downstream sensing line.
The slam-shut disk is held in the open position (reset
position) by a small ball holding the disk stem. If the
pressure below the diaphragm increases (or decreases)
reaching the Type VSX-2 setpoint, the diaphragm will
travel upwards (or downwards) operating a lever which
in turn releases the ball.
Once the ball is released, the spring force on the stem
will push the stem and disk to the closed position against
the seat shutting off all gas ow. The pilot supply pressure
is also shut off when the Type VSX-2 is closed. The
manual reset has an internal bypass to equalize the reset
pressure on either side on the slam-shut disk.
In order for the Underpressure Shutoff (UPSO) of
any slam shut to be triggered, the downstream pipe
pressure must drop below the UPSO setpoint. In the
case of a downstream line break, numerous factors
can prevent the downstream pipe pressure from
decreasing below the slam-shut UPSO setpoint. These
factors include the distance of pipe to the break, the
diameter of the pipe, size of the break and the number
of restrictions, such as valves, elbows and bends,
downstream of the regulator and/or slam-shut device.
Due to these factors additional protections should be
installed to stop ow in the event of a line break.
Overpressure Protection
Like most regulators, the Type 299H has outlet pressure
ratings lower than the inlet pressure ratings. Complete
downstream overpressure protection is needed if the
actual inlet pressure exceeds the outlet pressure rating.
Overpressure protection for internal parts is built
into the main and pilot diaphragms by means of a
small spring on each post. The springs will allow
the diaphragm heads to move farther on the posts
avoiding damage to or bending of the valve trim.
Overpressuring any portion of a regulator or
associated equipment may cause leakage, parts
damage or personal injury due to bursting of pressure-
containing parts or explosion of accumulated gas.
Regulator operation within ratings specied in the
Specications section and on the regulator nameplate
does not preclude the possibility of damage from
external sources or from debris in the pipeline. A
regulator should be inspected for damage periodically
and after any overpressure condition. The pilot vent
is provided with a 1/4 NPT tapped connection in the
spring case.
Monitoring Systems
Monitoring regulators serve as overpressure protection
devices to limit system pressure in the event of open
failure of a working regulator feeding the system.
OUTLET (CONTROL)
PRESSURE RANGE
TYPE PILOT CONTROL SPRING
299H
299HR,
299HS and
299HSR
Part Number Color
Free Length Wire Diameter
Inch w.c. mbar Inch mm Inch mm
3.5 to 6
(1)
5 to 9
(1)
7 to 20
(1)
16 to 40
(1)
9 to 15
(1)
12 to 22
(1)
17 to 50
(1)
40 to 99
(1)
X
X
X
X
X
X
X
X
T13707T0012
T13589T0012
1N3112X0012
1B413727222
Black
Yellow
Unpainted
Purple
1.86
2.05
2.18
2.12
47.2
52.1
55.4
53.8
0.055
0.051
0.075
0.092
1.40
1.30
1.90
2.34
1 to 3.25 psig
2.75 to 6 psig
5 to 16 psig
14 to 35 psig
30 to 60 psig
69 mbar to 0.22 bar
0.19 to 0.41 bar
0.34 to 1.1 bar
0.97 to 2.4 bar
2.1 to 4.1 bar
X
X
X
X
X
X
X
X
- - - -
- - - -
T13593T0012
T13671T0012
T13600T0012
19B0432X012
19B0432X022
Light blue
Orange
Red
Zinc
Green
2.12
2.40
2.10
2.15
2.75
53.8
61.0
53.3
54.6
69.8
0.105
0.120
0.142
0.207
0.225
2.67
3.05
3.61
5.26
5.71
1. Use a pilot supply regulator if actual inlet pressure varies more than ±20 psi / ±1.4 bar and the published accuracy is required.