Specifications
22 • Energy Meter 026-1726 Rev 0 22-MAR-2011
13 Energy Meter Standard
MODBUS Default Set-
tings
Setting Value
Modbus
Register
Setup Password 00000 –
Reset Password 00000 –
System Type 40 (3 + N) Wye 130
CT Primary Ratio (if
CTs are not included)
100A 131
CT Secondary Ratio 1V 132
PT Ratio 1:1 (none) 133
System Voltage 600 V LL 134
Max. Theoretical Power
(Analog Output: full
scale (20mA or 5V))
104 kW 135
Display Mode 1 (IEEE) 137
Phase Loss 10% of System Voltage
(60V), 25% Phase to
Phase Imbalance
142, 143
Pulse Energy 1kWh/pulse 144
Demand: number of
sub-intervals per inter-
val
1 (block mode) 149
Demand: sub-interval
length
900 sec (15 min) 150
Modbus Address 001 –
Modbus Baud Rate 19200 baud –
Modbus Parity None –
Log Read Page 0 158
Logging Configuration
Register
0159
Log Register Pointer 1 1 (Real Energy MSR) 169
Log Register Pointer 2 2 (Real Energy LSR) 170
Log Register Pointer 3 29 (Reactive Energy
MSR)
171
Log Register Pointer 4 30 (Reactive Energy
LSR)
172
Log Register Pointer 5 37 (Real Demand) 173
Log Register Pointer 6 38 (Reactive Demand) 174
Log Register Pointer 7 39 (Apparent Demand) 175
Table 13-1 -MODBUS Default Settings
Log Register Pointer 8 155 (Month/Day) 176
Log Register Pointer 9 156 (Year/Hour) 177
Log Register Pointer 10 157 (Minutes/Seconds) 178
Setting Value
Modbus
Register
Table 13-1 -MODBUS Default Settings