Specifications
12 • Energy Meter 026-1726 Rev 0 22-MAR-2011
6.2. Adding an Energy Meter
To enable communications between E2 and the
Energy Meter units, the devices must be added and
addressed in E2.
1. Log in to the E2 with Level 4 access.
2. Press
- Connected I/O Boards
and Controllers.
3. In the Connected I/O screen, under the ECT tab,
Enter the number of devices in the Energy Meter
number field.
4. Press
to return to the Network Setup menu,
then select
- Network Summary.
5. Locate the Energy Meter units you added to the net-
work list (press
and to scroll through the
list). The default name for an Energy Meter incre-
ments up starting with Energy001. The two and
three-letter designator does not apply here.
6. By default, each Energy Meter’s board number in
the network list is indicated by a - (dash). To set
the address and begin communication, press
to Commission. (If you have more than one MOD-
BUS network, specify which network you want the
device to belong to.) A screen will open that will al-
low you set the address:
7. In the list of MODBUS devices, choose the address
number corresponding to the Energy Meter’s dip
switch/jumper setting, and press
to select it.
If a network ID has already been selected, its name
will be shown next to the network ID in this list. If
the network ID you are trying to assign has already
been used, you must set the network ID dip switch/
jumper on this device to a different number that is
Figure 6-3 - Connected I/O Screen
Figure 6-4 - Network Summary Screen
Figure 6-5 - Set the Address of the Energy Meter