Specifications
5
CONFIGURATION
Comfort-Set II
Single Stage Models: Verify jumper wire W-22 on
the back of the thermostat (not the subbase) has
been clipped.
Multi-Stage and Heat Pump Models: Verify jumper
wire W-18 on the back of the thermostat (not the
subbase) has been clipped.
Comfort-Set III/Comfort-Set
90/90 Series
Single Stage Models(excluding touchscreen): Veri-
fy jumper wire W-922 on the back of the thermostat
(not the subbase) has been clipped. You must also
enable the remote sensor option in the Installation
Instructions, Conguration Menu.
Multi-Stage/Heat Pump and Touchscreen Models:
When installing a remote sensor you must enable the
remote sensor option in the Installation Instructions,
Installer Menu.
REMOTE SENSOR CALCULATED PRIORITY AVERAGE
Consult Maximum Sensing Locations Per Thermostat chart on page 6 to determine how many sensors a
thermostat will accept.
Tables 1-3 show how priority (LO, AVG, HI) eects the room temperature calculation. The example below
table three shows the calculation of each remote sensor and how it uses them to arrive at room tempera-
ture average.
The example below lists three sensors each with a dierent priority and room temperature. All three sensors
are combined in the calculation to display the average temperature. The priority multiplier shown in the
tables above causes a sensor with low priority to carry less weight in the calculated average. A sensor with
a HI priority setting contributes more to the calculated average. Assume that the building in which the
thermostat is located has three indoor remote sensors (SA, SB, SC) that have dierent room temperatures
(70, 75, 80). The calculated average will be displayed as the room temperature shown in the example below.
Table 1: Remote Sensor A congured as a LO priority sensor
Remote
Sensor
Sensor
Priority
Priority
Multiplier
Room Temperature Averaging Calculation
SA LO
1 70°F (Sensor Temp.) 1 x 70 = 70 (Priority Multiplier x Room Temp.)
Table 2: Remote Sensor A congured as a LO priority sensor
Remote
Sensor
Sensor
Priority
Priority
Multiplier
Room Tempera-
ture
Averaging Calculation
SB AVERAGE
2 75°F (Sensor Temp.) 2 x 75 = 150 (Priority Multiplier x Room Temp.)
Table 3: Remote Sensor A congured as a LO priority sensor
Remote
Sensor
Sensor
Priority
Priority
Multiplier
Room Temperature Averaging Calculation
Sc HI
4 80°F (Sensor Temp.) 4 x 80 = 320 (Priority Multiplier x Room Temp.)
Example: Remote Sensors A, B, and C congured as a LO, AVG, and HI priority sensors
Remote
Sensor
Sensor
Priority
Priority
Multiplier
Room Temperature Averaging Calculation
SA LO
1 70°F (Sensor Temp.) 1 x 70 = 70 (Priority Multiplier x Room Temp.)
SB AVERAGE
2 75°F (Sensor Temp.) 2 x 75 = 150 (Priority Multiplier x Room Temp.)
SC HI
4 80°F (Sensor Temp.) 4 x 80 = 320 (Priority Multiplier x Room Temp.)
Avg. Calc. (540)/Sum Priority Mult. (7)
540/7 = 77°F (Calculated Displayed Temp.)








