Technical Specifications

ASCO Power Technologies, Florham Park, New Jersey 07932 800-937-ASCO www.ascopower.com
01-2009
1 Publication 3208
SUGGESTED SPECIFICATION
for
Series 185 Service Entrance Rated Automatic Transfer Switches
Optional Standby Power Generator Systems
PART 1 GENERAL
1.01 Scope
A. Furnish and install automatic transfer switches (ATS) with number of poles,
amperage, voltage, and withstand and close-on current ratings as shown on the
plans. Each automatic transfer shall consist of an inherently double throw power
transfer switch unit and a microprocessor controller, interconnected to provide
complete automatic operation. All transfer switches and controllers shall be the
product of the same manufacturer.
B. Furnish an enclosure for the ATS that is for service entry. It shall provide all of the
proper disconnecting, protection, grounding and bonding required for service
entrance equipment.
1.02 Acceptable Manufacturers
Service Entrance Automatic transfer switches shall be ASCO Series 185SE. Any
alternate shall be submitted in writing at least 10 days prior to bid. Each alternate bid
must list any deviations from the specification.
1.03 Codes and Standards
The automatic transfer switches and controls shall conform to the requirements of:
A. UL 1008 - Standard for Automatic Transfer Switches
B. CSA – Listed to CSA 22.2
C. NFPA 70 - National Electrical Code
D. International Standards Organization ISO 9001: 2000
E. UL 508 Industrial Control Equipment
F. IEC 947-6-1 Automatic Transfer Switches
G. NEMA Standard ICS 10 Standard for Automatic Transfer Switches