Technical data

AXP 1410 Installation and Use (6806800H70D)
Safety Notes
196
System Damage or Injury
Covers and Panels
Failure to operate the system without covering vacant slots will void the manufacturer’s
warranty.
Do not operate the system with open module slots. For optimal cooling of the system and
associated payload and to prevent electric shock, cover all open module slots and put all panels
in place before turning on power. Slot covers and panels must remain in place during system
operation.
System Damage
Air Filter
Air contamination can pollute the air filter and obstruct the air intake of the system which may
cause system overheating and blade or system component damage.
Air filters should be cleaned at least every 90 days or sooner, depending on the conditions of
the central office environment. Because central offices vary in physical location and
cleanliness, check your air filters every week after you first install your system. In a dusty
environment, a filter may need cleaning more often than a filter in a cleaner environment.
Check the filters frequently until you have a good idea of how often it needs cleaning. Based on
your findings, establish a regular cleaning schedule and keep a log to record the date of each
filter cleaning or replacement.
System Damage
High humidity and condensation on surfaces cause short circuits.
Do not operate the system outside the specified environmental limits. Make sure the system is
completely dry and there is no moisture on any surface before applying power.
Personal Injury
High leakage current can be hazardous and cause injury.
Locate the caution label near the grounding studs (may vary from system to system) and make
an earth ground connection before connecting the PEM.