Data Sheet

Bulletin 71.1:133
8
Table 4. Full-Capacity Type 133L Regulated Flow in Thousands of SCFH of 0.6 Specic Gravity Gas at 14.7 psia and 60°F
Table 5. Full-Capacity Type 133H Regulated Flow in Thousands of SCFH of 0.6 Specic Gravity Gas at 14.7 psia and 60°F
INLET
PRESSURE
OUTLET PRESSURE SETTING
(1)
, SPRING PART NUMBER, AND OUTLET PRESSURE RANGE
3 psig / 0.21 bar
1H975927032
1.5 to 3 psig /
0.10 to 0.21 bar
2 psig / 0.14 bar
10A9440X012
2 to 5 psig /
0.14 to 0.34 bar
5 psig / 0.34 bar
10A9440X012
2 to 5 psig /
0.14 to 0.34 bar
5 psig / 0.34 bar
1J146927142
5 to 10 psig /
0.34 to 0.69 bar
10 psig / 0.69 bar
1J146927142
5 to 10 psig /
0.34 to 0.69 bar
psig bar
10%
Droop
20%
Droop
10%
Droop
20%
Droop
10%
Droop
20%
Droop
10%
Droop
20%
Droop
10%
Droop
20%
Droop
SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h
3
5
7
0.21
0.34
0.48
- - - -
14
21.5
- - - -
0.38
0.58
- - - -
22
31
- - - -
0.59
0.83
6.5
11
13
0.17
0.30
0.35
11.5
18
22
0.31
0.48
0.59
- - - -
- - - -
15.5
- - - -
- - - -
0.42
- - - -
- - - -
24
- - - -
- - - -
0.64
- - - -
- - - -
9
- - - -
- - - -
0.24
- - - -
- - - -
15
- - - -
- - - -
0.40
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
10
15
20
0.69
1.0
1.4
28
40
52
0.75
1.07
1.39
42
57
72
1.13
1.53
1.93
15
25.5
35
0.40
0.68
0.94
27
39
52
0.72
1.04
1.39
24
35
46
0.64
0.94
1.23
35
51
67
0.94
1.37
1.80
14
19
24
0.38
0.51
0.64
22
31.5
41
0.59
0.84
1.10
- - - -
21
31
- - - -
0.56
0.83
- - - -
35
51
- - - -
0.94
1.37
30
40
50
60
2.1
2.8
3.4
4.1
76
98
118
136
2.04
2.63
3.16
3.64
96
119
141
165
2.57
3.19
3.78
4.42
49
66
84
104
1.31
1.77
2.25
2.79
73
97
112
132
1.96
2.60
3.00
3.54
68
88
103
122
1.82
2.36
2.76
3.27
95
117
138
156
2.55
3.14
3.70
4.18
35
44
57
65
0.94
1.18
1.53
1.74
58
73
89
106
1.55
1.96
2.38
2.84
44
56
74
91
1.18
1.50
1.98
2.44
74
97
117
136
1.98
2.60
3.14
3.64
1. Outlet pressure setting was made at approximately 10% of the maximum capacity for the listed conditions.
INLET
PRESSURE
OUTLET PRESSURE SETTING
(1)
, SPRING PART NUMBER, AND OUTLET PRESSURE RANGE
4 inches w.c. /
10 mbar
1D892527022
2 to
4 inches w.c. /
5 to
10 mbar
6 inches w.c. /
15 mbar
1D892627022
3.5 to
6 inches w.c. /
8.7 to
15 mbar
7 inches w.c. /
17 mbar
1D892727012
5 to
9 inches w.c. /
12 to 22 mbar
14 inches w.c. /
35 mbar
1D893227032
8.5 to
18 inches w.c. /
21 to 45 mbar
14 inches w.c. /
35 mbar
1D893327032
14 to 28 inches w.c. /
35 to 70 mbar
1 psig / 0.07 bar
1D893327032
14 to 28 inches w.c. /
35 to 70 mbar
2 psig / 0.14 bar
1H975827032
0.75 to 2 psig /
0.05 to 0.14 bar
psig bar
1 inch w.c. /
3 mbar
Droop
1 inch w.c. /
3 mbar
Droop
1 inch w.c. /
3 mbar
Droop
1 inch w.c. /
3 mbar
Droop
2 inch w.c /
5 mbar
Droop
1 inch w.c. /
3 mbar
Droop
2 inch w.c. /
5 mbar
Droop
10%
Droop
20%
Droop
10%
Droop
20%
Droop
SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h SCFH Nm
3
/h
1
2
3
0.07
0.14
0.21
14
20.8
26
0.38
0.56
0.70
13
20
24.5
0.35
0.54
0.66
12
17
21
0.32
0.46
0.56
5
8.2
12
0.13
0.22
0.32
8.4
15.2
19.5
0.22
0.41
0.52
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
11.5
15.5
- - - -
0.31
0.42
- - - -
16
21.5
- - - -
0.43
0.58
- - - -
- - - -
12.5
- - - -
- - - -
0.34
- - - -
- - - -
18.5
- - - -
- - - -
0.50
5
10
20
0.34
0.69
1.4
35
52
78
0.94
1.39
2.09
33
52
77
0.88
1.39
2.06
32
48
79
0.86
1.29
2.12
16
34
69
0.43
0.91
1.85
28
45
76
0.75
1.21
2.04
14
26
60
0.38
0.70
1.61
23
38
69
0.62
1.02
1.85
24
37.5
70
0.64
1.00
1.88
31.5
44
77
0.84
1.18
2.06
20.5
38
62
0.55
1.02
1.66
28
46
76
0.75
1.23
2.04
30
40
50
60
2.1
2.8
3.4
4.1
101
124
146
170
2.71
3.32
3.91
4.56
100
122
144
168
2.68
3.27
3.86
4.50
100
124
145
166
2.68
3.32
3.89
4.45
91
109
130
155
2.44
2.92
3.48
4.15
97
116
136
161
2.60
3.11
3.64
4.32
87
107
132
152
2.33
2.87
3.54
4.07
93
115
137
158
2.49
3.08
3.67
4.23
90
110
127
149
2.41
2.95
3.40
3.99
101
122
145
167
2.71
3.27
3.89
4.48
87
105
124
145
2.33
2.81
3.32
3.89
101
121
145
170
2.71
3.24
3.89
4.56
1. Outlet pressure setting was made at approximately 10% of the maximum capacity for the listed conditions.