Data Sheet
Bulletin 71.1:133
6
from external sources or from debris in the gas line.
The regulator should be inspected for damage after
any overpressure condition. Complete instructions for
installation, operation, and maintenance are provided
with each regulator.
Capacity Data
Flow capacities for various inlet pressures and
outlet pressure settings are shown in Tables 3 to 10.
Capacities are in thousands of SCFH at 60°F and
14.7 psia and in thousands of Nm
3
/h at 0°C and
1.01325barof0.6specicgravitygas.Toconvert
to equivalent capacities of other gases, multiply the
SCFH values shown by the appropriate factor: air–
0.775; propane–0.628; butane–0.548; nitrogen–0.789.
Forgasesofotherspecicgravities,multiplythegiven
capacity by 0.775, and divide by the square root of
theappropriatespecicgravity.Then,ifcapacityis
desired in Nm³/h at 0°C and 1.01325 bar, multiply
SCFH by 0.0268.
Note
For optimum performance, select the
lowest spring range that includes the
desired outlet pressure setting.
Table 1. 133 Series Outlet Pressure Ranges, Control Springs
Table 2. Maximum Inlet and Outlet Pressures
PRESSURES
TYPE NUMBER
133H 133HP 133L 133Z
psig bar psig bar psig bar psig bar
Maximum Operating Inlet Pressure 60 4.1
150 10.3
60 4.1 20 1.4
Maximum Emergency Inlet Pressure 125 8.6 125 8.6 125 8.6
Maximum Operating Outlet Pressure
(1)
10 0.69
Setpoint
plus 40
Setpoint
plus 2.8
2 0.14 4 inches w.c. 10 mbar
Maximum Outlet Pressure Over
Outlet Pressure Setting
3 0.21 3 0.21 3 0.21
Maximum Emergency Outlet
(Casing) Pressure
15 1.0 150 10.3 15 1.0 15 1.0
1. With highest spring range available only.
TYPE
OUTLET PRESSURE RANGE CONTROL SPRINGS
psig bar Part Number Color Code
Free Length Wire Diameter
Inch mm Inch mm
133H
(1)
1.5 to 3
2 to 5
5 to 10
0.10 to 0.21
0.14 to 0.34
0.34 to 0.69
1H975927032
10A9440X012
1J146927142
Orange
Yellow
Blue
6.91
6.47
6.19
176
164
157
0.250
0.283
0.375
6.35
7.19
9.53
133HP
(1)
2 to 5
4.5 to 10
6 to 20
16 to 30
26 to 40
36 to 50
45 to 60
0.14 to 0.34
0.31 to 0.69
0.41 to 1.4
1.1 to 2.1
1.8 to 2.8
2.5 to 3.4
3.1 to 4.1
17B8632X012
17B8633X012
10C1238X012
10C1240X012
10C1241X012
10C1242X012
10C1243X012
Yellow
Orange
Silver
Red
Blue
Green
White
8.5
8.5
8.25
8.25
8.25
8.25
8.25
216
216
210
210
210
210
210
0.282
0.343
0.375
0.438
0.500
0.500
0.531
7.16
8.71
9.52
11.1
12.7
12.7
13.5
133L
(1)
and 133H
(2)
2 to 4 inches w.c.
3.5 to 6 inches w.c.
5 to 9 inches w.c.
8.5 to 18 inches w.c.
14 to 28 inches w.c.
0.75 to 2
5 to 10 mbar
9 to 15 mbar
12 to 22 mbar
21 to 45 mbar
35 to 70 mbar
0.05 to 0.14
1D892527022
1D892627022
1D892727012
1D893227032
1D893327032
1H975827032
Brown
Red
Black
White
Green
Blue
6.13
7.53
7.88
7.5
7.25
7.09
156
191
200
191
184
180
0.109
0.112
0.130
0.156
0.182
0.225
2.77
2.84
3.30
3.96
4.62
5.72
133Z
(1)
-1 to 1 inch w.c. -3 to 3 mbar
1K633427012
(Extension Spring)
Unpainted 2 50.8 0.075 1.91
0 to 4 inches w.c. 0 to 10 mbar
1K633427012
(Extension Spring)
and
1D892527022
(Compression Spring)
Unpainted
Brown
2
6.13
50.8
156
0.075
0.109
1.91
2.77
1. Pressure ranges shown are correct if the regulator is installed with the actuator portion above the body portion. If the regulator is installed with the actuator portion below the body, the
pressure ranges will be lowered by approximately 2 inches w.c. / 5 mbar for the Type 133L and by approximately 3 inches w.c. / 7 mbar for the Types 133H and 133Z.
2. If the 2 inches w.c. / 5 mbar to 2 psig / 0.14 bar springs (all 6 ranges) are used in the Type 133H, the pressure ranges will increase by approximately 1 inch w.c. / 2 mbar due to
the weight of the Type 133H parts (assuming that the actuator is installed above the body).