Brochures and Data Sheets

EmersonNetworkPower.com/loadbank
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co.
or one of its afliated companies. All the other marks are the property of their respective owners.
Emerson Network Power
Avtron 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A.
216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com
Avtron K841B
Reactive Permanent Load Bank - 103 to 1875 KVAR
Specications subject to change without notice.
©2015 Emerson Network Power Bulletin 404• Rev. F
Specications subject to change without notice.
ROOF EXHAUST VENTILATOR
66.00 [1676.00]
“A” (see chart)
63.50
[1612.00]
80.00
[2032.00]
Load Bank Weight (approx.)
KVAR
“A”
inches [mm]
Weight
approx.
lbs. [kg.]
375-750
(single voltage)
89.00
[2260.00]
7,500 [3401]
375-750
(dual voltage)
116.00
[2946.00]
8,500 [3855]
900-1125
116.00
[2946.00]
9,000 [4082]
1500-1875
144.00
[3657.00]
10,000 [4535]
Load Bank Capacity Ratings
Capacity
Available
103 to 1875 KVAR
AC Voltages
480 or 240/480 Volt AC,
3 phase, 60 Hz
Frequency
50/60 Hz (Reduced Voltage
and Capacity at 50 Hz)
Load Step
Resolution
0-3.75, 3.75, 37.5, or 375 KVAR
NOTE Designs for international 50/60 Hz voltages or custom
DC designs are also available. Consult factory.
Construction
Heavy gauge steel enclosure provides a rigid
structure with removable aluminized steel
panels for interior access. The base of the
unit features forklift channels for simplified
handling.
Cooling
The K841B contains a cooling fan to aid the
convection cooled reactors. The cooling fan
requires a power source of 120 volts, single
phase, 60 Hz.
Controls
The K841B control circuit requires 120 volts,
single phase, 60 Hz power. The standard 19"
rack-mount control panel includes a POWER
ON-OFF switch, BLOWER ON-OFF switch, a
POWER ON light, a MASTER LOAD ON-OFF
switch, a VOLTAGE SELECTOR switch (if ap-
plicable), and individual load step toggle
switches.
Reactors
Single and 3 phase iron core reactors are
designed for 130°C rise in a 50°C environment
with a maximum of 5% waveform distortion
and 0.05 p.f.
Protection
Each load step is fused using UL class T fuses
with 200,000 AIC rating. Each 3 phase re-
actor contains a normally closed thermal
switch in each coil. The load bank enclosure is
equipped with thermal switches. All thermal
switches are interconnected with the load
application control circuit.
Options
480 or 240/480 to 120 Volt Control
Transformer
Under Frequency Protection
Over Voltage Protection
Remote Control Panel Enclosure (NEMA 12)
Control Panel Mounted on Load Bank
All dimensions are in inches [millimeters].