Quick-start Manual IP2042/QS, Rev. AA January 2006 MSP-ULOG1/MSP-ULOG2 Quick-start: For MSP-ULOG1/MSP-ULOG2 www.mobrey.
Introduction What is this Quick-start? This Quick-Start is for anyone who has to install and commission the MSP-ULOG1 or MSP-ULOG2 ultrasonic system, and does not need in-depth information. For full installation instructions, you must refer to the installation (IM) manuals supplied with the equipment. What are these MSP-ULOG1 and MSP-ULOG2 systems? They are level, contents, or flow measurement and control systems.
Installation IMPORTANT - For hazardous area installations, you must refer to the installation (IM) manuals supplied with the system. Location of MSP900SH • Install the transmitter above the liquid surface using the bracket provided. Important instructions for an open channel flow installation are given in IP2040/IM. • Do not mount the MSP900SH on a structure that is subject to vibration, or in a position where impact or thermal stress may cause damage.
Getting started After completing the installation of both MCULOG control unit and the MSP900SH transmitter, the next stage is to switch on. 1. Familiarise yourself with the front panel fascia. Key to figure: c 4-line LCD with backlight. d Keypad with 6 function keys. e Status LED – flashes once per second if okay. Note: The model type is shown on the LCD display in the bottom, right-hand corner. Front Panel Fascia of MCULOGW 2. Switch on the MCULOG by applying the power.
4. Press the yellow (ENTER) key to display the top-level of the menu system. The primary display re-appears automatically if there is no keypad activity for several minutes, if on-line. In addition, it re-appears when pressing the ESC key whilst at the top level of the menu system. How to display the menu system 5. Navigation of the menu system is achieved by using the ARROW keys, the ENTER key, and the ESC key. (See figure, right). The ESC key will return you to the previous menu level. 6.
Application/Duty: Flow Measurement 1. With power on and the MSP900SH transmitter giving a 4-20mA signal to the MCULOG unit (see previous pages), you can now programme the MCULOG for an application. This application example is for flow measurements. Requirement Live flow measurements in units of cubic metres per second. Totalised flow in cubic metres per second.
Application Example: Flow Measurements using Duty Wizard January 2006 7 (IP2042/QS)
Application/Duty: Logging Overview The MCULOG will log up to 4,800 events, where an event is the value of the Primary Variable (PV) at regular intervals; the logging interval is user-defined (P590). An interval value of 15 minutes will log the PV at 15-minute intervals, which equates to 50 days elapsed time. If the MCULOG has been set-up to totalise the PV (see pages 6/7), the daily value of the totaliser at midnight is also logged. Up to 60 midnight totalised values will be held in memory.
Navigating to the LOGGING Menu Menu Map for LOGGING screens January 2006 9 (IP2042/QS)
Other Features Restoring factory defaults (Erases all user-entered data) To re-set the MCULOG unit back to the factory defaults, navigate to the “Load Defaults” screen and press the ENTER key twice. Navigating to the LOAD DEFAULTS Screen PIN Security Personal Identification Number (PIN) security prevents unauthorised people from programming the MCULOG control unit. Typically, this is set-up when all the other programming has been completed. As with Bankcards, there is one PIN number.
Relays Relay outputs 1 to 4 are normally On Point/Off Point relays which may be used to start/stop pumps. They normally energise at one level and de-energise at a different level. Alternatively, they may be programmed as out-of-limits alarms such that they are energised between defined points and will deenergise outside the defined limits. They may also be programmed to perform a variety of auto-sequences and auxiliary functions, such as logging a memory nearly full alarm.
Quick-start Manual MSP-ULOG1/MSP-ULOG2 IP2042/QS, Rev. AA January 2006 The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount is a registered trademark of Rosemount Inc. Mobrey is a registered trademark of Mobrey Ltd. All other marks are the property of their respective owners. We reserve the right to modify or improve the designs or specifications of product and services at any time without notice.