- Emerson Electric Co. Computer Monitor User Manual

Page 31
MSL600
Installation, Operation & Maintenance Manual
IP262/Z0, Rev. AB
February 2012
7.5.3 Alarm Action - P402
This parameter is used to select the desired action which is taken by the mA output when the system is in an
alarm condition.
The allowed options are:
x Go to 3.6mA
x Go to 21mA
x Hold (last reading)
The default action is to go to 3.6mA.
7.5.4 0/4-20mA - P403
This parameter is used to select the desired range of the mA output from a list.
The allowed options are:
x 0-20mA
x 4-20mA
The default is 4-20mA.