- Emerson Remote Terminal Unit Instruction Manual

3-4 / Service CI-ControlWave Express
Figure 3-1 - CPU/System Controller LED Board – Status LED Hexadecimal Codes
(See Table 3-1 for Definitions)
Table 3-1 - System Status Codes on LCD Display
& LEDs on CPU/System Controller Board’s LED Display Board.
LED
6
STA6
LED
5
STA5
LED
4
STA4
LED
3
STA3
LED
2
STA2
LED
1
STA1
Status
In Hex
LCD
Disp.
Indication
Definition
0 0 0 0 0 0 00 Blank Application Running
0 0 0 0 0 1 01 DIAG Unit in Diagnostic Mode
0 0 0 0 1 1 03 R DIAG Unit Running Diagnostics
0 0 0 1 0 0 04 FWXSU
M
Flash XSUM Error
0 0 0 1 0 1 05 DEVERR Error Initializing Application Device
0 0 0 1 1 1 07 FLASH Flash Programming Error
0 0 1 0 0 0 08 FACT Using Factory Defaults *
0 0 1 0 0 1 09 BATT Battery Failure Detected *
0 0 1 0 1 0 0A STRTUP Currently Loading the Boot Project
0 0 1 0 1 1 0B INIT System Initialization in Progress
0 1 0 0 0 0 10 RECOV Waiting in Recovery Mode
0 1 0 0 1 0 12 RAMERR Error Testing SRAM
1 0 0 0 0 0 20 STOP Application Loaded
1 0 1 0 0 0 28 HALT Stopped at a Break Point
Click here to return to Table of Contents