- Emerson Remote Terminal Unit Instruction Manual
CI-ControlWave Express Installation & Operation / 2-29
Step 3 - Flash Data Setup
Complete the following fields in the Flash Data Setup Wizard:
"Please enter the name of the binary file to Flash"
To upgrade system firmware, you must specify the path and name of a binary (*.BIN)
file on your hard disk containing the firmware.
Click on [Finish] to install the specified BIN file in FLASH memory at the RTU.
Once the Flash download has begun, you will NOT be allowed to shut down LocalView,
unless you cancel the download, or it has been completed.
The progress of the Flash download will be displayed in the window. Any mismatch in file
versions, or if the type of .BIN file does not match the type of RTU, the download will be
aborted.
Figure 2-18 - Communication Setup: Step 1 Menu
Once the download has completed, set SW1-3 to the OFF position and then turn power OFF
and then ON again.