- Emerson Remote Terminal Unit Instruction Manual

CI-ControlWave Express Installation & Operation / 2-25
2.3.7.2 Power Wiring
One Bulk DC supply can be connected to the ControlWave Express CPU/System Controller
Board. The Bulk DC supply (nominally +6Vdc, +12Vdc or +24Vdc) connected to TB1-3
(Power In +) and TB1-4 (GND -) is converted, regulated and filtered by the CPU/System
Controller Board to produce +3.3Vdc. This CPU/System Controller Bd. circuit is fused at
3.5A (F3). Depending on the version of the CPU/System Controller Board, the unit’s input
power operating range will vary as follows:
Nominal +6Vdc input source operating range: (+5.4Vdc to +16.0Vdc)
Nominal +12Vdc input source operating range: (+11.4Vdc to +16.0Vdc)
Nominal +24Vdc input source operating range: (+21.8Vdc to +28.0Vdc)
An alternate power connection is available at connector TB2, intended for use if power is
not available through TB1. Bulk DC power would be connected to TB2-1 (Power Input) and
TB2-2 (GND).
Figure 2-16 - CPU/System Controller Board (TB1 & TB2) Power Wiring
Note: Solar Power In+ and Aux. Power Out+ not available on CPUs with Ethernet
2.3.7.3 ControlWave Express System Grounding
ControlWave Express Enclosures are not provided with a Ground Lug. Instead, the user
utilizes one or more mounting screws to secure a ground cable to the unit. A ground wire
(#4 AWG Max. wire size) must be run between the enclosure via one or more mounting
screws (see Figure 2-1) and a known good Earth Ground. The following considerations are
provided for the installation of ControlWave Express system grounds (see S1400CW):
Earth Ground wire size should be #4 AWG. It is recommended that stranded copper wire
is used and that the length should be as short as possible.
This ground wire should be clamped or brazed to the Ground Bed Conductor (that is
typically a stranded copper AWG 0000 cable installed vertically or horizontally).
The wire end that is to be fastened to the ControlWave Express should be crimped to a
Terminal Ring/Lug and soldered. Note: Use a high wattage Soldering Iron.
The ground wire should be run such that any routing bend in the cable has a minimum
radius of 12-inches below ground and 8-inches above ground.
Click here to return to Table of Contents