- Emerson Remote Terminal Unit Instruction Manual

1-10 / Introduction CI-ControlWave Express
1.3.2.3 CPU/System Controller Board Configuration Jumpers
ControlWave Express CPU/System Controller Board are provided with 12 User
Configuration Jumpers that function as follows:
W1 - COM1 CTS Use Selection
1 to 2 = COM1 CTS Source is from Device
2 to 3 = COM1 RTS to CTS Loopback
W2 - COM2 CTS Use Selection
1 to 2 = COM2 CTS Source is from Device
2 to 3 = COM2 RTS to CTS Loopback
W3 - Enable/Disable Battery Backup Selection
1 to 2 = Enable Battery Backup
2 to 3 = Disable Battery Backup
W5 - Power Supply Shut-down Selection
1 to 2 = 12/24V Power Supply Shut-down Hysterisis
2 to 3 = 6V Power Supply Shut-down Hysterisis
W6 - Power Supply Shut-down Selection
1 to 2 = 12V Power Supply Shut-down
2 to 3 = 6/24V Power Supply Shut-down
W7 - Power Fail Trip Point Hysterisis Selection
1 to 2 = 12/24V Power Fail Trip Point Hysterisis
2 to 3 = 6V Power Fail Trip Point Hysterisis
W8 - Power Fail Trip Point Selection
1 to 2 = 12V Power Fail Trip Point
2 to 3 = 6/24V Power Fail Trip Point
W12 - COM3 Configuration Selection
1 to 2 = COM3 is RS-232
2 to 3 = COM3 is RS-485
W13 - COM3 Configuration Selection
1 to 2 = COM3 is RS-232
2 to 3 = COM3 is RS-485
W14 - COM3 Configuration Selection
1 to 2 = COM3 is RS-232
2 to 3 = COM3 is RS-485
W15 - COM3 Configuration Selection
1 to 2 = COM3 is RS-232
2 to 3 = COM3 is RS-485
W16 - COM3 Configuration Selection
1 to 2 = COM3 is RS-232
2 to 3 = COM3 is RS-485
Click here to return to Table of Contents