- Emerson Remote Terminal Unit Instruction Manual

C-18 / Appendix C - Hardware Installation Guide CI-ControlWave Express
(See Table C-7 for Definitions)
Table C-7 - System Status Codes on LCD Display
& LEDs on CPU/System Controller Board’s LED Board.
LED
6
STA6
LED
5
STA5
LED
4
STA4
LED
3
STA3
LED
2
STA2
LED
1
STA1
Status
In
Hex
LCD
Disp.
Indication
Definition
0 0 0 0 0 0 00 Blank Application Running
0 0 0 0 0 1 01 DIAG Unit in Diagnostic Mode
0 0 0 0 1 1 03 R DIAG Unit Running Diagnostics
0 0 0 1 0 0 04 FWXSUM
Flash XSUM Error
0 0 0 1 0 1 05 DEVERR Error Initializing Application Device
0 0 0 1 1 1 07 FLASH Flash Programming Error
0 0 1 0 0 0 08 FACT Using Factory Defaults *
0 0 1 0 0 1 09 BATT Battery Failure Detected *
0 0 1 0 1 0 0A STRTUP Currently Loading the Boot Project
0 0 1 0 1 1 0B INIT System Initialization in Progress
0 1 0 0 0 0 10 RECOV Waiting in Recovery Mode
0 1 0 0 1 0 12 RAMERR Error Testing SRAM
1 0 0 0 0 0 20 STOP Application Loaded
1 0 1 0 0 0 28 HALT Stopped at a Break Point
1 1 0 0 0 0 30 NO APP No Application Loaded
1 1 1 0 0 0 38 BREAKP Running with Break Points
1 1 1 0 1 1 3B POWERD Waiting for Power-down (after NMI)
1 1 1 1 1 0 3E UPDUMP
Waiting for Updump to be Performed
1 1 1 1 1 1 3F NOTRUN Unit Crashed (Watchdog Disabled)
* = Flashed at startup
Click here to return to Table of Contents