9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name
Address
Data
Type
Client
Access
Description
Modicon Daniel
Control.RemoteExclusive 2039 2039 Boolean R/W
Device access mode (0=Remote&LOI,
1=RemoteOnly)
Control.ResetDevice 2037 2037 Boolean R/W reset the device: 0=none, 1=reset
Info.ChannelId1
3201…
3210
3201…
3210
String RO channel identication text of comp1
Info.ChannelId2
3211…
3220
3211…
3220
String RO channel identication text of comp2
Info.ChannelId3
3221…
3230
3221…
3230
String RO channel identication text of comp3
Info.ChannelId4
3231…
3240
3231…
3240
String RO channel identication text of comp4
Info.EndOfRange1
6069…
6070
9035 Float RO end of range of component1
Info.EndOfRange2
6071…
6072
9036 Float RO end of range of component2
Info.EndOfRange3
6073…
6074
9037 Float RO end of range of component3
Info.EndOfRange4
6075…
6076
9038 Float RO end of range of component4
Info.InstalledOptions.DIO_Installed 3030 3030 Word RO
dig. IO installed: 0=None, 1=Card1, 2 =
Card1+2
Info.InstalledOptions.FlowAlarmInstalled 3023 3023 Word RO digital ow alarm installed
Info.InstalledOptions.FlowSensorAssigned1 3273 3273 Word RO
ow sensor assigned to comp1
(0=None, etc.)
Info.InstalledOptions.FlowSensorAssigned2 3274 3274 Word RO
ow sensor assigned to comp2
(0=None, etc.)
Info.InstalledOptions.FlowSensorAssigned3 3275 3275 Word RO
ow sensor assigned to comp3
(0=None, etc.)
Info.InstalledOptions.FlowSensorAssigned4 3276 3276 Word RO
ow sensor assigned to comp4
(0=None, etc.)
Info.InstalledOptions.PressureSensorIn-
stalled
3027 3027 Word RO
pressure (0=manual,1=intSens,2=cyclR
emote,3=comp2)
Info.InstalledOptions.PumpInstalled 3043
3043 Word RO
pump is installed and controlled by
device
Info.InstalledOptions.SIntInstalled 3025 3025 Word RO serial interface hardware installed
Info.InstalledOptions.TempSensorAssigned1 3277 3277 Word RO
temp sensor assigned to comp1
(0=None, etc.)
Info.InstalledOptions.TempSensorAssigned2 3278 3278 Word RO
temp sensor assigned to comp2
(0=None, etc.)
Info.InstalledOptions.TempSensorAssigned3 3279 3279 Word RO
temp sensor assigned to comp3
(0=None, etc.)
Info.InstalledOptions.TempSensorAssigned4 3280 3280 Word RO
temp sensor assigned to comp4
(0=None, etc.)