User Manual

80 Using AMS Device Manager to configure the meter
Section 4: Configuration Daniel 3814 Liquid Ultrasonic Meter Installation Manual
March 2015 3-9000-760 Rev E
g. Click Service Tools|Variables|All Variables tab to view Primary, Secondary, Third
and Fourth Variable parameter status.
Figure 4-17 AMS Device Manager - Service Tools All Variables
Gauges display each variable’s status as good or bad. If a status is bad refer to the
Service Tools Alerts page for recommended actions to resolve the alert condition. Also
refer to the Field Device Specification manual (P/N 3-9000-762) for Commands 48 and
140 details.
Alerts are triggered for Command 48 Additional device status and Command 140
detailed status information. Alerts are grouped as Failed - Fix Now, Maintenance - Fix
Soon and Advisory according to the severity level; 1-6. Severity 1 is the highest and 6 is
the lowest level.