Product Overview

2004FC-118 R16 (01/16) Emerson Climate Technologies
TPC 5
Temperature Pressure Controls
PS2 Series Dual Control
PS2 Dual Pressure Controls are designed for use on high and
low pressure applications in refrigeration, air conditioning, and
heat pump systems. This control react to changes in either
low or high side pressures, providing single-device control of the
compressor or other electrical device.
Features
Adjustable pressures and differentials
Narrow adjustable differential depending on model
Range and differential pointer in units bar and psig
Range and differential individually lockable by tab
High rated SPDT contacts for all versions
Captive terminal and cover screws
Manual toggle for system checkout and override
Factory installed wire bridge for reduced installation effort
High side convertible from manual to auto reset.
Options
Different pressure connections
Automatic and manual reset versions
Factory set to customer specification
Specifications
SPDT switch rated for 12FLA and 72LRA at 240VAC and 16FLA
and 96LRA at 120VAC
Agency approvals include:
UL/CUL le number E85974,
CE per (LVD) low voltage directive
Dimensional Diagram mm (in)
Nomenclature example: PS2-Y7A
PS2 Function Pressure Range Connection Type
Adjustable
Dual Pressure
Control
X = Auto reset Internal range
and differential adjust-
ments
7 = Left side: 9” Hg to 102 psig (-0.3
to 7 bar)
Right side: 87 to 464 psig
(6 to 32 bar)
A = 1/4” SAE are tting
K = 1 m (3 ft.) cap tube w/1/4” are nut
L = 1 m (3 ft.) cap tube w/ 1/4” ODM solder
connection
Y = Low side: Auto reset
Y = High side: Convertible reset
External range and
external differential
Ordering Information
Dual Pressure
Control
PCN
Low Pressure Side High Pressure Side
Connection Type
Pressure Range Differential
Factory
Setting
Pressure Range Differential
Factory
Setting
PS2-Y7A 099008
9” Hg to 102 psig 15 to 73 psig
49/65
psig
87 to 464 psig Fixed 290 psig
1/4” SAE are tting
PS2-Y7K 099009 1 m (3 ft.) cap tube w/ 1/4” are nut