Submittal Sheet

Thermal
Expansion Valves
TXV Extended
Capacity Tables
EX Valves
and Controls
EX Extended
Capacity Tables
Solenoid Valves
and Coils
Solenoid Capacity
Tables
Industrial Solenoid
Valves
Shut Off
Valves
System
Protectors
System Protectors
Capacity Tables
Oil
Controls
Temperature
Pressure Controls
Emerson Climate Technologies166
2003FC-91 R10 (06/15)
The Builder Series lter drier provides an economical system
protection for air conditioning applications.
Features
ODF - Solid copper connections
for easy installation
Solid core construction
40 micron ltration
Maximum working pressure = 680 psig
Specifications
Desiccant blend - optimized for high water capacity and
acid capacity
Filtration: 40 microns
Maximum working pressure: 680 psig
UL/CUL le number: SA 7175
Nomenclature example: BS-L0835VV
BS L 08 3 S VV
Drier
Series
L= Liquid
S = Suction
B = Bi Flow
Unit Size
(in cu. in.)
Connection Size
(in 1/8”)
S = ODF
connections
(omit for SAE)
VV = Dual areas
Valve
(Suction Line Only)
Builder Series Filter Drier
Ordering Information
Liquid Line Service
PCN Model
Water Capacity drops R-22
@ 125 °F
Flow Capacity Tons *
R-22 R-410A
066122 BSL-053S 36 4.9 4.8
066123 BSL-083S 51 4.6 4.5
066098 BSL-084S 51 7.6 7.4
066125 BSL-163S 70 5.3 5.2
066099 BSL-164S 70 9.3 9.1
Suction Line Service
PCN Model
Water Capacity drops R-22
@ 125 °F
Flow Capacity Tons
+
R-22 R-410A
066126 BSS-165S 72 3.4 3.5
066127 BSS-166S 72 4.1 4.2
066128 BSS-167S 72 4.1 4.2
066100 BSS-305S 111 3.4 3.5
066101 BSS-306S 111 5.4 5.5
066129 BSS-307S 111 5.9 6.0
066102 BSS-309S 111 6.1 6.2
Bi-Flow Service
PCN Model
Water Capacity drops R-22
@ 125 °F
Flow Capacity Tons *
R-22 R-410A
066130 BSB-083S 154 5.1 5.1
066131 BSB-163S 223 5.2 5.1
*Ratings in accordance with AHRI Standard 710
+
Ratings in accordance with AHRI Standard 730

Summary of content (1 pages)