Product Overview
2004FC-118 R12 (05/13)
Emerson Climate Technologies
TXV 2
Thermal Expansion Valves
Nomenclature example: AACEB 2 HC 30 IN 3/8 x 1/2 ODF ANG
A A C E B 2 H C 30 IN 3/8 x 1/2 ODF ANG
Valve 
Series 
Hermetic 
Design
Superheat 
Adjustment 
A = Adjustable
 N = Non-
Adjustable
Internal 
Check 
Valve 
(optional) 
Reverse 
Flow
Bypass 
Applica-
tion
 Equalizer 
E=External 
(Omit for 
Internal)
Bleed 
Hole 
(optional) 
(Omit for 
no bleed 
hole)
Capacity 
Nominal 
Rating in 
Tons 
(See nominal 
capacity table 
below)
Refrigerant 
Code
 +F = R-12
• H = R-22
+M = R-134a
• N = R-407C
*P = R-507
*R = R-502
*S = R-404A
Z = R-410A
Charge Code
C = medium 
temp
CA = heat pump
W(MOP) = 
press. limiting
Z = low temp
AA = wide range
Capillary  
Tube 
Length
30 IN 
&
5 FT (std)
Inlet x Outlet 
Connection 
Sizes
1/4 x 3/8
3/8 x 1/2
1/2 x 5/8
5/8 x 7/8
Connection 
Type 
SAE=are
ODF = solder
Chatleff 
(optional)
Aeroquip 
(optional)
Conguration
S/T = straight-thru
ANG = 90° angle
+ = R-12 and R-134a are interchangeable refrigerant charges
* = R-507, R-502 and R-404A are interchangeable refrigerant charges
• = R-22 and R-407C are interchangeable refrigerant charges
AA/AN Series – Nominal* Capacity Table in Tons (kW)
R-12 R-134a R-22 R-410A R-502 R-507/R-404A R-407C
– 1/8 (0.4) 1/5 (0.7) – – 1/8 (0.4) 1/5
1/8 (0.4) 1/4 (0.9) 1/4 (0.9) 1/4 (0.9) 1/8 (0.4) 1/4 (0.9) 1/4 (0.9)
1/4 (0.9)  1/2 (1.8) 1/2 (1.8) 1/2 (1.8) 1/4 (0.9) 1/2 (1.8) 1/2 (1.8)
1/2 (1.8) 3/4 (2.7) 1 (3.5) 1 (3.5) 1/2 (1.8) 3/4 1 (3.5)
1 (3.5) 1 (3.5) 1½ (5.3) 1½ (5.3) 1 (3.5) 1 (3.5) 1¼ (4.4)
– 1½ (5.3) 2 (7.0) 2 (7.0) – 1¼ (4.4) 2 (7.0)
1½ (5.3) 2 (7.0) 2½ (8.8) 3 (11.0) 1½ (5.3) 2 (7.0) 2½ (8.8)
2 (7.0) 2½ (9.0) 3 (11.0) 4 (14.0) 2 (7.0) 2¼ (8.0) 3¼ (11.5)
2½ (9.0) 3 (11.0) 4 (14.0) 5 (17.0) 2½ (8.8) 2½ (8.8) 4 (14.0)
3 (11.0)  4 (14.0) 5 (17.0) – 3 (11.0) 3½ (12.0) 5¼ (19.0)
All capacities shown are at 100°F condensing, 40°F evaporator temperature.
*See Extended Capacity Tables for ratings at a wide range of conditions per ARI standard 750.
Features
•  Stainless steel power element eliminates corrosion and
  prevents valve failure
•  Hermetic, leak-free construction
•  Compact size allows installation in limited spaces
•  Mass spectrometer tested to ensure less than 0.10 oz/year
  external leakage rate
A-Series
Specifications 
Maximum working pressure:  700 psig
UL/CUL le number:  SA 5312
The A-series is used for heat pump, air conditioning, food services 
and commercial applications. 
Options
•  ZW195 charge available for R-410A systems
•  Adjustable or non-adjustable superheat 
•  SAE or ODF connections standard – Chatleff or Aeroquip
  are available
•  External or internal equalizer 
•  Internal check valve allows reverse ow for heat   
  pump applications, eliminating the need for external piping 
  and external check valve
•  Bleed type pressure equalization to accommodate
  PSC type compressors
•  Pressure limiting charges (MOP) available
R-410A