Selection Guide
Emerson Climate Technologies144
Solenoid
Valves
Temperature
Pressure Controls
Coils
Industrial
Solenoid Valves
Shut Off
Valves
System
Protectors
Storage
Devices
Oil
Controls
Pressure
Regulators
Competitive Cross
Reference
Thermal
Expansion Valves
BFK Capacity Tables
1
All ratings in accordance with ARI Standard 710-04. 86
o
F liquid refrigerant temperature
2
Water Capacities are based on:
3
20 drops of water = 1 gram = 1 cc
5
o
F saturated vapor temperature Equilibrium Point Dryness (EPD) of:
3.1 lbs./min./ton for R-134a 50 parts per million for R-134a, R404-A/507,
2.9 lbs./min./ton for R-22 and R-407C R-410A and R-407C
4
For 2 PSI ∆P, Multiply values by 1.4
4.0 lbs./min./ton for R-404A/507 and R-12 60 parts per million for R-22
4.4 lbs./min./ton for R-502 15 parts per million for R-12
2.7 lbs./min./ton for R-410A 30 parts per million for R-502
Liquid Refrigerant Holding Capacity-Ounces
Unit Size
R-22 R-407C R-410A
75°F 125°F 75°F 125°F 75°F 125°F
05
4.6
4.2
4.4
3.9 4.1 3.5
08
7.7
6.9
7.3
6.4 6.9 5.8
16
14.2
12.7
13.5
11.8 12.6 10.6
30
21.0
18.7
20.0
17.4 19.6 16.5
Description Connection
Flow Capacity
Tons @ 1 psi ∆P
1, 4
(For kW, multiply tons by 3.5)
Water Capacity
2
Drops Of Water
3
R-22 R-407C R-410A
R-22 R-410A R-407C 75°F 125°F 75°F 125°F 75°F 125°F
BFK-05 2 1/4 SAE 1.6 1.6 1.6
73 66 58 42 39 35BFK-05 2S 1/4 ODF 2.2 2.2 2.2
BFK-05 3S 3/8 ODF 4.0 4.0 3.9
BFK-08 3 3/8 SAE 4.5 4.5 4.4
159 144 106 79 85 75
BFK-08 3S 3/8 ODF 5.1 5.1 5.0
BFK-08 4 1/2 SAE 6.4 6.4 6.3
BFK-08 4S 1/2 ODF 6.7 6.7 6.6
BFK-08 5S 5/8 ODF 8.1 8.1 7.9
BFK-16 3 3/8 SAE 4.6 4.6 4.5
323 294 237 179 178 160
BFK-16 3S 3/8 ODF 5.2 5.2 5.1
BFK-16 4 1/2 SAE 7.7 7.7 7.6
BFK-16 4S 1/2 ODF 8.1 8.1 7.9
BFK-16 5 5/8 SAE 8.3 8.3 8.1
BFK-16 5S 5/8 ODF 8.7 8.7 8.5
BFK-30 3S 3/8 ODF 5.8 5.8 5.7
585 532 452 345 415 293
BFK-30 4 1/2 SAE 7.6 7.6 7.5
BFK-30 4S 1/2 ODF 9.7 9.7 9.5
BFK-30 5 5/8 SAE 10.3 10.3 10.1
BFK-30 5S 5/8 ODF 14.2 14.2 13.9
BFK-30 6S 3/4 ODF 16.0 16.0 15.7
BFK-30 7S 7/8 ODF 16.7 16.7 16.4