Product Overview
2004FC-118 R13 (01/14) Emerson Climate Technologies
SOL 14
Solenoid Valves & Coils
Ordering Information and Nominal* Liquid Capacity Table – Tons (kW)
PCN
Description
Connection
Size
R-12 R-134a R-22 R-407C R-404A/R-507 R-502
Standard Valve Mounting Stud
1
060391 058573 540RA 8 T 4 1/2 ODF
12.2 (43.4) 14.8 (52.5) 15.6 (55.2) 14.8 (52.4) 10.3 (36.5) 10.1 (35.6)060392 046265 540RA 8 T 5 5/8 ODF
060393 046989 540RA 8 T 7 7/8 ODF
060394 046266 540RA 9 T 5 5/8 ODF 18.2 (64.6) 22.0 (78.0) 23.3 (82.5) 22.1 (78.2) 15.3 (54.2) 15.1 (53.4)
060395 046268 540RA 9 T 7 7/8 ODF
24.0 (85.0) 28.9 (102.3) 30.5 (108.0) 29.0 (103.0) 20.1 (71.1) 19.8 (70.1)
060396 047497 540RA 9 T 9 1 1/8 ODF
060397 046269 540RA 12 T 7 7/8 ODF
27.6 (97.6) 33.2 (117.5) 34.9 (123.0) 33.2 (118.0) 23.0 (81.0) 22.7 (80.0)
060398 047498 540RA 12 T 9 1 1/8 ODF
060399 046270 540RA 16 T 9 1 1/8 ODF
37.3 (132.0) 55.1 (195.1) 58.0 (205.0) 55.2 (195.0) 38.3 (136.0) 37.7 (133.0)
060400 047214 540RA 16 T 11 1 3/8 ODF
060401 047953 540RA 20 T 11 1 3/8 ODF
58.8 (208.0) 86.8 (307.4) 95.4 (338.0) 90.8 (321.0) 65.7 (233.0) 62.0 (219.0)060402 047954 540RA 20 T 13 1 5/8 ODF
060403 047955 540RA 20 T 17 2 1/8 ODF
Features
• Can be brazed into the line without disassembly
• PTFE diaphragm
• Extended ends for easy installation
• Long-life molded coils
• Low pressure differential required for full opening
Specifications
• Maximum uid temperature: 250°F
• Maximum working pressure: 500 psig
• MOPD: 250 psig
• UL/CUL le number: MP604
NOTE: Mounting enclosing tube more than 90
o
off vertical up
position is not recommended.
NOTE: This valve requires a DM, MM or ASC2-Type
coil assembly. ASC2-Type Coil requires snap
cap and cable assembly (PCN:059261).
The 540RA is a 2-way, normally open diaphragm valve. 540RA
valves are used for liquid, suction and hot gas service.
1
Add “T” to the end of description for Mounting Stud
Capacities based on 100°F liquid and 40°F saturated evaporator per ARI standard 760-87.
*See Extended Capacity Tables for ratings at a wide range of conditions.
Nomenclature example: 540RA 8T5 VLC
540R A
8 T 5 VLC
Valve
Series
Design
Series
Port Size
(in 1/16”)
Connection Type
T = copper entended ends
Connection Size
(in 1/8”)
Coil*
* NOTE: Valves are shipped without the solenoid coils (VLC = Valve Less Coil). See coil assemblies for availability.
540RA