Product Overview

2004FC-118 R16 (01/16)
Emerson Climate Technologies
TXV 2
Thermal Expansion Valves
Nomenclature example: AACEB 2 HC 30 IN 3/8 x 1/2 ODF ANG
A A C E B 2 H C 30 IN 3/8 x 1/2 ODF ANG
Valve
Series
Hermetic
Design
Superheat
Adjustment
A = Adjustable
N = Non-
Adjustable
Internal
Check
Valve
(optional)
Reverse
Flow
Bypass
Applica-
tion
Equalizer
E=External
(Omit for
Internal)
Bleed
Hole
(optional)
(Omit for
no bleed
hole)
Capacity
Nominal
Rating in
Tons
(See nominal
capacity table
below)
Refrigerant
Code
+F = R-12
• H = R-22
+M = R-134a
• N = R-407C
*P = R-507
*R = R-502
*S = R-404A
Z = R-410A
*B = R-448A
/R-449A
+D = R-450A
/R-513A
Charge Code
C = medium
temp
CA = heat pump
W(MOP) =
press. limiting
Z = low temp
AA = wide range
Capillary
Tube
Length
30 IN
&
5 FT (std)
Inlet x Outlet
Connection
Sizes
1/4 x 3/8
3/8 x 1/2
1/2 x 5/8
5/8 x 7/8
Connection
Type
SAE=are
ODF = solder
Chatleff
(optional)
Aeroquip
(optional)
Conguration
S/T = straight-thru
ANG = 90° angle
+ = R-12, R-134a, R-450A and R-513A are interchangeable refrigerant charges
* = R-507, R-502, R-404A, R-448A and R-449A are interchangeable refrigerant charges
• = R-22 and R-407C are interchangeable refrigerant charges
AA/AN Series – Nominal* Capacity Table in Tons (kW)
R-12 R-134a R-450A/R-513A R-22 R-410A R-502 R-507/R-404A **R-448A/R-449A R-407C
1/8 (0.4) 1/8 (0.4) 1/5 (0.7) 1/8 (0.4) 1/5 (0.7) 1/5
1/8 (0.4) 1/4 (0.9) 1/5 (0.7) 1/4 (0.9) 1/4 (0.9) 1/8 (0.4) 1/4 (0.9) 1/4 (0.9) 1/4 (0.9)
1/4 (0.9) 1/2 (1.8) 1/4 (0.9) 1/2 (1.8) 1/2 (1.8) 1/4 (0.9) 1/2 (1.8) 1/2 (1.8) 1/2 (1.8)
1/2 (1.8) 3/4 (2.7) 1/2 (1.8) 1 (3.5) 1 (3.5) 1/2 (1.8) 3/4 1 (3.5) 1 (3.5)
1 (3.5) 1 (3.5) 3/4 (2.7) 1½ (5.3) 1½ (5.3) 1 (3.5) 1 (3.5) 1½ (5.3) 1¼ (4.4)
1½ (5.3) 1 (3.5) 2 (7.0) 2 (7.0) 1¼ (4.4) 2 (7.0) 2 (7.0)
1½ (5.3) 2 (7.0) 1½ (5.3) 2½ (8.8) 3 (11.0) 1½ (5.3) 2 (7.0) 2¾ (9.7) 2½ (8.8)
2 (7.0) 2½ (9.0) 2 (7.0) 3 (11.0) 4 (14.0) 2 (7.0) 2¼ (8.0) 3½ (12.0) 3¼ (11.5)
2½ (9.0) 3 (11.0) 2½ (9.0) 4 (14.0) 5 (17.0) 2½ (8.8) 2½ (8.8) 4 (14.0) 4 (14.0)
3 (11.0) 4 (14.0) 3 (11.0) 5 (17.0) 3 (11.0) 3½ (12.0) 5½ (20.0) 5¼ (19.0)
All capacities shown are at 100°F condensing, 40°F evaporator temperature.
*See Extended Capacity Tables for ratings at a wide range of conditions per ARI standard 750.
**Use SZ charge for all R-448A/R-449A applications. Recommend oversizing the valve capacity by 50% for low temperature applications.
Features
Stainless steel power element eliminates corrosion and
prevents valve failure
Hermetic, leak-free construction
Compact size allows installation in limited spaces
Mass spectrometer tested to ensure less than 0.10 oz/year
external leakage rate
A-Series
Specifications
Maximum working pressure: 700 psig
UR/CUR le number: SA 5312
The A-series is used for heat pump, air conditioning, food services
and commercial applications.
Options
ZW195 charge available for R-410A systems
Adjustable or non-adjustable superheat
SAE or ODF connections standard – Chatleff or Aeroquip
are available
External or internal equalizer
Internal check valve allows reverse ow for heat
pump applications, eliminating the need for external piping
and external check valve
Bleed type pressure equalization to accommodate
PSC type compressors
Pressure limiting charges (MOP) available

Summary of content (3 pages)