Brochure
Emerson Climate Technologies
98
EX Valves & Controls
Ordering Information
Description Type
Inlet
Connection (in)
Outlet
Connection
(in)
PCN
EX4ElectricalControlValve EX4-I21 3/8 5/8 800615
EX5ElectricalControlValve EX5-U21 5/8 7/8 800618
EX6ElectricalControlValve EX6-I21 7/8 11/8 800620
EX7ElectricalControlValve EX7-I21 11/8 13/8 800624
EX8ElectricalControlValve EX8-I21 15/8 15/8 804631
EX4Bi-FlowElectricalControlValve EX4-U31 5/8 5/8 800617
EX5Bi-FlowElectricalControlValve EX5-U31 7/8 7/8 800619
EX6Bi-FlowElectricalControlValve EX6-I31 11/8 11/8 800622
EX7Bi-FlowElectricalControlValve EX7-U31 13/8 13/8 800626
ValveConnectorCable EXV-M60 N/A N/A 804665
EX4/EX5/EX6/EX7/EX8
Nominal capacities as expansion valves and liquid injection valves
Nominal Capacities in Tons (10% - 100%)
Valve Type R-407C R-22 R-134a R-404A R-410A R-23 R-124 R-744
EX4
.6–5 .6–4.7 .3–3.6 .3–3.3 .6–5.5 .6–5.1 .3–2.6 .9–9.5
EX5
1.4–15.1 1.4–14.2 1.1–11.1 1.1–10 1.7–16.5 1.4–15.4 .9–8 2.8–29
EX6
4.3–35.8 4.3–34.1 2.8–26.4 2.8–23.9 4.3–39.8 3.7–37 2–19.1 6.8–69.4
EX7
10–98.7 10–93.8 7.1–72.5 7.1–65.4 11.4–109.5 – – 19.9–190.5
EX8
28.4–263 25.6–250.2 19.9–193.4 17.1–174.3 28.4–292 – – 51.2–508.7
Note1:EXBi-owversionsarenotreleasedforusewithR-124andR-23refrigerants.
Note2:EXBi-owversionshaveidenticalcapacityinbothowdirection.
Refrigerant Evaporating Temperature Condensing Temperature Subcooling
R-22,R-134a,R-404A,R-410A +40°F +100°F 2°F
R-407C +40°Fdewpoint +100°Fbubble 2°F
R-124 +68°F +176°F 2°F
R-23 -76°F -13°F 2°F
R-744 -40°F 14°F 2°F
Thenominalcapacityisbasedonthefollowingconditions:
EX4-EX8 Electrical Control Valve