EX Valves & Controls
Features
Fullyhermeticdesign
Fastfullstroketime
Applicabletoallcommonrefrigerants(HCFC,HFC),for
subcriticalCO
2
applications
• Highresolutionandexcellentrepeatability
Bi-owversionsforheatpumpapplications
Positiveshut-offfunctiontoeliminatetheuseofan
additionalsolenoidvalve
Linearowcapacity
Widecapacityrange(10-100%)
Continuousmodulationofmassow,nostress
(liquidhammering)intherefrigerationcircuit
Directcouplingofmotorandvalveforhighreliability
(nogearmechanism)
Ceramicslideandportforaccurateowandminimalwear
Balancedforcedesign
Corrosionresistantstainlesssteelbody,andconnections
Specifications
CEmarking: EX4/EX5:notrequired
EX6-EX8:required,CatI,ModuleA
MOPD: EX4-EX6:580psid
EX7:507psid
EX8:435psid
MWP: EX4-EX7:870psig
EX8:650psig
Ambienttemperature: -40°Fto+130°F
Humidity: 5to95%R.H.
Externalleakage: ≤0.1oz/yr(R-22)
Steppermotortype: Bi-polar,phasecurrentby
choppercontrol
(constantcurrent)
Electricalconnection: 4pinterminalviaplug
Driversupplyvoltage: Recommended:24VDC
Range:18-36VDC
Phasecurrent(operating): EX4-EX6:500mAmax
EX7:750mA
EX8:800mA
Holdingcurrent: EX4-EX6:100mA
EX7:250mA
EX8:500mA
Nominalinputpower
perphase: EX4-EX6:3.5W
EX7-EX8:5W
Phaseinductance: EX4-EX6:30mH±25%
EX7:20mH±25%
EX8:22mH±25%
Stepmode: 2phasefullstep
Stepangle: 1.8°perstep±8%
Totalnumberofsteps: EX4-EX6:750fullsteps
EX7:1600fullsteps
EX8:2600fullsteps
Steppingrate: 500Hz
Windingresistance
perphase: EX4-EX6:13ohm±10%
EX7:8ohm±10%
EX8:6ohm±10%
Fulltraveltime: EX4-EX6:1.5seconds
EX7:3.2seconds
EX8:5.2seconds
TheEX4-EX8aresteppermotordrivenvalvesthatareoptimizedforthe
controlofliquidorgaseousmassowinrefrigerationsystems.Multifunction
capabilityasexpansionvalve,hotgasbypass,suctiongasthrottling,head
pressure,liquidlineactuatorandotherapplicationssystems.
Valve
Type
Inlet x Outlet
(ODF)
B C D E H1 H2
EX4-I21
3/8”x5/8” 0.3 1.8 2.2 0.4 4.4 1.0
EX5-U21
5/8”x7/8” 0.4 2.2 2.6 0.6 4.4 1.0
EX6-I21
7/8”x1-1/8” 0.6 2.6 3.0 0.7 4.4 1.0
EX7-I21
1-1/8”x1-3/8” 0.8 3.1 3.2 0.9 6.2 1.7
EX8-I21
1-5/8”x1-5/8” 0.8 3.1 3.1 0.8 7.9 2.2
Dimensional Data (in)
EX4-EX8 Electrical Control Valve