TXV Extended Capacity Tables
R-410A Conventional Valves (kWatts)– A Series
Evaporator Temperature
10°C 0°C -10°C
Nominal Pressure Drop Across Valve (kPa) Pressure Drop Across Valve (kPa) Pressure Drop Across Valve (kPa)
Valve Type Rating 750 1000 1100 1450 1700 2000 750 1000 1100 1450 1700 2000 750 1000 1100 1450 1700 2000
AA/AN/AAC/ANC 1/4 1.20 1.39 1.46 1.67 1.81 1.97 1.20 1.39 1.46 1.67 1.81 1.97 1.17 1.35 1.41 1.62 1.76 1.91
AA/AN/AAC/ANC/AFA 1/2 2.12 2.45 2.57 2.95 3.20 3.47 2.09 2.41 2.53 2.90 3.14 3.41 2.05 2.37 2.49 2.85 3.09 3.35
AA/AN/AAC/ANC/AFA 1 3.40 3.92 4.12 4.73 5.12 5.55 3.36 3.88 4.07 4.68 5.06 5.49 3.29 3.80 3.99 4.58 4.96 5.38
AA/AN/AAC/ANC/AFA 1-1/2 4.89 5.64 5.92 6.79 7.35 7.98 4.81 5.56 5.83 6.69 7.25 7.86 4.71 5.44 5.70 6.55 7.09 7.69
AA/AN/AAC/ANC/AFA 2 7.19 8.30 8.70 9.99 10.82 11.74 7.12 8.22 8.62 9.89 10.71 11.62 6.94 8.01 8.40 9.65 10.45 11.33
AA/AN/AAC/ANC/AFA 3 10.09 11.65 12.22 14.03 15.19 16.48 9.98 11.53 12.09 13.88 15.03 16.30 9.70 11.20 11.75 13.49 14.60 15.84
AA/AN/AAC/ANC/AFA 4 12.35 14.27 14.96 17.18 18.60 20.17 12.21 14.10 14.79 16.98 18.39 19.94 11.89 13.73 14.40 16.54 17.91 19.42
AA/AN/AAC/ANC 5 14.66 16.92 17.75 20.38 22.06 23.93 14.51 16.76 17.58 20.18 21.85 23.70 14.12 16.31 17.11 19.64 21.27 23.07
Evaporator Temperature
-20°C -30°C -40°C
Nominal Pressure Drop Across Valve (kPa) Pressure Drop Across Valve (kPa) Pressure Drop Across Valve (kPa)
Valve Type Rating 1000 1100 1450 1700 2000 2300 1000 1100 1450 1700 2000 2300 1000 1100 1450 1700 2000 2300
AA/AN/AAC/ANC 1/4 1.20 1.26 1.45 1.57 1.70 1.83 0.85 0.89 1.02 1.11 1.20 1.29 0.57 0.59 0.68 0.74 0.80 0.86
AA/AN/AAC/ANC/AFA 1/2 2.12 2.23 2.56 2.77 3.00 3.22 1.45 1.52 1.75 1.89 2.05 2.20 0.96 1.00 1.15 1.25 1.35 1.45
AA/AN/AAC/ANC/AFA 1 3.36 3.53 4.05 4.38 4.76 5.10 2.34 2.45 2.81 3.05 3.30 3.54 1.56 1.63 1.88 2.03 2.20 2.36
AA/AN/AAC/ANC/AFA 1-1/2 4.81 5.05 5.80 6.28 6.81 7.30 3.36 3.53 4.05 4.38 4.76 5.10 2.23 2.34 2.69 2.91 3.15 3.38
AA/AN/AAC/ANC/AFA 2 7.12 7.46 8.57 9.28 10.06 10.79 4.96 5.20 5.97 6.46 7.01 7.52 3.29 3.45 3.96 4.29 4.66 4.99
AA/AN/AAC/ANC/AFA 3 9.98 10.47 12.02 13.02 14.12 15.14 6.94 7.28 8.35 9.05 9.81 10.52 4.60 4.83 5.54 6.00 6.51 6.98
AA/AN/AAC/ANC/AFA 4 12.25 12.85 14.75 15.97 17.32 18.58 8.50 8.91 10.23 11.08 12.02 12.88 5.66 5.94 6.82 7.38 8.01 8.59
AA/AN/AAC/ANC 5 14.51 15.22 17.48 18.92 20.53 22.01 10.09 10.58 12.15 13.15 14.27 15.30 6.69 7.02 8.06 8.72 9.46 10.15
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an average evaporator temperature of 0°F.
However, they may be used for any evaporator temperature from ‑40°F to +40°F since the variation in the actual factors across this range is insignicant.
Refrigerant Liquid Temperature Correction Factors
Refrigerant Liquid Temperature °F
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
R-12 Correction Factor 1.60 1.54 1.48 1.42 1.36 1.30 1.24 1.18 1.12 1.06 1.00 .94 .88 .82 .75
R-134a Correction Factor 1.70 1.63 1.56 1.49 1.42 1.36 1.29 1.21 1.14 1.07 1.00 .93 .85 .78 .71
R-22 Correction Factor 1.56 1.51 1.45 1.40 1.34 1.29 1.23 1.17 1.12 1.06 1.00 .94 .88 .82 .76
R-404A/R-507 Correction 2.00 1.90 1.80 1.70 1.60 1.50 1.40 1.30 1.20 1.10 1.00 .90 .80 .70 .50