TXV Extended Capacity Tables
      Evaporator Temperature
  -20°C  -30°C  -40°C
  Nominal  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve (kPa)
Valve Type  Rating 400 600  700  800  1000 1100  600  700  800  1000 1100  1200  600  700 800 1000 1100 1200
AA/AN/AFA  1/8  0.32  0.39  0.42  0.45  0.50  0.53  0.25  0.30  0.33  0.35  0.39  0.41  0.18  0.22  0.23  0.25  0.28  0.29
AA/AN/AAC/ANC  1/4  0.57  0.69  0.75  0.80  0.90  0.94  0.42  0.52  0.56  0.60  0.67  0.70  0.28  0.35  0.37  0.40  0.45  0.47
AA/AN/AAC/ANC/AFA  1/2  0.99  1.21  1.31  1.40  1.57  1.64  0.78  0.95  1.03  1.10  1.23  1.29  0.50  0.61  0.66  0.70  0.78  0.82
AA/AN/AAC/ANC/AFA  3/4  1.56  1.91  2.06  2.20  2.46  2.58  1.24  1.52  1.64  1.75  1.96  2.05  0.81  1.00  1.08  1.15  1.29  1.35
AA/AN/AAC/ANC/AFA  1  2.23  2.73  2.95  3.15  3.53  3.70  1.77  2.17  2.34  2.50  2.80  2.94  1.13  1.39  1.50  1.60  1.79  1.88
AA/AN/AAC/ANC/AFA  1-1/2  3.29  4.03  4.36  4.66  5.21  5.46  2.58  3.16  3.42  3.65  4.09  4.29  1.70  2.08  2.25  2.40  2.69  2.82
AA/AN/AAC/ANC/AFA  2  4.64  5.68  6.13  6.56  7.33  7.69  3.65  4.47  4.82  5.16  5.77  6.05  2.37  2.90  3.14  3.35  3.75  3.93
AA/AN/AAC/ANC/AFA  2-1/2  5.70  6.98  7.54  8.06  9.01  9.45  4.46  5.46  5.90  6.31  7.05  7.40  2.90  3.56  3.84  4.11  4.59  4.81
AA/AN/AAC/ANC  3  6.76  8.28  8.94  9.56  10.69  11.21  5.31  6.50  7.02  7.51  8.40  8.81  3.47  4.25  4.59  4.91  5.49  5.75
AA/AN/AAC/ANC/AFA  4  9.24  11.32  12.22  13.07  14.61  15.32  7.22  8.84  9.55  10.21  11.42  11.98  4.74  5.81  6.28  6.71  7.50  7.87
TCLE  1/4  0.85  1.04  1.12  1.20  1.34  1.41  0.67  0.82  0.89  0.95  1.06  1.12  0.42  0.52  0.56  0.60  0.67  0.70
TCLE  3/4  1.59  1.95  2.11  2.25  2.52  2.64  1.24  1.52  1.64  1.75  1.96  2.05  0.81  1.00  1.08  1.15  1.29  1.35
TCLE  1-1/2  3.22  3.95  4.26  4.56  5.09  5.34  2.51  3.08  3.32  3.55  3.97  4.17  1.63  1.99  2.15  2.30  2.57  2.70
TCLE  2-1/2  5.91  7.24  7.82  8.36  9.35  9.80  4.64  5.68  6.13  6.56  7.33  7.69  3.04  3.73  4.03  4.31  4.81  5.05
TCLE  3-1/2  8.60  10.54  11.38  12.17  13.60  14.27  6.76  8.28  8.94  9.56  10.69  11.21  4.43  5.42  5.85  6.26  7.00  7.34
TCLE  5-1/2  12.50  15.30  16.53  17.67  19.76  20.72  9.81  12.01  12.97  13.87  15.50  16.26  6.41  7.85  8.48  9.06  10.13  10.63
TCLE  7-1/2  17.20  21.07  22.76  24.33  27.20  28.53  13.49  16.52  17.84  19.07  21.33  22.37  8.81  10.80  11.66  12.47  13.94  14.62
TCLE  9  20.74  25.41  27.44  29.34  32.80  34.40  16.28  19.94  21.54  23.03  25.75  27.00  10.66  13.05  14.10  15.07  16.85  17.67
TJL  9  18.37  22.50  24.30  25.98  29.05  30.47  14.41  17.65  19.06  20.38  22.78  23.89  9.42  11.53  12.46  13.32  14.89  15.62
TJL  11  23.43  28.70  31.00  33.14  37.05  38.86  18.41  22.55  24.35  26.03  29.11  30.53  12.04  14.74  15.92  17.02  19.03  19.96
R-404A/R-507 Conventional Valves (kWatts) – A Series, T Series
      Evaporator Temperature
  10°C  0°C  -10°C
  Nominal  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve(kPa)  Pressure Drop Across Valve (kPa)
Valve Type  Rating 400 600 700 800 1000 1100 400 600 700 800 1000 1100 400 600 700 800 1000 1100
AA/AN/AFA  1/8  0.39  0.48  0.52  0.55  0.62  0.65  0.39  0.48  0.52  0.55  0.62  0.65  0.35  0.43  0.47  0.50  0.56  0.59
AA/AN/AAC/ANC  1/4  0.67  0.82  0.89  0.95  1.06  1.12  0.67  0.82  0.89  0.95  1.06  1.12  0.64  0.78  0.84  0.90  1.01  1.06
AA/AN/AAC/ANC/AFA  1/2  1.17  1.43  1.55  1.65  1.85  1.94  1.17  1.43  1.55  1.65  1.85  1.94  1.10  1.34  1.45  1.55  1.74  1.82
AA/AN/AAC/ANC/AFA  3/4  1.91  2.34  2.53  2.70  3.02  3.17  1.84  2.25  2.44  2.60  2.91  3.05  1.77  2.17  2.34  2.50  2.80  2.94
AA/AN/AAC/ANC/AFA  1  2.73  3.34  3.61  3.85  4.31  4.52  2.66  3.25  3.51  3.75  4.20  4.40  2.51  3.08  3.32  3.55  3.97  4.17
AA/AN/AAC/ANC/AFA  1-1/2  4.00  4.90  5.29  5.66  6.32  6.63  3.89  4.77  5.15  5.51  6.16  6.46  3.72  4.55  4.92  5.26  5.88  6.16
AA/AN/AAC/ANC/AFA  2  5.59  6.85  7.40  7.91  8.84  9.28  5.49  6.72  7.26  7.76  8.68  9.10  5.20  6.37  6.88  7.36  8.23  8.63
AA/AN/AAC/ANC/AFA  2-1/2  6.87  8.41  9.08  9.71  10.86  11.39  6.69  8.19  8.85  9.46  10.58  11.10  6.37  7.80  8.43  9.01  10.08  10.57
AA/AN/AAC/ANC  3  8.14  9.97  10.77  11.51  12.87  13.50  7.97  9.76  10.54  11.26  12.59  13.21  7.58  9.28  10.02  10.71  11.98  12.56
AA/AN/AAC/ANC/AFA  4  11.15  13.66  14.75  15.77  17.63  18.49  10.90  13.35  14.42  15.42  17.24  18.08  10.34  12.66  13.67  14.62  16.34  17.14
TCLE  1/4  1.03  1.26  1.36  1.45  1.62  1.70  0.99  1.21  1.31  1.40  1.57  1.64  0.96  1.17  1.26  1.35  1.51  1.59
TCLE  3/4  1.91  2.34  2.53  2.70  3.02  3.17  1.88  2.30  2.48  2.65  2.97  3.11  1.77  2.17  2.34  2.50  2.80  2.94
TCLE  1-1/2  3.86  4.73  5.10  5.46  6.10  6.40  3.79  4.64  5.01  5.36  5.99  6.28  3.58  4.38  4.73  5.06  5.65  5.93
TCLE  2-1/2  7.12  8.71  9.41  10.06  11.25  11.80  6.97  8.54  9.23  9.86  11.03  11.56  6.62  8.11  8.76  9.36  10.47  10.98
TCLE  3-1/2  10.41  12.75  13.77  14.72  16.46  17.26  10.16  12.44  13.44  14.37  16.06  16.85  9.63  11.79  12.74  13.62  15.22  15.97
TCLE  5-1/2  15.08  18.47  19.95  21.33  23.84  25.01  14.73  18.04  19.48  20.83  23.28  24.42  13.98  17.13  18.50  19.77  22.11  23.19
TCLE  7-1/2  20.78  25.45  27.49  29.39  32.86  34.46  20.28  24.84  26.83  28.69  32.07  33.64  19.29  23.63  25.52  27.28  30.50  31.99
TCLE  9  25.06  30.70  33.16  35.44  39.63  41.56  24.46  29.96  32.36  34.59  38.68  40.56  23.26  28.48  30.77  32.89  36.77  38.57
TJL  9  22.20  27.18  29.36  31.39  35.09  36.81  21.70  26.58  28.71  30.69  34.31  35.99  20.60  25.23  27.25  29.14  32.58  34.17
TJL  11  28.32  34.68  37.46  40.05  44.78  46.96  27.65  33.86  36.57  39.10  43.71  45.85  26.27  32.17  34.75  37.15  41.53  43.56
                    Refrigerant Liquid Temperature °F
      0 10 20 30 40 50 60 70 80  90 100 110 120 130 140
  R-12 Correction Factor     1.60 1.54 1.48  1.42 1.36 1.30 1.24  1.18 1.12  1.06 1.00  .94  .88  .82  .75
  R-134a Correction Factor     1.70 1.63 1.56  1.49 1.42 1.36 1.29  1.21 1.14  1.07 1.00  .93  .85  .78  .71
  R-22 Correction Factor     1.56 1.51 1.45  1.40 1.34 1.29 1.23  1.17 1.12  1.06 1.00  .94  .88  .82  .76
  R-404A/R-507 Correction     2.00 1.90  1.80  1.70 1.60 1.50  1.40  1.30  1.20  1.10 1.00  .90  .80  .70  .50
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an average evaporator temperature of 0°F.
However, they may be used for any evaporator temperature from ‑40°F to +40°F since the variation in the actual factors across this range is insignicant.
Refrigerant Liquid Temperature Correction Factors