Brochure
 73
TXV Extended Capacity Tables
      Evaporator Temperature
  -20°C  -30°C  -40°C
  Nominal  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve (kPa)
Valve Type  Rating  400  600  700  800  1000  1100  600  700  800  1000  1100  1200  600  700   800  1000  1100  1200
AA/AN/AFA  1/5  0.46  0.56  0.61  0.65  0.73  0.76  0.35  0.38  0.41  0.46  0.48  0.50  0.25  0.27  0.29  0.32  0.34  0.35
AA/AN/AAC/ANC  1/4  0.81  1.00  1.08  1.15  1.29  1.35  0.64  0.69  0.74  0.82  0.86  0.90  0.42  0.46  0.49  0.55  0.58  0.60
AA/AN/AAC/ANC/AFA  1/2  1.42  1.73  1.87  2.00  2.24  2.35  1.13  1.22  1.31  1.46  1.53  1.60  0.74  0.80  0.86  0.96  1.01  1.05
AA/AN/AAC/ANC/AFA  1  2.27  2.77  3.00  3.20  3.58  3.76  1.81  1.95  2.08  2.33  2.44  2.55  1.20  1.30  1.39  1.55  1.63  1.70
AA/AN/AAC/ANC/AFA  1-1/2  3.22  3.95  4.26  4.56  5.09  5.34  2.58  2.79  2.98  3.34  3.50  3.65  1.70  1.84  1.96  2.19  2.30  2.40
AA/AN/AAC/ANC/AFA  2  4.78  5.85  6.32  6.76  7.56  7.93  3.79  4.09  4.37  4.89  5.13  5.36  2.51  2.71  2.90  3.24  3.40  3.55
AA/AN/AAC/ANC/AFA  2-1/2  6.69  8.19  8.85  9.46  10.58  11.10  5.35  5.77  6.17  6.90  7.24  7.56  3.50  3.79  4.05  4.52  4.75  4.96
AA/AN/AAC/ANC/AFA  3  8.18  10.02  10.82  11.56  12.93  13.56  6.55  7.07  7.56  8.45  8.87  9.26  4.32  4.66  4.99  5.58  5.85  6.11
AA/AN/AAC/ANC  4  9.74  11.92  12.88  13.77  15.39  16.14  7.75  8.37  8.95  10.01  10.50  10.96  5.10  5.51  5.89  6.58  6.90  7.21
AA/AN/AAC/ANC/AFA  5  13.28  16.26  17.56  18.77  20.99  22.01  10.62  11.47  12.26  13.71  14.38  15.02  6.97  7.53  8.05  9.00  9.44  9.86
TCLE  1/2  1.20  1.47  1.59  1.70  1.90  2.00  0.96  1.03  1.10  1.23  1.29  1.35  0.64  0.69  0.74  0.82  0.86  0.90
TCLE  1  2.30  2.82  3.04  3.25  3.64  3.82  1.84  1.99  2.13  2.38  2.49  2.60  1.20  1.30  1.39  1.55  1.63  1.70
TCLE  2  4.60  5.64  6.09  6.51  7.28  7.63  3.68  3.98  4.25  4.75  4.98  5.21  2.44  2.64  2.82  3.15  3.31  3.45
TCLE  3  8.50  10.41  11.24  12.02  13.43  14.09  6.80  7.34  7.85  8.77  9.20  9.61  4.46  4.82  5.15  5.76  6.04  6.31
TCLE  5  12.39  15.17  16.39  17.52  19.59  20.55  9.88  10.67  11.40  12.75  13.37  13.97  6.51  7.04  7.52  8.41  8.82  9.21
TCLE  7-1/2  17.98  22.02  23.79  25.43  28.43  29.82  14.34  15.49  16.55  18.51  19.41  20.28  9.45  10.21  10.91  12.20  12.80  13.37
TCLE  10  24.78  30.35  32.78  35.04  39.18  41.09  19.79  21.37  22.85  25.55  26.79  27.99  13.03  14.07  15.04  16.82  17.64  18.42
TCLE  12  29.88  36.59  39.52  42.25  47.24  49.55  23.86  25.77  27.55  30.80  32.31  33.74  15.72  16.98  18.15  20.29  21.28  22.23 
TJL  11  26.48  32.43  35.03  37.45  41.87  43.91  21.13  22.83  24.40  27.28  28.62  29.89  13.91  15.03  16.06  17.96  18.84  19.67
TJL  14  33.77  41.36  44.68  47.76  53.40  56.00  26.97  29.14  31.15  34.82  36.52  38.15  17.77  19.19  20.52  22.94  24.06  25.13
R-22 Conventional Valves (kWatts) – A Series, T Series
      Evaporator Temperature
  10°C  0°C  -10°C
  Nominal  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve (kPa)  Pressure Drop Across Valve (kPa)
Valve Type  Rating 400 600 700 800 1000 1100 400  600 700 800 1000 1100 400  600 700 800 1000 1100
AA/AN/AFA  1/5  0.53  0.65  0.70  0.75  0.84  0.88  0.52  0.64  0.69  0.74  0.82  0.86  0.50  0.61  0.66  0.70  0.78  0.82
AA/AN/AAC/ANC  1/4  0.92  1.13  1.22  1.30  1.46  1.53  0.90  1.11  1.20  1.28  1.43  1.50  0.89  1.08  1.17  1.25  1.40  1.47
AA/AN/AAC/ANC/AFA  1/2  1.63  1.99  2.15  2.30  2.57  2.70  1.59  1.95  2.10  2.25  2.51  2.64  1.56  1.91  2.06  2.20  2.46  2.58
AA/AN/AAC/ANC/AFA  1  2.58  3.16  3.42  3.65  4.09  4.29  2.55  3.12  3.37  3.61  4.03  4.23  2.48  3.03  3.28  3.50  3.92  4.11
AA/AN/AAC/ANC/AFA  1-1/2  3.72  4.55  4.92  5.26  5.88  6.16  3.65  4.47  4.82  5.16  5.77  6.05  3.58  4.38  4.73  5.06  5.65  5.93
AA/AN/AAC/ANC/AFA  2  5.45  6.68  7.21  7.71  8.62  9.04  5.37  6.58  7.11  7.60  8.50  8.91  5.24  6.42  6.93  7.41  8.28  8.69
AA/AN/AAC/ANC/AFA  2-1/2  7.65  9.36  10.12  10.81  12.09  12.68  7.54  9.24  9.98  10.66  11.92  12.50  7.36  9.02  9.74  10.41  11.64  12.21
AA/AN/AAC/ANC/AFA  3  9.38  11.49  12.41  13.27  14.83  15.56  9.24  11.32  12.22  13.07  14.61  15.32  9.03  11.06  11.94  12.77  14.27  14.97
AA/AN/AAC/ANC  4  11.12  13.61  14.70  15.72  17.58  18.43  10.97  13.43  14.51  15.51  17.34  18.19  10.73  13.14  14.19  15.17  16.96  17.79
AA/AN/AAC/ANC/AFA  5  15.22  18.64  20.14  21.53  24.07  25.24  15.00  18.37  19.84  21.21  23.72  24.87  14.66  17.95  19.39  20.73  23.17  24.30
TCLE  1/2  1.38  1.69  1.83  1.95  2.18  2.29  1.37  1.68  1.81  1.94  2.17  2.27  1.35  1.65  1.78  1.90  2.13  2.23
TCLE  1  2.62  3.21  3.47  3.70  4.14  4.34  2.58  3.16  3.41  3.65  4.08  4.27  2.51  3.08  3.32  3.55  3.97  4.17
TCLE  2  5.27  6.46  6.98  7.46  8.34  8.75  5.21  6.38  6.89  7.37  8.24  8.64  5.10  6.24  6.74  7.21  8.06  8.45
TCLE  3  9.74  11.92  12.88  13.77  15.39  16.14  9.60  11.75  12.70  13.57  15.17  15.92  9.38  11.49  12.41  13.27  14.83  15.56
TCLE  5  14.20  17.39  18.78  20.08  22.44  23.54  13.98  17.13  18.50  19.78  22.11  23.19  13.66  16.74  18.08  19.32  21.61  22.66
TCLE  7-1/2  20.60  25.23  27.25  29.14  32.58  34.17  20.35  24.92  26.92  28.77  32.17  33.74  19.82  24.28  26.22  28.04  31.34  32.87
TCLE  10  28.39  34.77  37.56  40.15  44.89  47.08  28.05  34.36  37.11  39.67  44.35  46.52  27.33  33.47  36.15  38.65  43.21  45.32
TCLE  12  34.23  41.93  45.28  48.41  54.13  56.77  33.81  41.41  44.73  47.81  53.46  56.07  32.96  40.36  43.60  46.61  52.11  54.65
TJL  11  30.34  37.16  40.13  42.90  47.97  50.31  29.97  36.71  39.65  42.39  47.39  49.70  29.21  35.77  38.63  41.30  46.18  48.43
TJL  14  38.66  47.34  51.14  54.67  61.12  64.11  38.22  46.82  50.57  54.06  60.44  63.39  37.24  45.61  49.26  52.67  58.88  61.76
  Refrigerant Liquid Temperature °F
      0  10  20 30 40 50  60  70 80 90 100 110 120 130 140
  R-12 Correction Factor     1.60  1.54  1.48 1.42 1.36 1.30  1.24 1.18 1.12 1.06 1.00  .94  .88  .82  .75
  R-134a Correction Factor     1.70 1.63  1.56 1.49 1.42 1.36  1.29 1.21 1.14 1.07 1.00  .93  .85  .78  .71
  R-22 Correction Factor     1.56  1.51  1.45 1.40 1.34 1.29  1.23 1.17 1.12 1.06 1.00  .94  .88  .82  .76
  R-404A/R-507 Correction     2.00  1.90  1.80 1.70 1.60 1.50  1.40 1.30 1.20 1.10 1.00  .90  .80  .70  .50
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an average evaporator temperature of 0°F.
However, they may be used for any evaporator temperature from ‑40°F to +40°F since the variation in the actual factors across this range is insignicant.
Refrigerant Liquid Temperature Correction Factors