TXV Extended Capacity Tables
Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors
Refrigerant Liquid Temperature °F
50 60 70 80 90 100 110 120 130 140
R-410A Correction Factor 1.37 1.30 1.23 1.15 1.08 1.00 0.92 0.84 0.75 0.65
These factors include corrections for liquid refrigerant density and net refrigeration effect, and are based on an average evaporator temperature of 0°F with a maximum 7°F Change in
Superheat. However, they may be used for any evaporator temperature from ‑40°F to +40°F since the variation in the actual factors across this range is insignicant.
R-410A Balanced Ported Valves (Tons) – NXT Series
Valve Type
Nominal
Rating
Tons
Evaporator Temperature
50 ºF 40 ºF 20 ºF
Pressure Drop Across Valve (PSI) Pressure Drop Across Valve (PSI) Pressure Drop Across Valve (PSI)
75 110 140 160 210 240 285 75 110 140 160 210 240 285 75 110 140 160 210 240 285
NXT-Series
1/2 0.4 0.5 0.5 0.6 0.6 0.7 0.8 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.4 0.5 0.5 0.5 0.6 0.7 0.7
1 0.7 0.8 0.9 1.0 1.2 1.2 1.3 0.7 0.8 0.9 1.0 1.1 1.2 1.3 0.7 0.8 0.9 1.0 1.1 1.2 1.3
1-1/2 1.0 1.3 1.4 1.5 1.7 1.9 2.0 1.0 1.2 1.4 1.5 1.7 1.8 2.0 1.0 1.2 1.4 1.5 1.7 1.8 2.0
2 1.4 1.7 1.9 2.0 2.3 2.5 2.7 1.4 1.7 1.9 2.0 2.3 2.4 2.7 1.3 1.6 1.8 2.0 2.2 2.4 2.6
3 2.1 2.5 2.8 3.0 3.5 3.7 4.0 2.1 2.5 2.8 3.0 3.4 3.7 4.0 2.0 2.4 2.7 2.9 3.4 3.6 3.9
4 2.8 3.3 3.8 4.0 4.6 4.9 5.4 2.7 3.3 3.7 4.0 4.6 4.9 5.3 2.7 3.2 3.7 3.9 4.5 4.8 5.2
5 3.5 4.2 4.7 5.0 5.8 6.2 6.7 3.4 4.1 4.7 5.0 5.7 6.1 6.7 3.3 4.1 4.6 4.9 5.6 6.0 6.5
6 4.1 5.0 5.7 6.1 6.9 7.4 8.1 4.1 5.0 5.6 6.0 6.9 7.3 8.0 4.0 4.9 5.5 5.9 6.7 7.2 7.8
7 4.8 5.9 6.6 7.1 8.1 8.6 9.4 4.8 5.8 6.5 7.0 8.0 8.6 9.3 4.7 5.7 6.4 6.8 7.8 8.4 9.1
8 5.8 7.0 7.9 8.5 9.7 10.4 11.3 5.7 7.0 7.8 8.4 9.6 10.3 11.2 5.6 6.8 7.7 8.2 3.4 10.1 11.0
10 7.1 8.6 9.7 10.4 11.9 12.7 13.9 7.1 8.5 9.6 10.3 11.8 12.6 13.8 6.9 8.4 9.4 10.1 11.6 12.4 13.5
12 8.7 10.6 11.9 12.7 14.6 15.6 17.0 8.6 10.5 11.8 12.6 14.5 15.5 16.9 8.5 10.2 11.6 12.4 14.2 15.1 16.5
15 10.2 12.4 14.0 14.9 17.1 18.3 19.9 10.1 12.3 13.8 14.8 16.9 18.1 19.7 9.9 12.0 13.5 14.5 16.6 17.7 19.3
Valve Type
Nominal
Rating
Tons
Evaporator Temperature
0 ºF -20 ºF -40 ºF
Pressure Drop Across Valve (PSI) Pressure Drop Across Valve (PSI) Pressure Drop Across Valve (PSI)
75 110 140 160 210 240 285 75 110 140 160 210 240 285 75 110 140 160 210 240 285
NXT-Series
1/2 0.4 0.4 0.5 0.5 0.6 0.7 0.7 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.3 0.4 0.5 0.6 0.6 0.6 0.7
1 0.7 0.8 0.9 1.0 1.1 1.2 1.3 0.6 0.6 0.9 0.9 1.1 1.1 1.2 0.6 0.7 0.8 0.9 1.0 1.1 1.2
1-1/2 1.0 1.2
1.3 1.4 1.6 1.8 1.9 0.9 1.1 1.3 1.4 1.6 1.7 1.8 0.9 1.1 1.2 1.3 1.5 1.6 1.8
2 1.3 1.6 1.8 1.9 2.2 2.3 2.5 1.3 1.5 1.7 1.8 2.1 2.3 2.5 1.2 1.5 1.7 1.8 2.0 2.2 2.4
3 2.0 2.4 2.7 2.9 3.3 3.5 3.8 1.9 2.3 2.6 2.8 3.2 3.4 3.7 1.8 2.2 2.5 2.7 3.1 3.3 3.6
4 2.6 3.2 3.6 3.8 4.4 4.7 5.1 2.5 3.1 3.5 3.7 4.2 4.5 4.9 2.4 3.0 3.3 3.6 4.1 4.4 4.8
5 3.3 3.9 4.5 4.8 5.5 5.8 6.4 3.2 3.8 4.3 4.6 5.3 5.7 6.2 3.0 3.7 4.2 4.5 5.1 5.5 5.9
6 3.9 4.7 5.3 5.7 6.5 7.0 7.6 3.8 4.6 5.2 5.5 6.3 6.8 7.4 3.7 4.4 5.0 5.3 6.1 6.5 7.1
7 4.8 5.9 6.6 6.7 8.1 8.6 9.4 4.4 5.4 6.0 6.5 7.4 7.9 8.6 4.3 5.2 5.8 6.2 7.1 7.6 8.3
8 5.5 6.6 7.5 8.0 9.2 9.8 10.7 5.3 6.4 7.2 7.7 8.9 9.5 10.3 5.1 6.2 7.0 7.5 8.6 9.2 10.0
10 6.7 8.1 9.2 9.8 11.3 12.0 13.1 6.5 7.9 8.9 9.5 10.9 11.7 12.7 6.3 7.6 8.6 9.2 10.5 11.2 12.3
12 8.2 10.0 11.3 12.0 13.8 14.7 16.1 8.0 9.7 10.9 11.7 13.4 14.3 15.6 7.7 9.3 10.5 11.2 12.9 13.8 15.0
15 9.6 11.7 13.2 14.1 16.1 17.3 18.8 9.3 11.3 12.8 13.7 15.6 16.7 18.2 9.0 10.3 12.3 13.2 15.1 15.1 17.6
Note: Standard capacity is rated at 100 ºF liquid inlet and 40 ºF evap temperature; with 160 Psi pressure drop across TXV per ARI-750-2001.
These ratings assume vapor free liquid entering the thermal expansion valve.