TXV Extended Capacity Tables
R-404A/R-507 Balanced Ported Valves (Tons)– B, HF, TFE, TRAE and T Series
Evaporator Temperature
50°F 40°F 20°F
Nominal Pressure Drop Across Valve (PSI) Pressure Drop Across Valve (PSI) Pressure Drop Across Valve (PSI)
Valve Type Rating 60 80 100 125 150 175 60 80 100 125 150 175 60 80 100 125 150 175
BA/BN 1/4 0.29 0.33 0.37 0.42 0.46 0.50 0.28 0.32 0.36 0.40 0.44 0.48 0.27 0.31 0.35 0.39 0.43 0.46
BA/BN 1/2 0.55 0.64 0.71 0.79 0.87 0.94 0.53 0.61 0.68 0.76 0.84 0.91 0.51 0.59 0.66 0.74 0.81 0.87
BA/BN 1 0.85 0.98 1.10 1.23 1.34 1.45 0.83 0.96 1.07 1.20 1.31 1.42 0.79 0.91 1.02 1.14 1.25 1.35
BA/BN 1-1/4 1.14 1.32 1.47 1.65 1.80 1.95 1.11 1.28 1.43 1.60 1.76 1.90 1.06 1.22 1.37 1.53 1.68 1.81
BA/BN 1-1/2 1.44 1.66 1.86 2.08 2.28 2.46 1.41 1.63 1.82 2.04 2.23 2.41 1.34 1.55 1.73 1.93 2.12 2.29
BA/BN 2 1.74 2.01 2.25 2.51 2.75 2.97 1.70 1.96 2.19 2.45 2.69 2.90 1.62 1.87 2.09 2.34 2.56 2.77
BA/BN 2-1/2 2.26 2.61 2.92 3.26 3.57 3.86 2.20 2.54 2.84 3.18 3.48 3.76 2.09 2.41 2.70 3.02 3.30 3.57
BA/BN 3 2.85 3.29 3.68 4.11 4.51 4.87 2.79 3.22 3.60 4.03 4.41 4.76 2.65 3.06 3.42 3.82 4.19 4.53
BA/BN 4 3.55 4.10 4.58 5.12 5.61 6.06 3.47 4.01 4.48 5.01 5.49 5.93 3.29 3.80 4.25 4.75 5.20 5.62
HF 1/8 0.16 0.18 0.21 0.23 0.25 0.27 0.16 0.18 0.21 0.23 0.25 0.27 0.15 0.17 0.19 0.22 0.24 0.26
HF 1/4 0.31 0.36 0.40 0.45 0.49 0.53 0.30 0.35 0.39 0.43 0.47 0.51 0.28 0.32 0.36 0.40 0.44 0.48
HF 1/2 0.55 0.64 0.71 0.79 0.87 0.94 0.53 0.61 0.68 0.76 0.84 0.91 0.51 0.59 0.66 0.74 0.81 0.87
HF 1 0.83 0.96 1.07 1.20 1.31 1.42 0.82 0.95 1.06 1.18 1.30 1.40 0.77 0.89 0.99 1.11 1.22 1.32
HF 1-1/4 1.12 1.29 1.45 1.62 1.77 1.91 1.10 1.27 1.42 1.59 1.74 1.88 1.04 1.20 1.34 1.50 1.64 1.78
HF 1-1/2 1.44 1.66 1.86 2.08 2.28 2.46 1.41 1.63 1.82 2.04 2.23 2.41 1.34 1.55 1.73 1.93 2.12 2.29
HF 2 1.90 2.19 2.45 2.74 3.00 3.24 1.86 2.15 2.40 2.68 2.94 3.18 1.76 2.03 2.27 2.54 2.78 3.01
HF 3-1/2 3.38 3.90 4.36 4.88 5.34 5.77 3.30 3.81 4.26 4.76 5.22 5.64 3.13 3.61 4.04 4.52 4.95 5.35
HF 5 4.70 5.43 6.07 6.78 7.43 8.03 4.59 5.30 5.93 6.63 7.26 7.84 4.36 5.03 5.63 6.29 6.89 7.45
HF 7 5.95 6.87 7.68 8.59 9.41 10.16 5.81 6.71 7.50 8.39 9.19 9.92 5.52 6.37 7.13 7.97 8.73 9.43
HF 10 8.83 10.20 11.40 12.75 13.96 15.08 8.62 9.95 11.13 12.44 13.63 14.72 8.19 9.46 10.57 11.82 12.95 13.99
HF 13 11.62 13.42 15.00 16.77 18.37 19.84 11.35 13.11 14.65 16.38 17.95 19.38 10.78 12.45 13.92 15.56 17.04 18.41
TFE 5 4.62 5.33 5.96 6.67 7.30 7.89 4.51 5.21 5.82 6.51 7.13 7.70 4.28 4.94 5.53 6.18 6.77 7.31
TFE 7 6.32 7.30 8.16 9.12 9.99 10.79 6.17 7.12 7.97 8.91 9.76 10.54 5.86 6.77 7.57 8.46 9.27 10.01
TFE 9 7.84 9.05 10.12 11.32 12.40 13.39 7.66 8.85 9.89 11.06 12.11 13.08 7.28 8.41 9.40 10.51 11.51 12.43
TFE 14 11.98 13.83 15.47 17.29 18.94 20.46 11.70 13.51 15.10 16.89 18.50 19.98 11.11 12.83 14.34 16.04 17.57 18.97
TRAE+ 8 6.79 7.84 8.77 9.80 10.74 11.60 6.63 7.66 8.56 9.57 10.48 11.32 6.30 7.27 8.13 9.09 9.96 10.76
TRAE+ 12 9.90 11.43 12.78 14.29 15.65 16.91 9.67 11.17 12.48 13.96 15.29 16.51 9.19 10.61 11.86 13.26 14.53 15.69
TRAE+ 14 11.05 12.76 14.27 15.95 17.47 18.87 10.79 12.46 13.93 15.57 17.06 18.43 10.25 11.84 13.23 14.79 16.21 17.51
TRAE+ 20 16.75 19.34 21.62 24.18 26.48 28.61 16.36 18.89 21.12 23.61 25.87 27.94 15.54 17.94 20.06 22.43 24.57 26.54
TRAE+ 30 23.02 26.58 29.72 33.23 36.40 39.31 22.49 25.97 29.03 32.46 35.56 38.41 21.36 24.66 27.58 30.83 33.77 36.48
TRAE 35 31.08 35.89 40.12 44.86 49.14 53.08 30.36 35.06 39.19 43.82 48.00 51.85 28.84 33.30 37.23 41.63 45.60 49.25
TRAE 40 33.90 39.14 43.76 48.93 53.60 57.90 33.11 38.23 42.74 47.79 52.35 56.55 31.45 36.32 40.60 45.39 49.73 53.71
TRAE 50 40.34 46.58 52.08 58.23 63.78 68.89 39.41 45.51 50.88 56.88 62.31 67.31 37.44 43.23 48.33 54.04 59.20 63.94
TJR 9 8.46 9.77 10.92 12.21 13.38 14.45 8.26 9.54 10.66 11.92 13.06 14.11 7.85 9.06 10.13 11.33 12.41 13.41
TJR 12 10.13 11.70 13.08 14.62 16.02 17.30 9.89 11.42 12.77 14.27 15.64 16.89 9.40 10.85 12.14 13.57 14.86 16.05
TER 14 12.66 14.62 16.34 18.27 20.02 21.62 12.37 14.28 15.97 17.85 19.56 21.13 11.75 13.57 15.17 16.96 18.58 20.07
TER 16 14.96 17.27 19.31 21.59 23.65 25.55 14.62 16.88 18.87 21.10 23.12 24.97 13.88 16.03 17.92 20.03 21.95 23.70
TER 21 20.14 23.26 26.00 29.07 31.84 34.40 19.68 22.72 25.41 28.41 31.12 33.61 18.69 21.58 24.13 26.98 29.55 31.92
TER 27 25.90 29.91 33.44 37.38 40.95 44.23 25.30 29.21 32.66 36.52 40.00 43.21 24.03 27.75 31.02 34.68 37.99 41.04
TIR 37 31.65 36.55 40.86 45.68 50.04 54.05 30.92 35.70 39.92 44.63 48.89 52.81 29.37 33.91 37.92 42.39 46.44 50.16
THR 48 40.29 46.52 52.01 58.15 63.70 68.81 39.35 45.44 50.80 56.80 62.22 67.20 37.38 43.16 48.26 53.95 59.10 63.84
THR 60 48.92 56.49 63.16 70.61 77.35 83.55 47.78 55.17 61.68 68.96 75.55 81.60 45.39 52.41 58.60 65.51 71.77 77.52
TMR 60 57.55 66.45 74.30 83.07 90.99 98.29 56.22 64.92 72.58 81.15 88.89 96.01 53.40 61.66 68.94 77.08 84.43 91.20
Refrigerant Liquid Temperature °F
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140
R-12 Correction Factor 1.60 1.54 1.48 1.42 1.36 1.30 1.24 1.18 1.12 1.06 1.00 .94 .88 .82 .75
R-134a Correction Factor 1.70 1.63 1.56 1.49 1.42 1.36 1.29 1.21 1.14 1.07 1.00 .93 .85 .78 .71
R-22 Correction Factor 1.56 1.51 1.45 1.40 1.34 1.29 1.23 1.17 1.12 1.06 1.00 .94 .88 .82 .76
R-404A/R-507 Correction Factor 2.00 1.90 1.80 1.70 1.60 1.50 1.40 1.30 1.20 1.10 1.00 .90 .80 .70 .50
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an average evaporator temperature of 0°F.
However, they may be used for any evaporator temperature from ‑40°F to +40°F since the variation in the actual factors across this range is insignicant.
Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors
Note: Standard capacity is rated at 100F liquid inlet and 40F evaporator temperature; with 100 Psi pressure drop across the TXV per ARI 750-2001.